Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Apply Date:
01/25/2007
Applicant:
N/A
Description:
TI: RESTAURANT- TACOS & SNOW CONES
Architects:
  • DOMINGUEZ, PORFIRIO
Contractors:
  • ARIZONA RESTAURANT SUPPLY INC
  • ARIZONA STYLE CONSTRUCTION
  • SUPER DRAIN ROOTER AND PLUMBERS INC *C

Permit Reviews

Permit Number - T07CM00308
Permit Status: C of o
Permit Description: TI: RESTAURANT- TACOS & SNOW CONES
Start Date Submittal Complete Date Status  
01/25/2007 PLANS OK TO SUBMIT - COMM 01/26/2007 COMPLETED Review Details
01/25/2007 PLANS OK TO SUBMIT - SITE 01/26/2007 COMPLETED Review Details
01/26/2007 COMMERCIAL TI 03/12/2007 COMPLETED Review Details
01/26/2007 SITE 03/12/2007 COMPLETED Review Details
04/09/2007 RESUBMITTAL 06/20/2007 COMPLETED Review Details
04/09/2007 RESUBMITTAL - SITE ALL 05/07/2007 COMPLETED Review Details
05/07/2007 RESUBMITTAL 07/18/2007 COMPLETED Review Details
06/20/2007 RESUBMITTAL - SITE ALL 07/18/2007 COMPLETED Review Details
07/20/2007 COMMERCIAL TI 07/25/2007 COMPLETED Review Details
07/20/2007 RESUBMITTAL - SITE ALL 07/27/2007 COMPLETED Review Details
07/25/2007 RESUBMITTAL 07/27/2007 COMPLETED Review Details
07/27/2007 RESUBMITTAL 08/08/2007 COMPLETED Review Details
10/05/2007 REVISION - SITE 10/08/2007 COMPLETED Review Details
11/14/2007 REVISION - - 1ST 11/14/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07CM00308
Permit Status: C of o
Permit Description: TI: RESTAURANT- TACOS & SNOW CONES
Total Outstanding Activity Conditions - 1
Date Name
01/25/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T07CM00308
Permit Description: TI: RESTAURANT- TACOS & SNOW CONES
Total Completed Inspections - 27
Date Description Inspector Results Comments
09/17/2007 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*
09/19/2007 PLUMBING - GAS PRESSURE TEST RMYERS Approved IVRS - Inspection :*
09/19/2007 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
09/25/2007 ELECTRIC - ABOVE CEILING DSANTACR Approved IVRS - Inspection :*
- OK DINING AREA ONLY
- KITCHEN AREA NEEDS CABLING & BOXES TO BE COVERED AND SUPPORTED TO CODE. INSTALL SEISMIC WIRES ON GRID FIXTURES.
09/25/2007 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :*
09/27/2007 FRAMING AQUIROZ Approved IVRS - Inspection :*
10/03/2007 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
10/04/2007 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
10/05/2007 MECHANICAL - ABOVE CEILING JMILITEL Approved CONDENSATE CANNOT TERMINATE ONTO THE SIDEWALK
PROVIDE A VENT FOR WATER HEATER
OK FOR CEILING TILES
CHECKED WELDS ON GREASE DUCT. OK TO FIRE WRAP.
FIRE WRAP ON TOP OF HOOD MUST BE SECURED.
PROVIDE INSTALL INSTRUCTIONS.
10/17/2007 MECHANICAL - HOODS MRAMBER Approved IVRS - Inspection :*
GREASE DUCT WRAP OK
OK TO PROCEED WITH SUPPRESSION SYSTEM
10/26/2007 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*
10/26/2007 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*
11/06/2007 PLUMBING - INTERMEDIATE BBENEDON Approved IVRS - Inspection :*
FLANGES OK
PIPE INSULATION AT WH OK
WH HAS HEAT TRAP NIPPS
11/19/2007 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
12/06/2007 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :
See detailed listing on site.| 999*
INCREASE M.U.A TO WITHIN 10% OF DESIGN
PROVIDE GREASE TROUGH AT HOOD
PROVIDE SPACING ON CONDENSATE PIPING
PROVIDE BLOCKING ON ELEC. BOX
PROVIDE GREASE TROUGH ON ROOF
PROVIDE REQUIRED A/C EQUIPMENT ON ROOF
12/06/2007 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :
See detailed listing on site.| 999*
1. REVISE PANEL DIRECTORIES SO THEY ARE CORRECT, LEGIBLE AND NEAT, SPELLED CORRECTLY - NO SCRIBBLE
2. SERVICE DISCONNECT TO BE UNLOCKED
3. ALARM WIRING IN PROGRESS
4. MULTI-WIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES
5. PROVIDE DISCONNECTING MEANS FOR ICE MACHINE
6. FLEX NOT ALLOWED FOR DISPLAY CASES - IT IS SUBJECT TO PHYSICAL DAMAGE, BOXES AND RECEPTACLES NOT TO BE MOUNTED TO MOVABLE DISPLAY CASES

