Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2011 | FIRE - FINAL | Denied | Not approved 4/12// 1.) Need hood final 2.) Life/safety inspection already conducted and approved 3.) OK for TCO. OK for kitchen opperations but not can not operate cooking appliances located under the hood. 4.) Must post bond for TCO. |
|
| 04/13/2011 | FIRE - FINAL | Approved | CARD SIGNED ON REINSPECT | |
| 04/11/2011 | FIRE - FINAL | Not ready for Inspection | Cintas was not on property to do hood final | |
| 04/07/2011 | FIRE - FINAL | Not ready for Inspection | Not ready 4/7/11 | |
| 03/30/2011 | FIRE - FINAL | Denied | Not approved 3/30/11 1.) Need to correct violations on items number: 1-3-7-8-9-10. 2.) Need panic hardware for door in the "Child Care" room. 3.) Both leafs on main door must open when pusing the"panic hardware" bar. 4.) Fire alarm system was installed without permit and without submitting plans. 5.) Must submit plans to Fire dept.for review and approval. 6.) Must obtain a permit. 7.) Fire Alarm system acceptance test must be conducted and approved. |
|
| 02/24/2011 | FIRE - FINAL | Denied | Not approved 2/24/11 1.) Need address numbers for the building. Must be readily visible from the street. Must be a minimum of 15 inches tall and the numbers must contrast with the background color 2.) Must provide panic hardware on all exterior doors except for the single office door and for the rear kitchen door. 3.) Front room, east side of corridor next to main entry, door sticks, hard to close and open. 4.) Door latch handles must open readily without the use of special knowledge. 5.) Remove the exit sign over door leading into the "Child Care" room. 6.) Provide a "directional" illuminated exit sign in corridor leading to the "east" wall exit door. 7.) Place a "Not An Exit" sign over the double doors that lead from the large multi-use room into the front area of the building. 8.) Need Fire Aarm final inspection. 9.) Need Hood final inspection 10.) Hood system must be incorporated with the Fire Alarm system. |