Permit: T09CM02572

Parcel: 10705121A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/06/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/30/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) AIR BALANCE OK
2) CAPTURE AND CONTAINMENT OK
3) FINISH ITEMS #8, 10 & 12
4) HEAT SENSOR TEST OK
02/24/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) NEED TO TEST HEAT SENSOR
2) NEED CAPTURE AND COTAINMENT TEST
3) PROVIDE AIR BALANCE REPORT
4) PROVIDE HIGH COMBUSTION AIR OPENING FOR WATER HEATER
5) 1/2" I.D. X 18" GAS FLEX NOT ADEQUATE FOR 180,000 BTU WATER HEATER
6) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. DO NOT USE DUCT TAPE OUTDOORS
7) SECURE CONDENSOR TO SLEEPERS
8) PROVIDE ECONOMIZERS AS PER PLANS
9) PERMANENTLY I.D. ALL EQUIPMENT ON ROOF
10) PROVIDE HINGE KIT AND GASKET FOR TYPE I FAN
11) STRAIGHTEN THE DRAIN SPOUT ON TYPE I FAN
12) STRAIGHTEN THE DRAIN SPOUT IN TYPE I FAN AND PROVIDE GREASE RECEPTOR
13) BATHROOM EXHAUST FANS AND A/C FANS MUST RUN CONTINOUSLY DURING OCCUPIED HOURS