Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T09CM02836
Permit Details
Apply Date:
10/23/2009
Applicant:
N/A
Description:
ADDT & RENOVATION:PEDIATRIC & MOTHER/BABY WING *A, B, & C*
Architects:
- HOBBS, WILLIAM SAMUEL
Contractors:
- LLOYD CONSTRUCTION COMPANY INC ,
Permit Reviews
Permit Number - T09CM02836
Permit Status: C of o
Permit Description: ADDT & RENOVATION:PEDIATRIC & MOTHER/BABY WING *A, B, & C*
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/14/2010 | RESUBMITTAL | 01/14/2010 | COMPLETED |
01/26/2011 | REVISION - WALK THRU | 01/26/2011 | COMPLETED |
02/22/2010 | REVISION - - 1ST | 02/22/2010 | COMPLETED |
02/22/2010 | REVISION - - 1ST | 03/16/2010 | COMPLETED |
03/16/2010 | REVISION - - 1ST | 03/29/2010 | COMPLETED |
04/05/2010 | REVISION - - 2ND | 04/13/2010 | COMPLETED |
04/12/2011 | REVISION - WALK THRU | 04/26/2011 | COMPLETED |
04/13/2010 | REVISION - - 3RD | 04/13/2010 | COMPLETED |
04/13/2010 | REVISION - - 3RD | 04/13/2010 | COMPLETED |
05/06/2010 | REVISION - - 4TH | 05/26/2010 | COMPLETED |
05/26/2010 | REVISION - - 4TH | 05/26/2010 | COMPLETED |
06/09/2010 | REVISION - - 5TH | 06/23/2010 | COMPLETED |
06/22/2011 | REVISION - - 1ST | 06/22/2011 | COMPLETED |
06/23/2010 | REVISION - - 6TH | 06/23/2010 | COMPLETED |
07/02/2010 | REVISION - - 7TH | 07/02/2010 | COMPLETED |
07/02/2010 | REVISION - - 7TH | 07/02/2010 | COMPLETED |
08/11/2010 | REVISION - - 8TH | 08/11/2010 | COMPLETED |
09/01/2010 | REVISION - - 9TH | 09/14/2010 | COMPLETED |
09/23/2010 | REVISION - 10TH | 09/23/2010 | COMPLETED |
09/23/2010 | REVISION - 10TH | 10/19/2010 | COMPLETED |
10/06/2010 | REVISION - WALK THRU | 10/06/2010 | COMPLETED |
10/23/2009 | PLANS OK TO SUBMIT - COMM | 10/23/2009 | COMPLETED |
10/26/2009 | COMMERCIAL NEW | 11/23/2009 | COMPLETED |
11/23/2009 | RESUBMITTAL | 12/21/2009 | COMPLETED |
12/21/2009 | RESUBMITTAL | 01/14/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09CM02836
Permit Status: C of o
Permit Description: ADDT & RENOVATION:PEDIATRIC & MOTHER/BABY WING *A, B, & C*
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/23/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T09CM02836
Permit Description: ADDT & RENOVATION:PEDIATRIC & MOTHER/BABY WING *A, B, & C*
Total Completed Inspections - 44
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2010 | FIRE - ALARM FINAL | LTHOMAS | Approved | PHASE II - MOTHER/BABY |
07/29/2010 | BUILDING PRE-SLAB | JBURGE | Approved | 1) P/A-P/D; P/13-P/2.5 OK TO POUR SLAB PROGRESS AREA |
08/24/2010 | PLUMBING - ROUGH, SOIL | BBENEDON | Approved | IVRS - Inspection :* |
08/31/2010 | PLUMBING - PRE SLAB | BBENEDON | Approved | IVRS - Inspection :* |
09/07/2010 | MECHANICAL - UNDERGROUND | MRAMBER | Approved | IVRS - Inspection :* 1) STEAM SUPPLY AND COND. RETURN UNDERGROUND (FEEDING MOTHER/BABY BLDG) HYDRO TEST OK BACK TO EXISTING OK TO INSULATE FITTINGS |
09/10/2010 | BUILDING - PROGRESS | JBURGE | Approved | IVRS - Inspection :* |
09/17/2010 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* 1) OK FOR FINAL MOTHER/BABY PHASE 3 |
09/17/2010 | BUILDING - FINAL | JBURGE | Approved | IVRS - Inspection :* 1) PHASE III: MOTHER/BABY OK TO OCCUPY ROOMS |
09/17/2010 | ELECTRIC - FINAL | RMORENO | Approved | IVRS - Inspection :* |
09/20/2010 | ROOF NAILING | JBURGE | Approved | IVRS - Inspection :*. 1) PARAPET WALLS AT G.L. MQ, MR-B-M10 R-S/P13; OK TO COVER PROGRESS AREAS |
09/20/2010 | FIRE SPKLR - FINAL | LTHOMAS | Approved | MOTHER AND BABY PHASE III |
10/14/2010 | PLUMBING - ROOF DRAINS | BBENEDON | Approved | IVRS - Inspection :* |
10/20/2010 | PLUMBING - YARD WTR LINE/TEST | BBENEDON | Approved | IVRS - Inspection :* |
