Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T01CM03462
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/31/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
09/16/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
01/31/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* | |
01/29/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*OK TEMP C OF O. | |
01/08/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) 2 BURNER COOK TOP NOT STABILIZED WILL MOVE. DOES NOT HAVE APPROVED GAS LINE AS NECESSARY. 2.) RM #116 INSP. 03/06/2002 ACCESS PANEL TO FAN COIL IS SUFFICENT FOR MINIMAL SERVICE, <PREVENTIVE MAINT. ONLY> UMC SEC 319.3 ADDRESSES FUTURE REPLACEMENT WHEN NECESSARY! HOW WILL THIS BE ACCOMPLISHED? |
|
11/26/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) ACCESS STILL PROBLEM FAN COILS #46/45, RM. #116 EXHAUST BLOWER EF23, 2.) A. GREASE COLLECTION CUP ON BLOWER & HOOD. B.) EXHAUST BLWS ON ROOF. COVER FLEX DUCT COM. W/RAIN SHIELD 3.) ELIMINATE MOVEMENT ON COOKING LINE FLEX GAS CONNECTORS OR USE PROPER APPROVED FLEX GAS LINES. 4.) CHILLER PERM. LABELS/NUMBER INK IS ALREADY FADDING |