Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 12/14/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
| 10/26/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* SAND/OIL SEPARATOR PIPING TO TIE IN TEST OK TIE IN NO MARKED TEST UP TO |
|
| 10/19/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* N/H RAIN LEADER TIED INTO PREVIOUSLY INSPECTED UNDERGROUND. |
|
| 10/15/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. 8" N/H RAIN LEADER STUBBED OUT OF BLDG. 2. BLDG. DRAIN ON SOUTH SIDE OF BLDG. OK TO COVER. |
|
| 08/28/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
| 08/15/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. PIPE DAMAGED BY LABORERS REPAIRED OK -- OK FOR CONCRETE. 2. HOT INSULATED OK FROM BATHROOM IN GROUP TO W.H |
|
| 08/10/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | 1. UPPER 6" CLEANOUT AT S.W CORNER OF BLDG. WITH 4" BRANCH STUBBED ABOUT FOUR FEET. 2. 6" CONNECTION INSIDE BLDG. LINE TO PREVIOUSLY INSPECTED SECTION -- OK TO COVER 3. PIPING DAMAGED BY LABORERS TO BE REPAIRED AND RETESTED AND INSPECTED. |
|
| 08/07/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
| 08/04/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* PIPE WRAPS OK IN JUVENILE HOLDING AREA FOOTINGS, ENSURE THAT TRAP ARMS HAVE PROPER GRADE DURING POUR. FDS NOT YET INSTALLED WHEN PIPES ARE REPAIRED, RETEST OK FOR CONCRETE 120 PSI TEST, TYPE L COPPER WATER PIPING OVERHEAD ALONG COL. B-1 WITH STUB OUTS TO SOUTH ADDITION AND NORTH RUNS ALONOG COLS 4 AND 5.2 FEEDING TOILET RMS 407, 407 AND WH RM 410, RM 404 ALSO SINKS AND WH AT RMS 315, 314. COPPER TOUCHING METAL AT WH AND RM 401 PROVIDE SPECS ALLOWING PULLED TEES. OK TO INSULATE HOT. TEST ON DWV ONLY TO 6'. PROVIDE 10' HEAD TEST ON ALL WASTE PIPING. TEST ALL VENTS TO ROOF. |
|
| 08/01/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* PIPE WRAPS IN ADULT HOLDING AREA OK |
|
| 07/13/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. N/H WASTE PIPING TO INTERCEPTOR (NOT SET) INCLUDING VENT TRACK EXTERIOR WALL OK |
|
| 07/05/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* OKAY TO POUR NEXT SECTION 07/03/06 |
|
| 06/29/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
| 06/02/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* OK TO POUR WHAT IS READY CONTRACTOR WILL RECALL NEXT SECTION. |
|
| 06/01/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. 6" ABS BLDG. DRAIN MAIN TO OUTSIDE JUST PAST TWO WAY CLEAN-OUT OK TO COVER. |
|
| 05/22/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. DWV UNDERGROUND AS HIGHLIGHTED ON PLAN AND VERIFIED BY J.C. OK TO COVER. WATER TEST ONE RISER TO TEN FEET. AS NOTED ON P1.1 & P1.0 |