Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2008 | ELECTRIC - FINAL | Approved | ALL REQUIRED SPECIAL INSPECTION REPORTS FOR ELECTRICAL SYSTEM REVIEWED AND ACCEPTED | |
| 09/06/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* LIGHTNING PROTECTION SYSTEM TO BE INSPECTED AND APPROVED BY THIRD PARTY NRTL ALL ELSE OK FOR FINAL |
|
| 08/30/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. TRANSFORMER "T1" TO BE MOVED 2. LIGHTNING PROTECTION SYSTEM TO HAVE THIRD PARTY INSPECTION |
|
| 08/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CORRECTIONS IN PROGRESS |
|
| 08/22/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* INSPECTION FOR EMERGENCY LIGHTING DONE 8/21/07 ALL OK EXCEPT EMERGENCY LIGHTING IN BOTH WEST SIDE BATHROOMS (NOT WORKING) CORRECTIONS IN PROGRESS |
|
| 08/16/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE A SIGN AT S.E.S MEETING THE REQUIREMENTS OF NEC 702.8 FOR U.P.S SYSTEM |
|
| 08/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR CEILING AREA ABOVE HOLDING CELLS & ROOM 206 1. NEED A SERVICE RECEPTACLE - NEC 210.63 2. LOW VOLTAGE WIRING TO BE RAN IN A NEAT AND WORKMANLIKE MANNER AND PROTECTED FROM PHYSICAL DAMAGE - NEC 800.6 3. FINISH WIRING, CLOSE J-BOXES |
|
| 08/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/10/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL BOX EXTENDERS IN ARMORY-NEC 314.20 2) MAX LENGTH DISPOSAL CORD 36" NEC 422.16 AND USE CONNECTOR NEXT INSPECTION 3) COM. ROOM, UPS EMERGENCY LIGHT TEST |
|
| 08/07/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* INSPECTION FOR GENERAL OFFICE AND HALL AREAS NORTH TO LOCKERS |
|
| 08/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* INSPECTION FOR CHILLER ROOM & AIR HANDLER ROOM #701-703 1. PLAN SHOWS FEEDER PULLED TO FUTURE CHILLER #2 |
|
| 08/02/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS WE WILL INSPECT #703, 702, 701 NEXT INSPECTION |
|
| 07/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS |
|
| 07/25/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS *NOTE: A SECOND ENTRANCE TO SES ROOM TO BE PROVIDED TO COMPLY WITH NEC 110.26 C2 |
|
| 07/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR FLEET SERVICE AREA 1. REPLACE WATER BOND CLAMP 2. PROVIDE GFI PROTECTION FOR RECEPTACLES PER NEC 511.12 3. REMOVE TEMP WIRING 4. CLOSE UP J-BOXES 5. WILL NEED ENGINEERS SEAL FOR LIGHTING PROTECTION PLAN FOR INSPECTION OR YOU CAN HAVE A THIRD PARTY (NRTL) INSPECTION |
|
| 07/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR GENERATOR ROOM 1. BONDING JUMPER FOR GENERATOR TO REMAIN REMOVED 2. EMERGENCY LIGHTING TO BE PER PLAN (LOCATION) 3. HAVE OPEN WIRING/ENCLOSURES 4. INSTALL SINGLE RECEPTACLE FOR GENERATOR HEAT/CHARGER NOT GFI RECEPTACLE 5. PROVIDE FAULT CURRENT INFORMATION FOR GENERATOR AND ASSOCIATED EQUIPMENT. ALSO, MISSING EQUIPMENT ON SINGLE LINE DIAGRAM 6. GENERATOR EXH. DAMPER NOT OPERATIONAL 7. PLANS SHOW SMOKE DETECTOR IN THIS ROOM |
|
| 07/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR SES ROOM 1. INSTALL PANIC HARDWARE FOR DOORS -- NEC 110.26 C2 2. FINISH ALL DEMO/REMOVE TEMP WIRING AND EQUIPMENT 3. SECURE BONDING CONDUCTOR TO STRUCTURE 4. DRAIN PIPE TO BE REMOVED ABOVE SERVICE - NEC 110.26F 5. FIRE ALARM, EX. FAN NOT COMPLETE 6. RECEPTACLES WITH METAL FACEPLATES TO EXTEND PAST FACE PLATE -- NEC 406.4D 7. FLEX TO TRANSFORMER NOT TO BE IN FRONT OF PANEL "EM" -- NEC 110.26 8. ADD SECOND PERSONNEL DOOR FOR EGRESS WITH PANIC BAR PER NEC 110.26 C 2 |
|
| 07/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR MAIN BUILDING ROOFTOP 1. LIGHTING PROTECTION SYSTEM NOT PER PLAN PROVIDE REVISED PLAN IF ONE EXISTS. ALSO, NEED TO MAKE CONNECTIONS AS OUTLINED BY PLAN. 2. NEED TO IDENTIFY AC 1 DATA PLATE 3. COMPLETE MAST WIRING/BONDING NOTE: GROUNDING ELECTRODE SYSTEM FOR LIGHTNING PROTECTION WILL NEED TO BE EXPOSED FOR INSPECTION ALSO, PROVIDE REVISED/APPROVED PLAN FOR THIS SYSTEM. |
|
| 07/12/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/05/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK INTERIOR WIRING PANELS MI, ACI, AC2 1. DRAIN ABOVE THESE PANELS TO BE RE-DIRECTED TO AN AREA AWAY FROM PANELS. |