10/20/2010 | PLUMBING - MD GAS/PRECONST MTG | BBENEDON | Approved | IVRS - Inspection :* |
10/27/2010 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* 1) 100 PSI TEST ON HOT WATER REHEAT MB 4A OK FOR INSULATION |
11/18/2010 | MECHANICAL - HYDRONIC PIPING | JMILITEL | Approved | IVRS - Inspection :* 100 PSI TEST ON REMANINING STEAM, CHILLED WATER, HEATING, HOT WATER, CONDENSATE RECOVERY. OK TO INSULATE. |
12/02/2010 | ELECTRIC - PROGRESS | RJIROUDE | Approved | IVRS - Inspection :* |
12/07/2010 | PLUMBING - PROGRESS | BBENEDON | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) THE OVER FLOW DRAIN ASSEMBLY CONNECTED TO THE UNLISTED SINKS AND LAVS, INSTALLED IN PATIENT ROOMS DO NOT APPEAR TO MEET THE REQUIREMENTS PRESCRIBED IN UPC SECTIONS 401.1 AND 301.1.3 THEY APPEAR TO PRESENT A POTENTIAL BACTERIA CONTAMINATION HAZARD 2) PROVIDE THE LISTING AS REQUIRED BY UPC 301.1.1 OR REMOVE THIS ASSEMBLY 3) BRIAN T WITH TMC, JASON WITH LLOYD AND FRED FROM R E ? |
12/09/2010 | ELECTRIC - INTERMEDIATE | RJIROUDE | Approved | IVRS - Inspection :* 1) OK MAKE UP TO XFMRS AND PANELS PEDS ELECTRID ROOM 2) OK FRONT CANOPY 3) OK CEILING ROOMS 15032,15036,15034,15035 AND 15038 |
12/09/2010 | REINFORCED MASONRY PRE-GROUT | JBURGE | Approved | IVRS - Inspection :* 1) MAIN ENTRY (EAST) GLAZED BLOCK VENEER TOPPED OUT AT 25'-4" OK TO GROUT |
12/10/2010 | PLUMBING - FINAL | BBENEDON | Approved | 1) AREAS A AND C APPROVED |
12/10/2010 | SHEET ROCK NAILING | JBURGE | Approved | IVRS - Inspection :* 1) MAIN ENTRY CANOPY (DENSGLASS SYSTEM) OK TO COVER |
12/10/2010 | PLUMBING - MEDICAL GAS/TEST | BBENEDON | Approved | IVRS - Inspection :* 1) 150 PSI TEST ON 02 AND AIR MAINS |
12/10/2010 | PLUMBING - INTERMEDIATE | BBENEDON | Approved | IVRS - Inspection :* 1) CLOSET FLANGES OK |
12/10/2010 | ELECTRIC - OUTDOOR LIGHTING | RMORENO | Approved | IVRS - Inspection :* |
12/17/2010 | ELECTRIC - UNDERGROUND | RMORENO | Approved | IVRS - Inspection :* 1) 4-4" STUBS AT PATIO, BLDG OK 2) 1 1/2 RIGID IN DITCH FOR CAN LIGHTS NORTHEAST SIDE COURT YARD |
12/21/2010 | FRAMING | JBURGE | Approved | IVRS - Inspection :* 1) MAIN ENTRY CANOPY-RC CHANNEL IN PLACE OK TO COVER |
12/21/2010 | EXCAVATION/LAYOUT REBAR & ZON | JBURGE | Approved | IVRS - Inspection :* 1) N.W. COURTYARD-3 SEAT WALL STEM WALLS OK TO POUR |
12/28/2010 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* 1) OK ABOVE CEILING MOTHER/BABY 4A & 4B |
12/28/2010 | BUILDING ABOVE CEILING | JBURGE | Approved | IVRS - Inspection :* 1) AREAS "C" & "D" COMPLETE OK TO SET CEILING TILES |
12/28/2010 | STEM WALL/RETAINING WALL | JBURGE | Approved | IVRS - Inspection :* 1) SEAT WALL FOOTING IN "C" AREA COURTYARD OK TO POUR FOOTINGS |
12/28/2010 | PLUMBING - ABOVE CEILING | RLEDONNE | Approved | IVRS - Inspection :* |
12/28/2010 | ELECTRIC - ABOVE CEILING | RJIROUDE | Approved | IVRS - Inspection :* |
06/14/2011 | SIGN - FINAL | JYBARRA | Approved | C/O ONLY |
06/14/2011 | RIGHT OF WAY - FINAL | P.Whiddon | Approved | |
06/15/2011 | NPPO - FINAL | MRUSSO | Approved | |
06/15/2011 | LANDSCAPE - FINAL | MRUSSO | Approved | |
06/15/2011 | ENGINEERING - FINAL | MRUSSO | Approved | |
06/16/2011 | PLUMBING - MEDICAL GAS/FINAL | BBENEDON | Approved | IVRS - Inspection :* |
06/21/2011 | ZONING - FINAL | pgehlen | Approved | Documents recorded as required. |
06/23/2011 | FIRE - FINAL | WMOTTO | Approved | |
06/23/2011 | CERTIFICATE OF OCCUPANCY | JBURGE | Approved | IVRS - Inspection :* |
06/23/2011 | OUTDOOR LIGHTING FINAL | RMORENO | Approved | IVRS - Inspection :* |
06/24/2011 | ELECTRIC - UFER | RMORENO | Approved | PER EL FINAL |