Permit Number - T07CM00308
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/26/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07CM00308 7/25/07 Phase B appears to be overloaded at 202A, which would not only overload the panel, but also the entire electrical service. This was determined by multiplying all continuous loads by 125%. Where continuous load was already indicated on the circuit, that figure was not subject to the demand factor again. |