Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Apply Date:
07/13/2001
Applicant:
TUCSON UNIFIED SCHOOL DISTRICT
Description:
ELEMENTARY SCHOOL:TD#15-16-62
Contractors:
  • LAMBERT LTD , RICHARD E
  • TUCSON UNIFIED SCHOOL DIST #1

Permit Reviews

Permit Number - T01CM03462
Permit Status: C of o
Permit Description: ELEMENTARY SCHOOL:TD#15-16-62
Start Date Submittal Complete Date Status  
01/13/2003 REVISION 01/13/2003 COMPLETED Review Details
07/13/2001 COMMERCIAL-BLDG/FIRE ONLY 07/31/2001 COMPLETED Review Details
11/29/2002 REVISION 12/10/2002 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T01CM03462
Permit Status: C of o
Permit Description: ELEMENTARY SCHOOL:TD#15-16-62
Total Outstanding Activity Conditions - 1
Date Name
07/13/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T01CM03462
Permit Description: ELEMENTARY SCHOOL:TD#15-16-62
Total Completed Inspections - 37
Date Description Inspector Results Comments
08/07/2001 ELECTRIC - CABLE DROP JORTA Approved IVRS - Inspection 0000*
09/05/2001 PLUMBING - ROUGH, SOIL RMYERS Approved 1.) THE NO HUB UNDERGROUND IS NOW COMPLETE 2.) ALL AREAS HIGHLIGHTED. 3.) ALL AREAS OK TO COVER.
09/28/2001 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection 0000*
10/05/2001 ELECTRIC - UFER JORTA Approved IVRS - Inspection 0000*FROM REBAR UFER SYSTEM TO WATER TO GAS TO SES ATTACHMENT 3 AND STUB OUT APPROVED.
11/28/2001 ELECTRIC - UNDERGROUND JORTA Approved IVRS - Inspection 0000*APPROVED ELECTRIC ROOM UNDER GROUND APPROVED. MECH. ROOM MCC UNDERGROUND APPROVED
12/07/2001 STEM WALL/RETAINING WALL LHANLY Approved IVRS - Inspection 0000*F-4 FOOTERS OK PROVIDING FINISHED STEM GRADE IS LOWERED TO ACCOUNT FOR PLACEMENT OF #3 TIES.
12/19/2001 ROOF NAILING LHANLY Approved IVRS - Inspection 0000*PARTIAL WEST ROOM 1.) DIAPHRAGM BLOCKING IN OTHER AREAS MUST BE CORRECTED 2.) DO NAILS NEED TO BE BENT OVER ON STRAPPING.
12/19/2001 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection 0000*
12/27/2001 REINFORCED MASONRY PRE-GROUT LHANLY Approved IVRS - Inspection 0000*PARTIAL 4'-12' SOUTH CLASSROOMS.
12/27/2001 BUILDING PRE-SLAB LHANLY Approved IVRS - Inspection 0000*181,182,184
03/26/2002 STUCCO MESH LHANLY Approved IVRS - Inspection 0000*
06/18/2002 MECHANICAL - TEMP PWR FOR TEST RSUBA Approved
06/25/2002 ELECTRIC - TEMP POWER FOR TEST JORTA Approved IVRS - Inspection 0000*RECEIVED TORQUE LETTER AND BEFORE C OF O WILL NEED GFI PERFORMANCE TEST. ALL OTHER INSPECTION SIGNED OFF. ADJUSTMENT FOR MAX AMP SETTING OF MAIN BREAKER 1500AMPS TO BE VERIFIED.
07/29/2002 SHEET ROCK NAILING LHANLY Approved IVRS - Inspection 0000*
07/29/2002 BUILDING ABOVE CEILING LHANLY Approved IVRS - Inspection 0000*
08/15/2002 U VALUE FOR WINDOW LHANLY Approved IVRS - Inspection 0000*
08/15/2002 FRAMING LHANLY Approved IVRS - Inspection 0000*
09/13/2002 PLUMBING - GAS PRESSURE TEST RMYERS Approved
09/13/2002 PLUMBING - ABOVE CEILING RMYERS Approved
10/01/2002 PLUMBING - PROGRESS RMYERS Approved 1.) PLUMBING PROGRESS OK 2.) CONTRACTOR POSTED BOND FOR TEMP POWER/ENERGY/FUEL GAS CARD LEFT AT METER SET.
