Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL ADDITION
Address:
5301 E GRANT RD
Apply Date:
10/23/2009
Applicant:
N/A
Description:
ADDT & RENOVATION:PEDIATRIC & MOTHER/BABY WING *A, B, & C*
Architects:
  • HOBBS, WILLIAM SAMUEL
Contractors:
  • LLOYD CONSTRUCTION COMPANY INC ,

Permit Reviews

Permit Number - T09CM02836
Permit Status: C of o
Permit Description: ADDT & RENOVATION:PEDIATRIC & MOTHER/BABY WING *A, B, & C*
Start Date Submittal Complete Date Status  
01/14/2010 RESUBMITTAL 01/14/2010 COMPLETED Review Details
01/26/2011 REVISION - WALK THRU 01/26/2011 COMPLETED Review Details
02/22/2010 REVISION - - 1ST 02/22/2010 COMPLETED Review Details
02/22/2010 REVISION - - 1ST 03/16/2010 COMPLETED Review Details
03/16/2010 REVISION - - 1ST 03/29/2010 COMPLETED Review Details
04/05/2010 REVISION - - 2ND 04/13/2010 COMPLETED Review Details
04/12/2011 REVISION - WALK THRU 04/26/2011 COMPLETED Review Details
04/13/2010 REVISION - - 3RD 04/13/2010 COMPLETED Review Details
04/13/2010 REVISION - - 3RD 04/13/2010 COMPLETED Review Details
05/06/2010 REVISION - - 4TH 05/26/2010 COMPLETED Review Details
05/26/2010 REVISION - - 4TH 05/26/2010 COMPLETED Review Details
06/09/2010 REVISION - - 5TH 06/23/2010 COMPLETED Review Details
06/22/2011 REVISION - - 1ST 06/22/2011 COMPLETED Review Details
06/23/2010 REVISION - - 6TH 06/23/2010 COMPLETED Review Details
07/02/2010 REVISION - - 7TH 07/02/2010 COMPLETED Review Details
07/02/2010 REVISION - - 7TH 07/02/2010 COMPLETED Review Details
08/11/2010 REVISION - - 8TH 08/11/2010 COMPLETED Review Details
09/01/2010 REVISION - - 9TH 09/14/2010 COMPLETED Review Details
09/23/2010 REVISION - 10TH 09/23/2010 COMPLETED Review Details
09/23/2010 REVISION - 10TH 10/19/2010 COMPLETED Review Details
10/06/2010 REVISION - WALK THRU 10/06/2010 COMPLETED Review Details
10/23/2009 PLANS OK TO SUBMIT - COMM 10/23/2009 COMPLETED Review Details
10/26/2009 COMMERCIAL NEW 11/23/2009 COMPLETED Review Details
11/23/2009 RESUBMITTAL 12/21/2009 COMPLETED Review Details
12/21/2009 RESUBMITTAL 01/14/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09CM02836
Permit Status: C of o
Permit Description: ADDT & RENOVATION:PEDIATRIC & MOTHER/BABY WING *A, B, & C*
Total Outstanding Activity Conditions - 1
Date Name
10/23/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T09CM02836
Permit Description: ADDT & RENOVATION:PEDIATRIC & MOTHER/BABY WING *A, B, & C*
Total Completed Inspections - 44
Date Description Inspector Results Comments
07/15/2010 FIRE - ALARM FINAL LTHOMAS Approved PHASE II - MOTHER/BABY
07/29/2010 BUILDING PRE-SLAB JBURGE Approved 1) P/A-P/D; P/13-P/2.5 OK TO POUR SLAB PROGRESS AREA
08/24/2010 PLUMBING - ROUGH, SOIL BBENEDON Approved IVRS - Inspection :*
08/31/2010 PLUMBING - PRE SLAB BBENEDON Approved IVRS - Inspection :*
09/07/2010 MECHANICAL - UNDERGROUND MRAMBER Approved IVRS - Inspection :*
1) STEAM SUPPLY AND COND. RETURN UNDERGROUND (FEEDING MOTHER/BABY BLDG) HYDRO TEST OK BACK TO EXISTING OK TO INSULATE FITTINGS
09/10/2010 BUILDING - PROGRESS JBURGE Approved IVRS - Inspection :*
09/17/2010 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
1) OK FOR FINAL MOTHER/BABY PHASE 3
09/17/2010 BUILDING - FINAL JBURGE Approved IVRS - Inspection :*
1) PHASE III: MOTHER/BABY OK TO OCCUPY ROOMS
09/17/2010 ELECTRIC - FINAL RMORENO Approved IVRS - Inspection :*
09/20/2010 ROOF NAILING JBURGE Approved IVRS - Inspection :*.
