Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 03/30/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) AIR BALANCE OK 2) CAPTURE AND CONTAINMENT OK 3) FINISH ITEMS #8, 10 & 12 4) HEAT SENSOR TEST OK |
|
| 02/24/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED TO TEST HEAT SENSOR 2) NEED CAPTURE AND COTAINMENT TEST 3) PROVIDE AIR BALANCE REPORT 4) PROVIDE HIGH COMBUSTION AIR OPENING FOR WATER HEATER 5) 1/2" I.D. X 18" GAS FLEX NOT ADEQUATE FOR 180,000 BTU WATER HEATER 6) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. DO NOT USE DUCT TAPE OUTDOORS 7) SECURE CONDENSOR TO SLEEPERS 8) PROVIDE ECONOMIZERS AS PER PLANS 9) PERMANENTLY I.D. ALL EQUIPMENT ON ROOF 10) PROVIDE HINGE KIT AND GASKET FOR TYPE I FAN 11) STRAIGHTEN THE DRAIN SPOUT ON TYPE I FAN 12) STRAIGHTEN THE DRAIN SPOUT IN TYPE I FAN AND PROVIDE GREASE RECEPTOR 13) BATHROOM EXHAUST FANS AND A/C FANS MUST RUN CONTINOUSLY DURING OCCUPIED HOURS |