Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* 05, 10, 35, 36, 40, 50, 60, 62, 65, 70, 85, 99 |
|
| 06/29/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING ROOM 105 |
|
| 06/19/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK REMAINDER LIDS SOUTH ENTRY AREA, INCLUDES #102 INTERIOR/EXTERIOR CANS |
|
| 06/11/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK INTERIOR HARD LIDS ROOM #102 |
|
| 06/08/2007 | ELECTRIC - ABOVE CEILING | Cancelled | ||
| 06/08/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 05/22/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING COVER PUBLIC RESTROOMS CHECK FOR PROPER CONDUCTOR DERATION IN GUTTERS -- NEC 366.22 (2005) |
|
| 05/14/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* TALK ABOUT FLOOR BOXES IN AUDITORIUM NO ANGLED FITTINGS CONCEALED BELOW SLAB AND PROVIDE PHYSICAL PROTECTION FOR FLEX GOING THROUGH SLAB. |
|
| 05/09/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* WEST SIDE UPPER WALL LOBBY & OUT TO EXTERIOR |
|
| 05/02/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HARD LIDS IN AUDITORIUM AREA (#105) |
|
| 04/26/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* EXTERIOR ENTRY SOFFIT CANS @ AUDITORIUM (4) |
|
| 04/24/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO INSTALL REMAINDER OF CEILING TILES IN MAIN BUILDING -- MAKE SURE ALL TEMP WIRING IS REMOVED BEFORE TILES |
|
| 04/20/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SUPPORT ALL FIXTURES WITH CLIPS OR SCREW TO GRID. 2. SUPPORT DATA/COMM CABLES TO STRUCTURE. |
|
| 04/17/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 04/12/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/04/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 03/27/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* NORTH CENTRAL AREAS SOUTH OF "H" LINE (CORRIDOR INCLUDED) NOTE: ALL LOW VOLTAGE WIRING TO BE NEAT AND WORKMANLIKE REMOVE ALL TEMP WIRING J-BOXES TO BE CLOSED, DO A BETTER JOB WITH FLEX SUPPORT |
|
| 03/23/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | ||
| 03/09/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. INSTALL ALL FUSES IN SERVICE -- NEC 310 2. TIGHTEN BOND CLAMPS TO WATER/GAS, ETC 3. BONDING CONDUCTORS FOR TRANSFORMER UNDERSIZED NEC 250.30 CALL BACK FOR ALL TRANSFORMER, PANELS, FEEDER INSPECTION. |
|
| 03/05/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CENTER AREA SOUTH OF CORRIDOR 009 |
|
| 02/23/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING COVER ROOMS #401, 402, 403, 408, 409, 411, 412, 413, 414, 415 |
|
| 02/09/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER HIGH DROP CEILINGS IN AREAS 012 & 008 PER PLAN TJ 955-0225 |
|
| 01/31/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* CEILING TILES NEED TO BE REMOVED FOR INSPECTION YOU CAN LEAVE TILES IN THAT ARE NEEDED TO INSTALL EQUIPMENT SUCH AS LIGHT CANS, SPRINKLER TRIMS, HVAC VENT ETC. OK TO CONTINUE SITE LIGHTING. |
|
| 01/17/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 12/19/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/29/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/28/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 11/13/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER N.W AREA ADDED HALL SECTIONS TALKED ABOUT SIZING OF PULL BOXES -- SIZE PER NEC 314 |
|
| 10/20/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/05/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/03/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* BREAK ROOM, CRT ROOM, DISTRIBUTION WALL SOFFIT LIGHTING, EXERCISE ROOM WALLS. * NOTE: INSTALL MUD RINGS & K.O SEALS AS NEEDED OK TO ONE SIDE DRYWALL DO NOT COVER COMPLETELY |
|
| 09/22/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/07/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CENTER AREA BETWEEN CORRIDORS |