Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL ADDITION
Apply Date:
02/09/2006
Applicant:
MICHAEL BECHERER
Description:
ADDITION:MEETING ROOM & TI:OFFICE & SITE WORK
Contractors:
  • LLOYD CONSTRUCTION COMPANY INC ,

Permit Reviews

Permit Number - T06CM00831
Permit Status: C of o
Permit Description: ADDITION:MEETING ROOM & TI:OFFICE & SITE WORK
Start Date Submittal Complete Date Status  
02/09/2006 PLANS OK TO SUBMIT - 3RD PARTY 02/09/2006 COMPLETED Review Details
02/09/2006 PLANS OK TO SUBMIT - SITE 02/09/2006 COMPLETED Review Details
02/09/2006 3RD PARTY REVIEW-COMMERCIAL TI 04/24/2006 COMPLETED Review Details
02/09/2006 SITE 03/21/2006 COMPLETED Review Details
04/05/2006 RESUBMITTAL - SITE ALL 04/26/2006 COMPLETED Review Details
04/16/2007 3RD PARTY REVIEW-REVISION/OTHER 04/16/2007 COMPLETED Review Details
04/24/2006 POST 3RD PARTY REVIEW 05/04/2006 COMPLETED Review Details
04/28/2006 RESUBMITTAL - SITE ALL 05/17/2006 COMPLETED Review Details
05/01/2006 RESUBMITTAL 05/05/2006 COMPLETED Review Details
05/05/2006 RESUBMITTAL 05/15/2006 COMPLETED Review Details
05/15/2006 RESUBMITTAL 05/17/2006 COMPLETED Review Details
05/29/2007 REVISION - SITE 05/29/2007 COMPLETED Review Details
10/25/2006 3RD PARTY REVIEW-REVISION/OTHER 10/31/2006 COMPLETED Review Details
12/06/2006 3RD PARTY REVIEW-REVISION/OTHER 04/16/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM00831
Permit Status: C of o
Permit Description: ADDITION:MEETING ROOM & TI:OFFICE & SITE WORK
Total Outstanding Activity Conditions - 1
Date Name
02/09/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T06CM00831
Permit Description: ADDITION:MEETING ROOM & TI:OFFICE & SITE WORK
Total Completed Inspections - 49
Date Description Inspector Results Comments
06/26/2006 ROOF NAILING AQUIROZ Approved IVRS - Inspection :*
1) MAIN BLDG OK
08/04/2006 PLUMBING - ABOVE CEILING BBENEDON Approved IVRS - Inspection :*
09/25/2006 STEM WALL/RETAINING WALL AQUIROZ Approved ROOM 102, 105
10/09/2006 EXT METAL CLIPS/EXT SHEATHING LHANLY Approved IVRS - Inspection :*
ALL PROGRESS OK
10/13/2006 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
ONE SIDE WEST END OF BUILDING.
10/31/2006 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*
- SUPPLY/RETURN DISTRIBUTION OVER DEBRIEFING
AREAS #111 & #112
- HOLDING CELL AREA, PROGRESSING W/SUSPENDED DUCTS.
- CHECKED CHILLER IN RM. ON PRED.
11/02/2006 PLUMBING - SEWER HCS CONNECT RMYERS Approved IVRS - Inspection :*
TIE IN TO EXISTING @ NORTHSIDE OK
OK TO COVER
11/09/2006 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
CENTER POD OK
11/09/2006 FRAMING AQUIROZ Approved IVRS - Inspection :*
UP TO B LINE OK
11/09/2006 PLUMBING - YARD WTR LINE/TEST RLEDONNE Approved IVRS - Inspection :*
1. YARD WATER TEST FROM BUILDING 6' FROM METER AT STREET 3" PVC WITH TRACER WIRE.
2. PROVIDE BACKFLOW PREVENTOR.
12/04/2006 PLUMBING - PRE SLAB RMYERS Approved IVRS - Inspection :*
MENS AND WOMENS RESTROOM #109, #110 OK FOR CONCRETE
12/05/2006 ELECTRIC - OUTDOOR LIGHTING CCLEMENS Approved IVRS - Inspection :*
OK TO COVER S.E AREA PARKING LIGHTING, CALL FOR PROGRESS OK TO CONTINUE PARKING LIGHTING.
12/06/2006 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection :*
1. WALKED INTERIOR GENERAL AREA
2. JOB PROGRESSING
3. ABOVE CEILING NORTH OF "131" LINE TO "B6"
J1 TO J6 AREA, OK TO COVER
12/14/2006 PLUMBING - GAS PRESSURE TEST RMYERS Approved IVRS - Inspection :*
12/14/2006 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*
12/18/2006 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection :*
12/19/2006 ELECTRIC - INTERMEDIATE CCLEMENS Approved IVRS - Inspection :*
OK TO COVER N.E PARKING AREA UNDERGROUND
OK WALL, HARD LID COVER P.A COUNTER AREAS.
12/19/2006 ELECTRIC - ABOVE CEILING CCLEMENS Approved IVRS - Inspection :*
12/19/2006 ELECTRIC - UNDERGROUND CCLEMENS Approved IVRS - Inspection :*
12/21/2006 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
MAIL ROOM #115 OK TO COVER AFTER HOT INSULATION
12/22/2006 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection :*
8 COLUMNS
12/27/2006 REINFORCED MASONRY PRE-GROUT LHANLY Approved IVRS - Inspection :*
03/12/2007 ELECTRIC - TEMPORARY SERVICE CCLEMENS Approved IVRS - Inspection :*
AT GENERATOR
1. ISOLATE NEUTRAL & GROUND AND REMOVE BONDING STRAP
2. AT SERVICE - INSTALL A SIGN PER NEC 701.9A, IDENTIFY ALL FEEDERS
3. PROVIDE INFORMATION/NEW CALCULATION FOR PANEL "EL" AND TRANSFORMER "TE"
4. EQUIPMENT GROUNDING CONDUCTOR TO BE PROPERLY IDENTIFIED NEC 250.119

