Permit: T01CM03462

Parcel: 119280310


Addresses:

2700 S LA CHOLLA BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM03462

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/07/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK C OF O.
11/25/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*IRREGATION CONTROLLER NOT READY ON SEWAGE SUMP SYSTEM: NEED A COMPLETE APPROVED (CITY) PLAN I.D. PUMP 1 & 2 CONTROLLER, NEED DISCONNECT FOR COMPRESSOR, BOTH PUMPS FROM PANEL AA? NEED GROUND BUSH. & BOND JUMPER FOR ALL RACEWAYS.
11/05/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) DISPOSAL SW DISCONNECT MOUNTED BELOW CONTRACTOR.
2.) DISHWASHER SWAP SW DISCONNECT MOUNTED SIDE OF CONTROL BOX.
3.) BOOSTER HEATER VAP SW DISCONNECT TO SIDE OF ENCLOSURE.
4.) CO BE OVEN DISCONNECT MOUNTED TO SIDE ON 5200 SERIES WIREMOULD SUPPORT ENNOR BACK SIDE. ALL ABOVE OK.
11/04/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PARTIAL LOCATION OF DISCONNECTING MEANS FOR KIT EQUIPMENT DISCUSSED WILL CALL FOR FINAL WHEN DONE.
10/10/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*DISCONNECTING MEANS REQUIRED FOR D.W. DISP AND THE KITCHEN ACCESSORIER IMPROPER CLEARANCE OF CIRCUIT BREAKER DISCONNECT BEHIND RANGE. PANEL BROAD DESIGNATION MISSING A DISCONNECTING MEANS REQUIRED FOR EVAPORATOR UNITS INSIDE WALK INS.