Permit: T06CM00831
Permit Details
Status:
C of o
Type:
COMMERCIAL ADDITION
Address:
1310 W MIRACLE MILE #140
Address NEW:
1310 W MIRACLE MILE #140
Apply Date:
02/09/2006
Applicant:
MICHAEL BECHERER
Description:
ADDITION:MEETING ROOM & TI:OFFICE & SITE WORK
Contractors:
- LLOYD CONSTRUCTION COMPANY INC ,
Permit Reviews
Permit Number - T06CM00831
Permit Status: C of o
Permit Description: ADDITION:MEETING ROOM & TI:OFFICE & SITE WORK
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/09/2006 | PLANS OK TO SUBMIT - 3RD PARTY | 02/09/2006 | COMPLETED |
| 02/09/2006 | PLANS OK TO SUBMIT - SITE | 02/09/2006 | COMPLETED |
| 02/09/2006 | 3RD PARTY REVIEW-COMMERCIAL TI | 04/24/2006 | COMPLETED |
| 02/09/2006 | SITE | 03/21/2006 | COMPLETED |
| 04/05/2006 | RESUBMITTAL - SITE ALL | 04/26/2006 | COMPLETED |
| 04/16/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 04/16/2007 | COMPLETED |
| 04/24/2006 | POST 3RD PARTY REVIEW | 05/04/2006 | COMPLETED |
| 04/28/2006 | RESUBMITTAL - SITE ALL | 05/17/2006 | COMPLETED |
| 05/01/2006 | RESUBMITTAL | 05/05/2006 | COMPLETED |
| 05/05/2006 | RESUBMITTAL | 05/15/2006 | COMPLETED |
| 05/15/2006 | RESUBMITTAL | 05/17/2006 | COMPLETED |
| 05/29/2007 | REVISION - SITE | 05/29/2007 | COMPLETED |
| 10/25/2006 | 3RD PARTY REVIEW-REVISION/OTHER | 10/31/2006 | COMPLETED |
| 12/06/2006 | 3RD PARTY REVIEW-REVISION/OTHER | 04/16/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM00831
Permit Status: C of o
Permit Description: ADDITION:MEETING ROOM & TI:OFFICE & SITE WORK
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/09/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T06CM00831
Permit Description: ADDITION:MEETING ROOM & TI:OFFICE & SITE WORK
Total Completed Inspections - 49
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2006 | ROOF NAILING | AQUIROZ | Approved | IVRS - Inspection :* 1) MAIN BLDG OK |
| 08/04/2006 | PLUMBING - ABOVE CEILING | BBENEDON | Approved | IVRS - Inspection :* |
| 09/25/2006 | STEM WALL/RETAINING WALL | AQUIROZ | Approved | ROOM 102, 105 |
| 10/09/2006 | EXT METAL CLIPS/EXT SHEATHING | LHANLY | Approved | IVRS - Inspection :* ALL PROGRESS OK |
| 10/13/2006 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* ONE SIDE WEST END OF BUILDING. |
| 10/31/2006 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | IVRS - Inspection :* - SUPPLY/RETURN DISTRIBUTION OVER DEBRIEFING AREAS #111 & #112 - HOLDING CELL AREA, PROGRESSING W/SUSPENDED DUCTS. - CHECKED CHILLER IN RM. ON PRED. |
| 11/02/2006 | PLUMBING - SEWER HCS CONNECT | RMYERS | Approved | IVRS - Inspection :* TIE IN TO EXISTING @ NORTHSIDE OK OK TO COVER |
| 11/09/2006 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* CENTER POD OK |
| 11/09/2006 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* UP TO B LINE OK |
| 11/09/2006 | PLUMBING - YARD WTR LINE/TEST | RLEDONNE | Approved | IVRS - Inspection :* 1. YARD WATER TEST FROM BUILDING 6' FROM METER AT STREET 3" PVC WITH TRACER WIRE. 2. PROVIDE BACKFLOW PREVENTOR. |
| 12/04/2006 | PLUMBING - PRE SLAB | RMYERS | Approved | IVRS - Inspection :* MENS AND WOMENS RESTROOM #109, #110 OK FOR CONCRETE |
| 12/05/2006 | ELECTRIC - OUTDOOR LIGHTING | CCLEMENS | Approved | IVRS - Inspection :* OK TO COVER S.E AREA PARKING LIGHTING, CALL FOR PROGRESS OK TO CONTINUE PARKING LIGHTING. |
| 12/06/2006 | MECHANICAL - ABOVE CEILING | CWILLIAM | Approved | IVRS - Inspection :* 1. WALKED INTERIOR GENERAL AREA 2. JOB PROGRESSING 3. ABOVE CEILING NORTH OF "131" LINE TO "B6" J1 TO J6 AREA, OK TO COVER |
