Permit: TC-COM-0823-01930
Permit Details
Apply Date:
08/07/2023
Applicant:
Brad Hoge
Description:
REV 1 - Started Oct 2026 - Revisions to outdoor lighting CITIZENS TRANSFER AND STORAGE WAREHOUSE AND OFFICES
Permit Reviews
Permit Number - TC-COM-0823-01930
Permit Status: In review
Permit Description: REV 1 - Started Oct 2026 - Revisions to outdoor lighting
CITIZENS TRANSFER AND STORAGE WAREHOUSE AND OFFICES
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/08/2023 | COMMERCIAL REVIEW - FULL v.1 | 09/11/2023 | REQUIRES RESUBMIT |
| 10/31/2023 | COMMERCIAL REVIEW - FULL v.2 | 11/15/2023 | APPROVED |
| 09/30/2026 | COMMERCIAL REVIEW - FULL REVISION v.1 | 10/16/2026 | APPROVED |
| 11/12/2026 | SPECIAL INSPECTION REVIEW v.1 | N/A | REQUIRES RESUBMIT |
| 06/25/2026 | COMMERCIAL REVIEW - FULL v.1 | N/A | REQUIRES RESUBMIT |
| 11/02/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 11/04/2026 | APPROVED |
| 11/17/2026 | SPECIAL INSPECTION REVIEW v.2 | N/A | IN REVIEW |
| 11/15/2023 | RESTAMP - COMMERCIAL v.1 | 11/17/2023 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-COM-0823-01930
Permit Status: In review
Permit Description: REV 1 - Started Oct 2026 - Revisions to outdoor lighting
CITIZENS TRANSFER AND STORAGE WAREHOUSE AND OFFICES
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/11/2026 | Prior to Final - Required Documents - AIR BALANCING REPORT IS REQUIRED. |
Conditions
Permit Number - TC-COM-0823-01930
Permit Status: In review
Permit Description: REV 1 - Started Oct 2026 - Revisions to outdoor lighting
CITIZENS TRANSFER AND STORAGE WAREHOUSE AND OFFICES
| Date | Description | Comments |
|---|---|---|
| 11/15/2023 | SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED. | |
| 11/15/2023 | SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED. | |
| 11/15/2023 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. | |
| 11/15/2023 | SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED. | |
| 11/15/2023 | SPECIAL INSPECTION FOR FOUNDATION/EXCAVATION IS REQUIRED. | |
| 11/15/2023 | SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED. | |
| 11/15/2023 | Masonry Inspection Report submittal review is required. | |
| 08/08/2023 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment. | |
| 09/11/2026 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: In Review
Permit Number: TC-COM-0823-01930
Permite Description: REV 1 - Started Oct 2026 - Revisions to outdoor lighting
CITIZENS TRANSFER AND STORAGE WAREHOUSE AND OFFICES
Total Outstanding Inspections - 20
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2026 | COT - HCEL - Electrical Above Ceiling | N/A | Partial Pass | 9/14/2026 office areas all approved. Okay to proceed with progress areas. |
| 11/02/2026 | BULD - Electrical Clearance | N/A | Not Applicable | 11/2/26: previously inspected & approved by a different inspector. |
| 11/02/2026 | COT - BULD - SWG Clearance | N/A | Not Applicable | 11/2/26: not applicable |
| 11/02/2026 | ENGR Engineering Final | N/A | Partial Pass | Site is okay to apply for TCO level 1. |
| 11/25/2025 | COT - HCPL - Plumbing Progress | N/A | Partial Pass | Plumbing underground: waste lines (2” - 4”) at South side of structure under hydro test, approximately 35 feet from structure. Ok to cover progress areas. |
| 01/27/2026 | COT - HCPL - Sewer | N/A | Partial Pass | 1-27-26: precon meeting discuss sewer requirements & testing. |
| 11/03/2026 | COT - HCEL - Electrical Final | N/A | Partial Pass | 11/3/26: provide panel schedule for panels 3 & 4, label panel 3. |
| 06/03/2026 | COT - HCEL - Electrical Intermediate | N/A | Canceled | 6-3-26: canceled by contractor. |
| 11/18/2025 | COT - HCEL - Electrical Underground | N/A | Partial Pass | 11-18-25: verified a 3" Schedule 40 electrical conduit to feed building. Okay to backfill approximately 30' of trench and continue with construction at progress areas. |
