Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* AT GENERATOR 1. ISOLATE NEUTRAL & GROUND AND REMOVE BONDING STRAP 2. AT SERVICE - INSTALL A SIGN PER NEC 701.9A, IDENTIFY ALL FEEDERS 3. PROVIDE INFORMATION/NEW CALCULATION FOR PANEL "EL" AND TRANSFORMER "TE" 4. EQUIPMENT GROUNDING CONDUCTOR TO BE PROPERLY IDENTIFIED NEC 250.119 NOTE: KEEP ALL OPEN WIRING LOCKED OUT UNTIL SAFE TO ENERGIZE. |
|
| 03/09/2007 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* |