Permit Details

Status:
Issued
Type:
Commercial Building
Address NEW:
5500 S NOGALES HY
Apply Date:
01/17/2023
Applicant:
Cody Conca
Description:
Replacement Fire Station No. 14 for the City of Tucson, located on an undeveloped piece of property recently purchased and subdivided by the City of Tucson. The county APN has not been assigned but the new address will be 5500 South Nogales Highway.

Permit Reviews

Permit Number - TC-COM-0123-00490
Permit Status: Issued
Permit Description: Replacement Fire Station No. 14 for the City of Tucson, located on an undeveloped piece of property recently purchased and subdivided by the City of Tucson. The county APN has not been assigned but the new address will be 5500 South Nogales Highway.
Start Date Submittal Complete Date Status  
11/25/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 11/28/2025 APPROVED Review Details
05/05/2023 COMMERCIAL REVIEW - FULL v.3 05/23/2023 REQUIRES RESUBMIT Review Details
12/23/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 12/23/2025 REQUIRES RESUBMIT Review Details
11/01/2023 COMMERCIAL REVIEW - FULL v.4 11/14/2023 APPROVED Review Details
12/24/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.2 12/30/2025 APPROVED Review Details
03/24/2023 COMMERCIAL REVIEW - FULL v.2 04/26/2023 REQUIRES RESUBMIT Review Details
10/31/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 11/04/2025 APPROVED Review Details
02/01/2023 COMMERCIAL REVIEW - FULL v.1 03/06/2023 REQUIRES RESUBMIT Review Details
11/14/2023 RESTAMP - COMMERCIAL v.1 11/15/2023 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0123-00490
Permit Status: Issued
Permit Description: Replacement Fire Station No. 14 for the City of Tucson, located on an undeveloped piece of property recently purchased and subdivided by the City of Tucson. The county APN has not been assigned but the new address will be 5500 South Nogales Highway.
Total Outstanding Activity Conditions - 1
Date Name
12/22/2025 SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED.

Conditions

Permit Number - TC-COM-0123-00490
Permit Status: Issued
Permit Description: Replacement Fire Station No. 14 for the City of Tucson, located on an undeveloped piece of property recently purchased and subdivided by the City of Tucson. The county APN has not been assigned but the new address will be 5500 South Nogales Highway.
Date Description Comments
02/01/2023 Please contact Pima County Addressing to resolve your addressing issue related to FILL IN THIS SPACE. Addressing@pima.gov or 520-724-9512
12/22/2025 AIR BALANCING REPORT IS REQUIRED.
06/27/2024 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
11/15/2023 The Contractor you have added to your permit cannot be verified. Please contact staff to have the ROC number added to the account.
06/27/2024 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
06/27/2024 SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED.
06/27/2024 SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED.
06/27/2024 SPECIAL INSPECTION FOR FOUNDATION/EXCAVATION IS REQUIRED.
06/27/2024 Masonry Inspection Report submittal review is required.
12/22/2025 WATER STERILIZATION REPORT IS REQUIRED.
06/27/2024 SPECIAL INSPECTION FOR WOOD FRAMED DIAPHRAGMS AND SHEAR WALLS IS REQUIRED.
06/27/2024 Prior to project being finalized applicant must provide REPLACE THIS SECTION WITH THE REQUIRED DOCUMENT(S).

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0123-00490
Permite Description: Replacement Fire Station No. 14 for the City of Tucson, located on an undeveloped piece of property recently purchased and subdivided by the City of Tucson. The county APN has not been assigned but the new address will be 5500 South Nogales Highway.
Total Outstanding Inspections - 14
Last Inspection Date Description Inspector Results Comments
04/17/2025 COT - HCEL - Electrical Above Ceiling N/A Partial Pass 4/17/25: electrical above ceiling approved in rooms (112,116,108) Hard lid areas only.
04/01/2025 COT - HCBU - Firewall/Fire Barrier/Firestop N/A Partial Pass 4-1-25, partial pass on firewall inspection-verified fire caulking on 5/8" drywall up to the deck on dorm room's 122, 123, 124, 125, 126, 127, 136, 137, 138, 139, 140, 141. Okay to insulate at progress areas.
12/02/2024 COT - HCPL - Plumbing Progress N/A Partial Pass 8/20/24: North half of building Plumbing underground per plans. Pending corrections at laundry room and missing Clean out at dining room. Ok to backfill approved areas. Shading required.
8/21/24: North half of building plumbing underground per plans. Corrections were made . Ok to backfill.
9/6/24: plumbing Underground at Apparatus Bay per plans ok to backfill. Shading required.

