Permit: TC-COM-0823-01930

Parcel: 132130260


Addresses:

1501 E METRIC PL

Inspection Status: Not Ready

Inspection History: COT - HCBU - Building Final 

Date Description Inspector Results Comments
09/11/2026 COT - HCBU - Building Final  Not Ready 9/11/26: PERMIT REQUIRED FOR RACKING SYSTEM, PERMIT REQUIRES Resubmittal FOR OUTDOOR LIGHT REQUIREMENTS. WATER STERILIZATION REQUIRED, OUTDOOR LIGHT SIC REQUIRED, VENTILATION REQUIRED AT WEARHOUSE (REVISION IS REQUIRED).
11/02/2026 COT - HCBU - Building Final  Re-inspection required 11/2/26: complete electrical at restrooms, install fan covers in each restroom, label all disconnects, install a gfci adjacent to mop sink in warehouse, seal penetrations at demising warehouse walls, provide a support on hvac exhausts at warehouse, drinking fountain receptacle at warehouse needs to be gfci, provide panel schedules, wall hung urinal height not per ADA standards, add R3 insulation to hot leg of water heater, complete electrical at room 107, install gfci receptacle at room 107, install a hammer arrestor at ice machine, add R3 insulation to hot cvpvc lines at mezzanine areas, receptacles within 6' of water at shop storage require gfci's, have architect submit a letter indicating that floor sink at control area has been eliminated, per previous conversation a RFI for the warehouse exhausts/ventilation is required. Please schedule all remaining inspections and submit all 3rd party reports to the city for review & approval.
Note: I did not inspect roof top, above ceiling lighting and exterior. I will walk these areas at upcoming inspection & additional items may be noted.
11/13/2026 COT - HCBU - Building Final  Partial Pass 11/10/26: approved for level 1 TCO only