| 11/03/2026 | COT - HCME - Mechanical Final | N/A | Partial Pass | 11/3/26: secure mini split & pending RFI for warehouse ventilation. |
| 11/03/2026 | COT - HCPL - Plumbing Final | N/A | Partial Pass | 11/3/26: paint DWV at loading dock, a pressure test for sewer and a utility permit is required. |
| 01/21/2025 | COT - HCBU - Preslab | N/A | Partial Pass | 1/8/25: reinforcement at loading dock footing per plan (per detail S3.2/315, S3.3/19, S3.3/25) 1/16/25: reinforcement per plan at (19) column footings GL A-D.2/1.2-7. Ok for concrete placement. 1/17/24: reinforcement per plan at slab column footings GL A-D.5/1-7 ok for concrete placement 1/21/25: reinforcement per plan at (16) column footings GL A-D.3/8-12 |
| 01/21/2026 | COT - HCBU - Masonry Pregrout | N/A | Partial Pass | 1-21-26: reinforcement at cmu wall verified per plans-okay to grout top out 12-16' at the peak. |
| 06/24/2026 | COT - HCBU - Exterior Clips/Sheathing | N/A | Partial Pass | |
| 02/09/2026 | COT - HCBU - Excavation/Rebar/Zoning | N/A | Partial Pass | Drainage trough at loading dock area; slab area at trash enclosure (rebar reenforcement). Ok to place concrete in progress areas (3000 psi rated). |
| COT - FCON - Sprinkler - Final | N/A | Not Ready | ||
| 11/05/2026 | COT - FCON - Fire - Final | N/A | Partial Pass | need fire pump installed ok for tco level 1 |
| COT - FCON - Alarm - Final | N/A | Not Ready | ||
| 11/03/2026 | COT - HCBU - Framing | N/A | Partial Pass | 11/3/26: submit requested framing RFI from 6/12/26, a racking permit is required and complete installation of chain at mezzanine. |
| 11/13/2026 | COT - HCBU - Building Final | N/A | Partial Pass | 11/10/26: approved for level 1 TCO only |
Completed Inspections
Permit Status: In Review
Permit Number: TC-COM-0823-01930
Permit Description: REV 1 - Started Oct 2026 - Revisions to outdoor lighting
CITIZENS TRANSFER AND STORAGE WAREHOUSE AND OFFICES
Total Completed Inspections - 21
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2026 | COT - HCPL - Plumbing Intermediate | Passed | ||
| 09/11/2026 | COT - HCME - Mechanical Progress | Passed | 9/11/26: mechanical progress office areas approved. | |
| 10/30/2026 | COT - HCBU - Building Above Ceiling | Passed | ||
| 10/30/2026 | COT - HCEL - Electrical Above Ceiling | Passed | ||
| 10/30/2026 | COT - HCME - Mechanical Above Ceiling | Passed | ||
| 10/30/2026 | COT - HCPL - Plumbing Above Ceiling | Passed | ||
| 11/02/2026 | TRSP - ROW - Notice of Completion | Passed | ||
| 11/02/2026 | COT - HCBU - Building Progress | Passed | 11/2/26: approved. | |
| 11/03/2026 | COT - HCPL - Plumbing Progress | Passed | 11/3/26: approved. | |
| 11/03/2026 | COT - HCPL - Rough Soil | Passed | 11/3/26: rough soil/plumbing underground approved. | |
| 11/03/2026 | COT - HCEL - Electrical Intermediate | Passed | 11/3/26: electrical intermediates approved. | |
| 11/03/2026 | COT - HCEL - Electrical Underground | Passed | 11/3/26: electrical underground approved. | |
| 11/03/2026 | COT - HCEL - Outdoor Lighting | Passed | 11/3/26: approved. | |
| 11/03/2026 | COT - HCME - Mechanical Intermediate | Passed | 11/3/26: mechanical intermediates approved. | |
| 11/03/2026 | COT - HCBU - Roof Nailing | Passed | 11/3/26: roof nailing approved. | |
| 11/03/2026 | COT - HCBU - Preslab | Passed | 11/3/26: preslab approved. | |
| 11/03/2026 | COT - HCBU - Masonry Pregrout | Passed | 11/3/26: approved. | |
| 11/03/2026 | COT - HCBU - Exterior Clips/Sheathing | Passed | 11/3/26: exterior clips/framing approved. | |
| 11/03/2026 | COT - HCBU - Excavation/Rebar/Zoning | Passed | 11/3/26: previously inspected & approved. | |
| 11/04/2026 | PDSD Building Division SIte Consultation | Passed | ||
| 11/04/2026 | COT - HCBU - Framing | Passed |