NOTE: KEEP ALL OPEN WIRING LOCKED OUT UNTIL SAFE TO ENERGIZE.
03/12/2007 ELECTRIC - TEMP POWER FOR TEST CCLEMENS Approved IVRS - Inspection :*
03/14/2007 TEP CLEARANCE - AM JWEATHER Approved TEC CLEARED FOR #140 PER C. CLEMENS
05/23/2007 U VALUE FOR WINDOW AQUIROZ Approved IVRS - Inspection :*
07/05/2007 BUILDING - PROGRESS AQUIROZ Approved IVRS - Inspection :*
07/06/2007 PLUMBING - GAS PRESS TEST FNL RMYERS Approved IVRS - Inspection :*
07/12/2007 OUTDOOR LIGHTING FINAL CCLEMENS Approved IVRS - Inspection :*
07/12/2007 ELECTRIC - RECONNECT CCLEMENS Approved IVRS - Inspection :*
07/12/2007 ELECTRIC - SERVICE UPGRADE CCLEMENS Approved IVRS - Inspection :*
07/12/2007 ELECTRIC - CABLE DROP CCLEMENS Approved IVRS - Inspection :*
07/12/2007 ELECTRIC - SERVICE RELOCATION CCLEMENS Approved IVRS - Inspection :*
07/12/2007 ELECTRIC - UFER CCLEMENS Approved IVRS - Inspection :*
07/13/2007 MECHANICAL - PROGRESS JMILITEL Approved IVRS - Inspection :*
OK FOR CEILING TILES EVERYWHERE
07/19/2007 ELECTRIC - CONSTRUCTION POWER CCLEMENS Approved
08/15/2007 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
08/20/2007 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
1) PLUMBING FINAL OK
2) OK FOR C OF O S.T.O.I.
08/21/2007 NPPO - FINAL ACONNOR Approved
08/21/2007 FIRE - HYDRANTS LTHOMAS Approved
08/22/2007 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL (NOTE: ALL RADII DESIGNS WERE APPROVED BY TRAFFIC ENGINEERING)
08/29/2007 LANDSCAPE - FINAL ACONNOR Approved
09/05/2007 SIGN - FINAL JSONKIN Approved IVRS - Inspection :*
09/06/2007 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :*
LIGHTNING PROTECTION SYSTEM TO BE INSPECTED AND APPROVED BY THIRD PARTY NRTL

ALL ELSE OK FOR FINAL
09/13/2007 FIRE SPKLR - FINAL LTHOMAS Approved
09/13/2007 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
09/19/2007 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
1) OK TEMP C OF O
2) FULL C OF O PENDING LIGHTING PROTECTION CERT
09/19/2007 ENGINEERING - FINAL MRUSSO Approved
09/19/2007 FIRE - FINAL LTHOMAS Approved