Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2011 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* 1) RECEIVED LETTER FROM ARCHITECT FOR LIGHT POLES |
|
| 11/05/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) COMPLETE TRIM OUT FOR FINAL INSPECTION 2) RECALL INSPECTION AND HAVE ELECTRICIAN ON SITE TO REMOVE COVERS FOR INSPECTION 3) NEED TO ADDRESS ALUM. CONDUCTORS |
|
| 07/30/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) CONTRACTOR OF RECORD RESPONSIBLE TO LOCK OUT TAG OUT 2) DISCONNECTS OR PANELS NOT YET APPROVED BY INSPECTOR 3) ONLY AUTHORIZED PERSONS TO HAVE ACCESS TO ELECTRICAL EQUIPMENT |
|
| 07/29/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE INSPECTION 2) TAPED SPLIT BOLTS NEED TO BE TAPED PROPERLY TO EQUAL MANUFACTURES INSULATION 3) TERMINATE ENDS OF 500 MCM FUTURE CONDUCTORS IN APPROVED MANNER 4) INSTALL WEDGE OR SOMETHING TO KEEP CONDUCTORS FROM PUSHING AGAINST GUTTER COVER |
|
| 07/26/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLANS CALL FOR 2 SETS 500 MCM FROM CT-TO GUTTER 2) SECONDARYS NOT INSTALLED |
|
| 07/13/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) NEUTRALS NOT RUN TO SERVICE DISCONNECT AS REQUIRED PER CODE 2) SERVICE EQUIPMENT NOT PER PLAN 3) GROUNDS OR BOND JUMPERS ON SUPPLY SIDE PER 250.56 |
|
| 06/18/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/15/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) INSTALL NAIL PLATES TO PROTECT CABLES LESS 1 1/4" FROM FACE OF STUD 2) NEED TO CHECK INTER LOCK FOR KITCHEN EQUIPMENT-SEE NOTES ON SHEET E.6 DIA. #1 3) OK WALLS AND CEILING AT NEW BLDG EXCEPT KITCHEN |
|
| 04/30/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK 2" AND 2 1/2" POWER & DATA NEW FEED TO OFFICE AREA, WILL REVISE PLAN 2) SUPPORT MC PER CODE 12" AND 6' |