ON ROOFTOP
- AC 1 KINKED CONDUIT, LOOSE FITTINGS, NO STRAP, UNDERSIZED GROUND, DISCONNECT NOT TO BLOCK ACCESSIBLE COVER, PINCHED OPEN WIRING, MISSING K.O
CONTACTOR J-BOX NOT SEALED/SECURE SELF TAP SCREW NOT ALLOWED FOR GROUND, STRAP ALL FLEX.
12/11/2007 ENGINEERING - FINAL MRUSSO Approved 1) PROVIDE "ONEWAY " SIGNAGE" AS SHOWN ON PLAN, NOTE #29.
2) PROVIDE 6" WATER HARVESTING AREA WITH DRAINAGE TO WALL OPENING, NOTE #32.
3) COMPLETE LANDSCAPE WORK.
4) INSTALL WHEEL STOPS AS SHOWN ON PLAN - ADD PARKING SPACE TO NORTH SIDE OF BLDG.
5) PROVIDE TWO - CLASS II BICYCLE PARKING SPACES.
6) PROVIDE HC SIGN FOR PARKING SPACE.
7) INSTALL WEEP HOLES IN SCREEN WALL TO ALLOW FOR DRAINAGE, NOTE #38.
8) PROVIDE APPROVAL FROM ARCHETECT FOR CHANGES MADE TO THE 6' SCREEN WALL TO A 2' SCREEN WALL SEE NTE #28.
12/21/2007 NPPO - FINAL ACONNOR Approved
12/21/2007 LANDSCAPE - FINAL ACONNOR Approved
01/22/2008 HEALTH DEPT - FINAL 724-7908 RBROWNIN Approved
01/25/2008 FIRE - KITCHEN EXH HOOD FINAL LLAKEY Approved
01/25/2008 FIRE - FINAL LLAKEY Approved
01/28/2008 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
02/29/2008 SIGN - FINAL JYBARRA Approved
03/04/2008 BUILDING - PROGRESS AQUIROZ Approved IVRS - Inspection :*
04/01/2008 PERMIT FINALED LJACKSON Approved
04/01/2008 BUILDING - FINAL AQUIROZ Approved

Documents

File Name Document Type  
C OF O_04-01-2008.TIF CERT OF OCC VIEW
None DOCUMENTS VIEW
T07CM00308-R2_001.TIF CONSTRPLANS VIEW
T07CM00308-R_001.TIF CONSTRPLANS VIEW
T07CM00308_001.TIF CONSTRPLANS VIEW
T07CM00308_002.TIF CONSTRPLANS VIEW
T07CM00308_003.TIF CONSTRPLANS VIEW
T07CM00308_004.TIF CONSTRPLANS VIEW
T07CM00308_005.TIF CONSTRPLANS VIEW
T07CM00308_006.TIF CONSTRPLANS VIEW
T07CM00308_007.TIF CONSTRPLANS VIEW