10/15/2002 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection 0000*
11/14/2002 FIRE - FINAL LTHOMAS Approved
11/14/2002 FIRE SPKLR - FINAL LTHOMAS Approved
11/24/2002 PLUMBING - FINAL RMYERS Approved IVRS - Inspection 0000*1.) NOT READY FOR INSPECTION
2.) CALL IN ALL REQUIRED INSPECTION BEFORE CALLING IN FINAL STILL NEED
11/25/2002 ELECTRIC - FINAL JORTA Approved IVRS - Inspection 0999*IRREGATION CONTROLLER NOT READY ON SEWAGE SUMP SYSTEM: NEED A COMPLETE APPROVED (CITY) PLAN I.D. PUMP 1 & 2 CONTROLLER, NEED DISCONNECT FOR COMPRESSOR, BOTH PUMPS FROM PANEL AA? NEED GROUND BUSH. & BOND JUMPER FOR ALL RACEWAYS.
11/26/2002 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection 0999*1.) ACCESS STILL PROBLEM FAN COILS #46/45, RM. #116
EXHAUST BLOWER EF23,
2.) A. GREASE COLLECTION CUP ON BLOWER & HOOD.
B.) EXHAUST BLWS ON ROOF. COVER FLEX DUCT COM. W/RAIN SHIELD
3.) ELIMINATE MOVEMENT ON COOKING LINE FLEX GAS CONNECTORS OR USE PROPER APPROVED FLEX GAS LINES. 4.) CHILLER PERM. LABELS/NUMBER INK IS ALREADY FADDING
12/18/2002 PLUMBING - SEWER HCS CONNECT RMYERS Approved IVRS - Inspection 0999*1.) NO APPROVAL SITE UTILITY PLAN ON SITE 2.) YARDWATER COVERED BEFORE INSPECTION.
3.) SEWER COVERED BEFORE INSPECTION.
12/27/2002 PLUMBING - YARD WTR LINE/TEST SLONG Approved YARD WATER LINE COVERED W/O INSP. SITE VISIT ON 12-26-02 TO DETERMINE IF POTHOLING WOULD BE ADEQUATE FOR INSPECTION. IT WAS DETERMINED THAT THE ENTIRE LINE SHOULD BE EXPOSED IN ORDER TO BE CERTAIN THAT NO NON-POTABLE LINES IRRIGATION ARE CONNECTED TO THE POTABLE WATER.
01/30/2003 SIGN - FINAL JYBARRA Approved IVRS - Inspection 0000*
09/15/2005 ENGINEERING - FINAL DROBERTS Approved THIS SITE WAS CHECKED AND FOUND TO BE SUBSTANTIALLY COMPLETE, WITH MINOR DRAINAGE ISSUES TO BE RESOLVED UNDER THE NEW CONTRACT. THE SCHOOL WILL BE INSTALLING ADDITIONAL SIDEWALK SCUPPERS AS NEEDED DURING THE CONSTRUCTION PHASE OF THE NEW CLASSROOMS. ALSO IT WAS NOTED THAT THE ON-SITE DETENTION/RETENTION BASINS ARE NOT OPERATING PER OUR DEVELOPMENT STANDARDS AND STORMWATER RET./DET. MANUAL IN REGARDS TO THE PERCOLATION RATES. THE NEW CONTRACTOR WILL WORK ON REMOVING THE SEDIMENT FROM THE BASINS TO HELP RE-ESTABLISH THE PERCOLATION RATES. THE SCHOOL WILL INVESTIGATE THE INSTALLATION OF A LOW FLOW PIPE TO ALLOW FOR CONTINOUS DISCHARGE OF THE WATERS OVER TIME.
09/15/2005 RIGHT OF WAY - FINAL LLOPEZ Approved CLEARED FOR C OF O BY PHONE 9:58AM
10/31/2006 EXT METAL CLIPS/EXT SHEATHING LHANLY Approved
10/31/2006 BUILDING - FINAL LHANLY Approved ALL TRADES DONE. SPECIAL INSPECTION FORMS SHOULD ALREADY BE TURNED IN.
11/01/2006 PERMIT FINALED GBONILLA Approved
11/01/2006 MECHANICAL - INTERMEDIATE CWILLIAM Approved
11/01/2006 MECHANICAL - ABOVE CEILING CWILLIAM Approved
11/01/2006 MECHANICAL - HOODS CWILLIAM Approved

Documents

File Name Document Type  
C OF O_11-01-2006.TIF CERT OF OCC VIEW
TEMP C OF O_01-31-2003.TIF CERT OF OCC VIEW
BONDRELEASE.TIF DOCUMENTS VIEW
None DOCUMENTS VIEW