Turnout room, decon shower , workshop. Approved. Okay to backfill progress areas. Shading required. 9/10/2024
11/15/24: county inspection at tap passed ok to cover the first 60 feet. Passed test at first section.
11/21/24: not ready
12/2/24: inspection of sanitary to cover on south east corner partial pass for 3" under test.
12/03/2025 COT - BULD - SWG Clearance N/A Not Applicable 12-3-25: not applicable.
12/23/2024 COT - HCBU - Excavation/Rebar/Zoning N/A Partial Pass 6/28/24: reinforcement per plan at exterior footings (Dorm Rooms, Day Room, Electric, Lobby, Training(excluding N. Wall), Secured Patio, Captains Office, kitchen, pantry, EMS, Staff patio)
7/3/24: phase 2 reinforcement at footings around exterior perimeter at rooms (144,143,145,146,147 and 149), footing type WF1 and WF2.
7/24/24: phase 3 reinforcement at footings per plan ok to proceed with concrete pour.
8/2/24: reinforcement per plan at perimeter wall West side of project and Half way of North side.
11/25/24: vertical and horizontal rebar reinforcement at Dorms South, North, East and West wall at 15'4" per plan ok to proceed.
12/23/24: inspection requested fell under DP inspector for site wall.
09/19/2024 COT - HCBU - Preslab N/A Partial Pass 9/19/2024: first pour north wing phase 1. Okay for concrete placement.
10/28/2024 COT - HCBU - Masonry Pregrout N/A Partial Pass Reinforcing steel, horizontal and vertical rebar for north wing cmu walls. N, S, and W walls of dorms, N, S, and W walls of day room, S wall of gym, N walls of public lobby, N, E, and S walls of training room, N, E, and W walls of captain's office; all from 0-4'8". N, E, and W walls of gym from 0-3'5". Okay to grout 1st lift. 10/28/2024
10/04/2024 COT - HCEL - Electrical Progress N/A Partial Pass 10/4/24: okay to back fill feeder area.
12/22/2025 COT - HCBU - CofO N/A Partial Pass 12-22-25: okay for Level 1 TCO.
NOTE: pending 3rd party for outdoor lighting.
12/22/2025 COT - HCEL - Outdoor Lighting N/A Partial Pass 12-22-25: pending 3rd party inspection report.
12/22/2025 COT - HCBU - Building Final N/A Re-inspection required 12-22-25: Decon room-is not label, extractor not installed, tail piece condensate is after p-trap to sink at Decon room ( must be installed before), missing light cover on recessed light in Decon bathroom, adjust restroom door to 5 pounds of pressure at restroom- check all interior doors-must be at 5 pounds of pressure, copper line for evap. cooler required a 1" air gap, water heater condensation lines require 1" air gap, F4 receptacle in workshop keeps tripping, add plastic bushings on 2-junction boxes for low voltage at E3 in apparatus bay, missing hammer arrestors for dishwashers, ADA restroom doors at 10 pounds of pressure-adjust to 5 pounds of pressure, cap galvanized pipe northwest exit of fitness room, install gfci receptacles next to drinking fountain of fitness room, adjust restroom door at dorm to 5 pounds of pressure, add labels to receptacles in EMS room,label for fire pump room missing, RTU disconnect boxes must be labeled, missing fuses at AC-7, MicroMeti at AC-7 is over amped, AC-6 over amped, label receptacle st roof, all rooftop units are over amped, flex duct connector must be protected from sun damage, properly support liquid tight from roof, extension bar required at roof hatch. Okay for Level 1 TCO.
12/22/2025 COT - HCEL - Electrical Final N/A Re-inspection required 12-22-25: Decon room-is not label, extractor not installed, tail piece condensate is after p-trap to sink at Decon room ( must be installed before), missing light cover on recessed light in Decon bathroom, adjust restroom door to 5 pounds of pressure at restroom- check all interior doors-must be at 5 pounds of pressure, copper line for evap. cooler required a 1" air gap, water heater condensation lines require 1" air gap, F4 receptacle in workshop keeps tripping, add plastic bushings on 2-junction boxes for low voltage at E3 in apparatus bay, missing hammer arrestors for dishwashers, ADA restroom doors at 10 pounds of pressure-adjust to 5 pounds of pressure, cap galvanized pipe northwest exit of fitness room, install gfci receptacles next to drinking fountain of fitness room, adjust restroom door at dorm to 5 pounds of pressure, add labels to receptacles in EMS room,label for fire pump room missing, RTU disconnect boxes must be labeled, missing fuses at AC-7, MicroMeti at AC-7 is over amped, AC-6 over amped, label receptacle st roof, all rooftop units are over amped, flex duct connector must be protected from sun damage, properly support liquid tight from roof, extension bar required at roof hatch. Okay for Level 1 TCO.
12/22/2025 COT - HCME - Mechanical Final N/A Re-inspection required 12-22-25: Decon room-is not label, extractor not installed, tail piece condensate is after p-trap to sink at Decon room ( must be installed before), missing light cover on recessed light in Decon bathroom, adjust restroom door to 5 pounds of pressure at restroom- check all interior doors-must be at 5 pounds of pressure, copper line for evap. cooler required a 1" air gap, water heater condensation lines require 1" air gap, F4 receptacle in workshop keeps tripping, add plastic bushings on 2-junction boxes for low voltage at E3 in apparatus bay, missing hammer arrestors for dishwashers, ADA restroom doors at 10 pounds of pressure-adjust to 5 pounds of pressure, cap galvanized pipe northwest exit of fitness room, install gfci receptacles next to drinking fountain of fitness room, adjust restroom door at dorm to 5 pounds of pressure, add labels to receptacles in EMS room,label for fire pump room missing, RTU disconnect boxes must be labeled, missing fuses at AC-7, MicroMeti at AC-7 is over amped, AC-6 over amped, label receptacle st roof, all rooftop units are over amped, flex duct connector must be protected from sun damage, properly support liquid tight from roof, extension bar required at roof hatch. Okay for Level 1 TCO.
12/22/2025 COT - HCPL - Plumbing Final N/A Re-inspection required 12-22-25: Decon room-is not label, extractor not installed, tail piece condensate is after p-trap to sink at Decon room ( must be installed before), missing light cover on recessed light in Decon bathroom, adjust restroom door to 5 pounds of pressure at restroom- check all interior doors-must be at 5 pounds of pressure, copper line for evap. cooler required a 1" air gap, water heater condensation lines require 1" air gap, F4 receptacle in workshop keeps tripping, add plastic bushings on 2-junction boxes for low voltage at E3 in apparatus bay, missing hammer arrestors for dishwashers, ADA restroom doors at 10 pounds of pressure-adjust to 5 pounds of pressure, cap galvanized pipe northwest exit of fitness room, install gfci receptacles next to drinking fountain of fitness room, adjust restroom door at dorm to 5 pounds of pressure, add labels to receptacles in EMS room,label for fire pump room missing, RTU disconnect boxes must be labeled, missing fuses at AC-7, MicroMeti at AC-7 is over amped, AC-6 over amped, label receptacle st roof, all rooftop units are over amped, flex duct connector must be protected from sun damage, properly support liquid tight from roof, extension bar required at roof hatch. Okay for Level 1 TCO.

