Permit: T01CM03462

Parcel: 119280310


Addresses:

2700 S LA CHOLLA BL


Inspection Status: Denied

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T01CM03462

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Denied

Date Description Inspector Results Comments
01/14/2003 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*1.) NO APPROVED PLAN ON SITE.
2.) CONTRACTOR TO PAY REINSPECTION FEE.
01/14/2003 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection 0000*
1.) YARDWATER INSTALLED PER APPROVED REVISED PLAN. OK TO COVER.
01/12/2003 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*1.) UNABLE TO LOCATE GENERAL CONTRACTOR ON SITE.
2.) I OBSERVED" POTHOLING" ON THE SEWER PIPING HOWEVER NOT ALL OF THE CRITERICA HAVE BEEN MET IN ORDER TO APPROVED THE SEWER.
A. SEE NOTES FROM 10/15/02 VERIFICATION OF GRADE OF SITE SEWER PORTIONS COVERED W/O INSPECTION.
B.) 12/18/2002 SEWER COVERED BEFORE INSPECTION.
I HAVE APPROVED NOTHING BEYOND THE TWO WAY CLEAN OUT AT HTE BUILDING DRAIN. I SAW NO HCS CONNECTION AT THE EDGE OF THE PROPERTY, AND DID NOT INSPECT IN THE RIGHT OF WAY OR STREET I CAN NOT APPROVED PLUMBING I HAVE NOT WITNESSED.
3.) NEED APPROVED YARDWATER PIPING PLAN BEFORE YOU CAN COVER.
01/08/2003 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*
1.) ENGINEER OKAYS SCH 40 PVC IN LIEU OF CLASS 160
2.) 2-2" RPPBP DO NOT EQUAL 4" SERVICE.
REQUIRED SIZE OF RPPBP IS TO BE SAME SIZE AS BUILDING SUPPLY (4").
3.) NOT INSTALLED PER APPROVED PLAN (ROUTING DIFFERENCT.)
12/27/2002 PLUMBING - YARD WTR LINE/TEST Denied YARD WATER LINE COVERED W/O INSP. SITE VISIT ON 12-26-02 TO DETERMINE IF POTHOLING WOULD BE ADEQUATE FOR INSPECTION. IT WAS DETERMINED THAT THE ENTIRE LINE SHOULD BE EXPOSED IN ORDER TO BE CERTAIN THAT NO NON-POTABLE LINES IRRIGATION ARE CONNECTED TO THE POTABLE WATER.
12/18/2002 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*
07/25/2002 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*1.) REC'D LETTER FROM MIKE SHIPIONE CONCERNING MAT'L AND SIZES SPEC'D FOR EXTERIOR BELOW GRADE YARDWATER PIPING. THE LETTER CONFLICTS WITH THE SPEC'S PLEASE READ 15,100 PART 2-2.01 DI.
07/17/2002 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*1.) SEE PLUMBING SPEC. FOR EXTERIOR WATER PIPING BELOW GRADE. NOT INSTALLED PER PLAN.
12/13/2001 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000$1.) WATER SERVICE THRU SLAB OK CORRECTIONS FROM 12/10/01 OK 2.) OK FOR CONCRETE.
12/10/2001 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*1) CONTRACTOR DESIRES PARTIAL INSPECTION OF WATER SERVICE THROUGH SLAB. 2.) 90 ELBO UNDER SLAB SIL PHOS'D OK PRESSURE TEST OK PRESSURE TEST OK 3.) GENERAL CONTRACTOR AND PLUMBING INSPECTOR UNABLE TO FIND EITHER BLUE STRIPE, OR STAMP ON PIPING DENOTING WHICH TYPE IT IS. SPECS REQUIRE TYPE "L".
09/20/2001 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection 0000*1.) NOT READY FOR INSPECTION.