| 12/14/2006 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
| 12/14/2006 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* |
| 12/18/2006 | BUILDING PRE-SLAB | AQUIROZ | Approved | IVRS - Inspection :* |
| 12/19/2006 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection :* OK TO COVER N.E PARKING AREA UNDERGROUND OK WALL, HARD LID COVER P.A COUNTER AREAS. |
| 12/19/2006 | ELECTRIC - ABOVE CEILING | CCLEMENS | Approved | IVRS - Inspection :* |
| 12/19/2006 | ELECTRIC - UNDERGROUND | CCLEMENS | Approved | IVRS - Inspection :* |
| 12/21/2006 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* MAIL ROOM #115 OK TO COVER AFTER HOT INSULATION |
| 12/22/2006 | EXCAVATION/LAYOUT REBAR & ZON | AQUIROZ | Approved | IVRS - Inspection :* 8 COLUMNS |
| 12/27/2006 | REINFORCED MASONRY PRE-GROUT | LHANLY | Approved | IVRS - Inspection :* |
| 03/12/2007 | ELECTRIC - TEMPORARY SERVICE | CCLEMENS | Approved | IVRS - Inspection :* AT GENERATOR 1. ISOLATE NEUTRAL & GROUND AND REMOVE BONDING STRAP 2. AT SERVICE - INSTALL A SIGN PER NEC 701.9A, IDENTIFY ALL FEEDERS 3. PROVIDE INFORMATION/NEW CALCULATION FOR PANEL "EL" AND TRANSFORMER "TE" 4. EQUIPMENT GROUNDING CONDUCTOR TO BE PROPERLY IDENTIFIED NEC 250.119 NOTE: KEEP ALL OPEN WIRING LOCKED OUT UNTIL SAFE TO ENERGIZE. |
| 03/12/2007 | ELECTRIC - TEMP POWER FOR TEST | CCLEMENS | Approved | IVRS - Inspection :* |
| 03/14/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED FOR #140 PER C. CLEMENS |
| 05/23/2007 | U VALUE FOR WINDOW | AQUIROZ | Approved | IVRS - Inspection :* |
| 07/05/2007 | BUILDING - PROGRESS | AQUIROZ | Approved | IVRS - Inspection :* |
| 07/06/2007 | PLUMBING - GAS PRESS TEST FNL | RMYERS | Approved | IVRS - Inspection :* |
| 07/12/2007 | OUTDOOR LIGHTING FINAL | CCLEMENS | Approved | IVRS - Inspection :* |
| 07/12/2007 | ELECTRIC - RECONNECT | CCLEMENS | Approved | IVRS - Inspection :* |
| 07/12/2007 | ELECTRIC - SERVICE UPGRADE | CCLEMENS | Approved | IVRS - Inspection :* |
| 07/12/2007 | ELECTRIC - CABLE DROP | CCLEMENS | Approved | IVRS - Inspection :* |
| 07/12/2007 | ELECTRIC - SERVICE RELOCATION | CCLEMENS | Approved | IVRS - Inspection :* |
| 07/12/2007 | ELECTRIC - UFER | CCLEMENS | Approved | IVRS - Inspection :* |
| 07/13/2007 | MECHANICAL - PROGRESS | JMILITEL | Approved | IVRS - Inspection :* OK FOR CEILING TILES EVERYWHERE |
| 07/19/2007 | ELECTRIC - CONSTRUCTION POWER | CCLEMENS | Approved | |
| 08/15/2007 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |
| 08/20/2007 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* 1) PLUMBING FINAL OK 2) OK FOR C OF O S.T.O.I. |
| 08/21/2007 | NPPO - FINAL | ACONNOR | Approved | |
| 08/21/2007 | FIRE - HYDRANTS | LTHOMAS | Approved | |
| 08/22/2007 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL (NOTE: ALL RADII DESIGNS WERE APPROVED BY TRAFFIC ENGINEERING) |
| 08/29/2007 | LANDSCAPE - FINAL | ACONNOR | Approved | |
| 09/05/2007 | SIGN - FINAL | JSONKIN | Approved | IVRS - Inspection :* |
| 09/06/2007 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection :* LIGHTNING PROTECTION SYSTEM TO BE INSPECTED AND APPROVED BY THIRD PARTY NRTL ALL ELSE OK FOR FINAL |
| 09/13/2007 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 09/13/2007 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 09/19/2007 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* 1) OK TEMP C OF O 2) FULL C OF O PENDING LIGHTING PROTECTION CERT |
| 09/19/2007 | ENGINEERING - FINAL | MRUSSO | Approved | |
| 09/19/2007 | FIRE - FINAL | LTHOMAS | Approved |