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-0123-00490
Permit Description: Replacement Fire Station No. 14 for the City of Tucson, located on an undeveloped piece of property recently purchased and subdivided by the City of Tucson. The county APN has not been assigned but the new address will be 5500 South Nogales Highway.
Total Completed Inspections - 26
Date Description Inspector Results Comments
02/26/2025 COT - HCBU - Interior Shear Bracing Passed
02/26/2025 COT - HCBU - Framing Passed
07/28/2025 COT - HCEL - Electrical Above Ceiling Passed
08/21/2025 BULD - Electrical Clearance Passed Approved 1000A 3-phase Service panel - ECO Clearance to TEP is required for the new service
10/27/2025 TRSP - ROW - Final/Close-Out Passed
10/24/2025 COT - HCBU - Firewall/Fire Barrier/Firestop Passed 10-24-25: previously inspected and approved.
10/24/2025 COT - HCPL - Backwater Valve Passed 10-24-25: backwater valve approved.
10/24/2025 COT - HCPL - Plumbing Progress Passed 10-24-25: approved.
10/30/2025 COT - HCEL - Electrical Intermediate Passed
10/30/2025 COT - HCBU - Building Above Ceiling Passed Ok to set ceiling tiles
10/30/2025 COT - HCME - Mechanical Above Ceiling Passed Ok to set ceiling tiles
10/30/2025 COT - HCPL - Plumbing Above Ceiling Passed Ok to set ceiling tiles.
12/03/2025 COT - HCBU - Excavation/Rebar/Zoning Passed 12-3-25: approved.
12/03/2025 COT - HCBU - Preslab Passed 12-3-25: approved.
12/03/2025 COT - HCBU - Exterior Clips/Sheathing Passed 12-3-25: approved.
12/03/2025 COT - HCBU - Masonry Pregrout Passed 12-3-25: previously inspected & approved.
12/03/2025 COT - HCBU - Roof Nailing Passed 12-3-25: approved.
12/03/2025 COT - HCEL - Electrical Progress Passed 12-3-25: approved.
12/03/2025 COT - HCEL - Electrical Underground Passed 12-3-25: previously inspected.
12/03/2025 COT - HCME - Mechanical Intermediate Passed 12-3-25: mechanical intermediate approved.
12/03/2025 COT - HCME - Mechanical Progress Passed 12-3-25: approved.
12/03/2025 COT - HCPL - Plumbing Intermediate Passed 12-3-25: approved.
12/22/2025 COT - FCON - Fire - Final Passed
12/22/2025 COT - HCEL - Grounding/Bonding Passed 12-22-25: approved.
12/22/2025 COT - HCBU - Building Progress Passed 12-22-25: approved.
12/30/2025 ENGR Engineering Final Passed

