Permit Number: T07CM00308
Parcel: 10612149A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM00308
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM00308 7/25/07

Phase B appears to be overloaded at 202A, which would not only overload the panel, but also the entire electrical service. This was determined by multiplying all continuous loads by 125%. Where continuous load was already indicated on the circuit, that figure was not subject to the demand factor again.