Permit: T06CM00831

Parcel: 10706023G

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/12/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05, 10, 35, 36, 40, 50, 60, 62, 65, 70, 85, 99
06/29/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING ROOM 105
06/19/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK REMAINDER LIDS SOUTH ENTRY AREA, INCLUDES #102 INTERIOR/EXTERIOR CANS
06/11/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK INTERIOR HARD LIDS ROOM #102
06/08/2007 ELECTRIC - ABOVE CEILING Cancelled
06/08/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/22/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING COVER PUBLIC RESTROOMS
CHECK FOR PROPER CONDUCTOR
DERATION IN GUTTERS -- NEC 366.22 (2005)
05/14/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
TALK ABOUT FLOOR BOXES IN AUDITORIUM
NO ANGLED FITTINGS CONCEALED BELOW SLAB AND PROVIDE PHYSICAL PROTECTION FOR FLEX GOING THROUGH SLAB.
05/09/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
WEST SIDE UPPER WALL LOBBY & OUT TO EXTERIOR
05/02/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK HARD LIDS IN AUDITORIUM AREA (#105)
04/26/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
EXTERIOR ENTRY SOFFIT CANS @ AUDITORIUM (4)
04/24/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO INSTALL REMAINDER OF CEILING TILES IN MAIN BUILDING -- MAKE SURE ALL TEMP WIRING IS REMOVED BEFORE TILES
04/20/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SUPPORT ALL FIXTURES WITH CLIPS OR SCREW TO GRID.
2. SUPPORT DATA/COMM CABLES TO STRUCTURE.
04/17/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/12/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
04/04/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/27/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
NORTH CENTRAL AREAS SOUTH OF "H" LINE (CORRIDOR INCLUDED)

NOTE: ALL LOW VOLTAGE WIRING TO BE NEAT AND WORKMANLIKE
REMOVE ALL TEMP WIRING
J-BOXES TO BE CLOSED, DO A BETTER JOB WITH FLEX SUPPORT
03/23/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection
03/09/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. INSTALL ALL FUSES IN SERVICE -- NEC 310
2. TIGHTEN BOND CLAMPS TO WATER/GAS, ETC
3. BONDING CONDUCTORS FOR TRANSFORMER UNDERSIZED
NEC 250.30

CALL BACK FOR ALL TRANSFORMER, PANELS, FEEDER INSPECTION.
03/05/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
CENTER AREA SOUTH OF CORRIDOR 009
02/23/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING COVER ROOMS #401, 402, 403, 408, 409, 411, 412, 413, 414, 415
02/09/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO COVER HIGH DROP CEILINGS IN
AREAS 012 & 008 PER PLAN
TJ 955-0225
01/31/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
CEILING TILES NEED TO BE REMOVED FOR INSPECTION YOU CAN LEAVE TILES IN THAT ARE NEEDED TO INSTALL EQUIPMENT SUCH AS LIGHT CANS, SPRINKLER TRIMS, HVAC VENT ETC.
OK TO CONTINUE SITE LIGHTING.
01/17/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/19/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/29/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/28/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/13/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER N.W AREA ADDED HALL SECTIONS TALKED ABOUT SIZING OF PULL BOXES -- SIZE PER NEC 314
10/20/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
10/05/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/03/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
BREAK ROOM, CRT ROOM, DISTRIBUTION WALL SOFFIT LIGHTING, EXERCISE ROOM WALLS.

* NOTE: INSTALL MUD RINGS & K.O SEALS AS NEEDED
OK TO ONE SIDE DRYWALL
DO NOT COVER COMPLETELY
09/22/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/07/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
CENTER AREA BETWEEN CORRIDORS