Documents

File Name Document Type  
TUCSON FS NO. 14 SPECIAL INSP REQUIREMENTS REVISION-2025-11-25_V1.PDF DOCUMENTS VIEW
FIRE 14 TC-COM-0123-00490 FINAL-2025-10-31_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-CONS-322006 COT FS14 BLDG_V2_V1.PDF DOCUMENTS VIEW
CONS-CONS-322006 COT FS14 BLDG_V2_V1.PDF DOCUMENTS VIEW
GEOTECHNICAL REPORT -TUCSON FIRE STATION NO. 14_V1.PDF DOCUMENTS VIEW
SAFEBUILT_APPROVED_CHECK_V1_V1.PDF DOCUMENTS VIEW
SAFEBUILT_APPROVED_DRAINAGE REPORT_V1_V1.PDF DOCUMENTS VIEW
SAFEBUILT_APPROVED_GEOTECHNICAL REPORT_V1.PDF DOCUMENTS VIEW
SAFEBUILT_APPROVED_HYDRAULIC CALCULATIONS RA1_V1_V1.PDF DOCUMENTS VIEW
SAFEBUILT_STRUCTURAL RESPONSE CALCS_V1_V1.PDF DOCUMENTS VIEW
TUCSON FS 14_PERLMAN_RESPONSE LETTER_BUILDING_V1.PDF DOCUMENTS VIEW
TUCSON FS NO. 14 STRUCTURAL RESPONSE CALCS_V1.PDF DOCUMENTS VIEW
CONS-322006 COT FS14 BLDG_V2.PDF DOCUMENTS VIEW
GEOTECHNICAL REPORT -TUCSON FIRE STATION NO. 14_V1.PDF DOCUMENTS VIEW
TUCSON FS 14_PERLMAN_RESPONSE LETTER_BUILDING_V1.PDF DOCUMENTS VIEW
TUCSON FS NO. 14 STRUCTURAL RESPONSE CALCS_V1.PDF DOCUMENTS VIEW