Permit: T09CM02572

Parcel: 10705121A

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
01/25/2011 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
1) RECEIVED LETTER FROM ARCHITECT FOR LIGHT POLES
11/05/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) COMPLETE TRIM OUT FOR FINAL INSPECTION
2) RECALL INSPECTION AND HAVE ELECTRICIAN ON SITE TO REMOVE COVERS FOR INSPECTION
3) NEED TO ADDRESS ALUM. CONDUCTORS
07/30/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) CONTRACTOR OF RECORD RESPONSIBLE TO LOCK OUT TAG OUT
2) DISCONNECTS OR PANELS NOT YET APPROVED BY INSPECTOR
3) ONLY AUTHORIZED PERSONS TO HAVE ACCESS TO ELECTRICAL EQUIPMENT
07/29/2010 ELECTRIC - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE INSPECTION
2) TAPED SPLIT BOLTS NEED TO BE TAPED PROPERLY TO EQUAL MANUFACTURES INSULATION
3) TERMINATE ENDS OF 500 MCM FUTURE CONDUCTORS IN APPROVED MANNER
4) INSTALL WEDGE OR SOMETHING TO KEEP CONDUCTORS FROM PUSHING AGAINST GUTTER COVER
07/26/2010 ELECTRIC - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLANS CALL FOR 2 SETS 500 MCM FROM CT-TO GUTTER
2) SECONDARYS NOT INSTALLED
07/13/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) NEUTRALS NOT RUN TO SERVICE DISCONNECT AS REQUIRED PER CODE
2) SERVICE EQUIPMENT NOT PER PLAN
3) GROUNDS OR BOND JUMPERS ON SUPPLY SIDE PER 250.56
06/18/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/15/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) INSTALL NAIL PLATES TO PROTECT CABLES LESS 1 1/4" FROM FACE OF STUD
2) NEED TO CHECK INTER LOCK FOR KITCHEN EQUIPMENT-SEE NOTES ON SHEET E.6 DIA. #1
3) OK WALLS AND CEILING AT NEW BLDG EXCEPT KITCHEN
04/30/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK 2" AND 2 1/2" POWER & DATA NEW FEED TO OFFICE AREA, WILL REVISE PLAN
2) SUPPORT MC PER CODE 12" AND 6'