Permit: T07CM00308

Parcel: 10612149A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
11/06/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
FLANGES OK
PIPE INSULATION AT WH OK
WH HAS HEAT TRAP NIPPS
11/05/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. USE APPROVED, LISTED CLOSET FLANGES
FLANGE MUST HAVE UPC SHIELD OR PROVIDE PROPER LISTING PAPERS
2. FLANGE MUST SIT 1/4" ABOVE FINISHED FLOOR
3. SCREWS TO BE STAINLESS STEEL OR BRASS
11/01/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/29/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. MAY NOT INTERMINGLE ABS AND PVC
2. CLOSET FLANGE TO EXTEND ABOVE THE FLOOR 1/4"
10/26/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
I'M SORRY WITH MY WORKLOAD TODAY I CANNOT WAIT
10/25/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/18/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ALL AREAS
NEED TO SEE CLOSET FLANGES
09/17/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER UNDERGROUND INSIDE
MAY NOT USE LOW HEEL AT EXTERIOR W.C
GREASE TRAP LEAKING
09/12/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/06/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*