Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/12/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) AT GENERATOR ISLOATE NEUTRAL GROUND AND REMOVE BONDING STRAP 2) AT SERVICE INSTALL A SIGN PER NEC 701.9A, IDENTIFY ALL FEEDERS 3) PROVIDE INFORMATION/NEW CALCULATION FOR PANEL "EL" AND TRANSFORMER "TE" 4) EQUIPMENT GROUNDING CONDUCTOR TO BE PROPERLY IDENTIFIED NEC 250.119 2) NOTE: KEEP ALL OPEN WIRING LOCKED OUT UNTIL SAFE TO ENERGIZE |
|
| 03/09/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |