Permit: T07CM00308

Parcel: 10612149A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/25/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/06/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CEILING NOT COMPLETE/NOT READY FOR INSPECTION

IN WALLS -
1. DEMO ALL UNUSED WIRING BOXES, ETC
2. STRAP MC WITHIN 12" OF TERMINATIONS
3. MAKE SURE ALL BOXES ARE GROUNDED
4. INSTALL NAIL PLATES WHERE HOLE IS LESS THAN 1 1/4" FROM STUD FACE FOR MC OR FLEX