Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2008 | ELECTRIC - FINAL | Approved | ||
| 03/04/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* WORK IN PROGRESS 1. CORRECTIONS ON ROOF NOT COMPLETE 2. FINISH PANEL DIRECTORIES 3. ALL KITCHEN 120V RECEPTACLES TO BE GFI PROTECTED |
|
| 02/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DOOR LOCKED |
|
| 12/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REVISE PANEL DIRECTORIES SO THEY ARE CORRECT, LEGIBLE AND NEAT, SPELLED CORRECTLY - NO SCRIBBLE 2. SERVICE DISCONNECT TO BE UNLOCKED 3. ALARM WIRING IN PROGRESS 4. MULTI-WIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES 5. PROVIDE DISCONNECTING MEANS FOR ICE MACHINE 6. FLEX NOT ALLOWED FOR DISPLAY CASES - IT IS SUBJECT TO PHYSICAL DAMAGE, BOXES AND RECEPTACLES NOT TO BE MOUNTED TO MOVABLE DISPLAY CASES ON ROOFTOP - AC 1 KINKED CONDUIT, LOOSE FITTINGS, NO STRAP, UNDERSIZED GROUND, DISCONNECT NOT TO BLOCK ACCESSIBLE COVER, PINCHED OPEN WIRING, MISSING K.O CONTACTOR J-BOX NOT SEALED/SECURE SELF TAP SCREW NOT ALLOWED FOR GROUND, STRAP ALL FLEX. |