Permit: T07CM00308

Parcel: 10612149A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/01/2008 ELECTRIC - FINAL Approved
03/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
WORK IN PROGRESS
1. CORRECTIONS ON ROOF NOT COMPLETE
2. FINISH PANEL DIRECTORIES
3. ALL KITCHEN 120V RECEPTACLES TO BE GFI PROTECTED
02/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
DOOR LOCKED
12/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REVISE PANEL DIRECTORIES SO THEY ARE CORRECT, LEGIBLE AND NEAT, SPELLED CORRECTLY - NO SCRIBBLE
2. SERVICE DISCONNECT TO BE UNLOCKED
3. ALARM WIRING IN PROGRESS
4. MULTI-WIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES
5. PROVIDE DISCONNECTING MEANS FOR ICE MACHINE
6. FLEX NOT ALLOWED FOR DISPLAY CASES - IT IS SUBJECT TO PHYSICAL DAMAGE, BOXES AND RECEPTACLES NOT TO BE MOUNTED TO MOVABLE DISPLAY CASES

ON ROOFTOP
- AC 1 KINKED CONDUIT, LOOSE FITTINGS, NO STRAP, UNDERSIZED GROUND, DISCONNECT NOT TO BLOCK ACCESSIBLE COVER, PINCHED OPEN WIRING, MISSING K.O
CONTACTOR J-BOX NOT SEALED/SECURE SELF TAP SCREW NOT ALLOWED FOR GROUND, STRAP ALL FLEX.