1) PARAPET WALLS AT G.L. MQ, MR-B-M10 R-S/P13; OK TO COVER PROGRESS AREAS
09/20/2010 FIRE SPKLR - FINAL LTHOMAS Approved MOTHER AND BABY PHASE III
10/14/2010 PLUMBING - ROOF DRAINS BBENEDON Approved IVRS - Inspection :*
10/20/2010 PLUMBING - YARD WTR LINE/TEST BBENEDON Approved IVRS - Inspection :*
10/20/2010 PLUMBING - MD GAS/PRECONST MTG BBENEDON Approved IVRS - Inspection :*
10/27/2010 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
1) 100 PSI TEST ON HOT WATER REHEAT MB 4A OK FOR INSULATION
11/18/2010 MECHANICAL - HYDRONIC PIPING JMILITEL Approved IVRS - Inspection :*
100 PSI TEST ON REMANINING STEAM, CHILLED WATER, HEATING, HOT WATER, CONDENSATE RECOVERY. OK TO INSULATE.
12/02/2010 ELECTRIC - PROGRESS RJIROUDE Approved IVRS - Inspection :*
12/07/2010 PLUMBING - PROGRESS BBENEDON Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) THE OVER FLOW DRAIN ASSEMBLY CONNECTED TO THE UNLISTED SINKS AND LAVS, INSTALLED IN PATIENT ROOMS DO NOT APPEAR TO MEET THE REQUIREMENTS PRESCRIBED IN UPC SECTIONS 401.1 AND 301.1.3 THEY APPEAR TO PRESENT A POTENTIAL BACTERIA CONTAMINATION HAZARD
2) PROVIDE THE LISTING AS REQUIRED BY UPC 301.1.1 OR REMOVE THIS ASSEMBLY
3) BRIAN T WITH TMC, JASON WITH LLOYD AND FRED FROM R E ?
12/09/2010 ELECTRIC - INTERMEDIATE RJIROUDE Approved IVRS - Inspection :*
1) OK MAKE UP TO XFMRS AND PANELS PEDS ELECTRID ROOM
2) OK FRONT CANOPY
3) OK CEILING ROOMS 15032,15036,15034,15035 AND 15038
12/09/2010 REINFORCED MASONRY PRE-GROUT JBURGE Approved IVRS - Inspection :*
1) MAIN ENTRY (EAST) GLAZED BLOCK VENEER TOPPED OUT AT 25'-4" OK TO GROUT
12/10/2010 PLUMBING - FINAL BBENEDON Approved 1) AREAS A AND C APPROVED
12/10/2010 SHEET ROCK NAILING JBURGE Approved IVRS - Inspection :*
1) MAIN ENTRY CANOPY (DENSGLASS SYSTEM) OK TO COVER
12/10/2010 PLUMBING - MEDICAL GAS/TEST BBENEDON Approved IVRS - Inspection :*
1) 150 PSI TEST ON 02 AND AIR MAINS
12/10/2010 PLUMBING - INTERMEDIATE BBENEDON Approved IVRS - Inspection :*
1) CLOSET FLANGES OK
12/10/2010 ELECTRIC - OUTDOOR LIGHTING RMORENO Approved IVRS - Inspection :*
12/17/2010 ELECTRIC - UNDERGROUND RMORENO Approved IVRS - Inspection :*
1) 4-4" STUBS AT PATIO, BLDG OK
2) 1 1/2 RIGID IN DITCH FOR CAN LIGHTS NORTHEAST SIDE COURT YARD
12/21/2010 FRAMING JBURGE Approved IVRS - Inspection :*
1) MAIN ENTRY CANOPY-RC CHANNEL IN PLACE OK TO COVER
12/21/2010 EXCAVATION/LAYOUT REBAR & ZON JBURGE Approved IVRS - Inspection :*
1) N.W. COURTYARD-3 SEAT WALL STEM WALLS OK TO POUR
12/28/2010 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
1) OK ABOVE CEILING MOTHER/BABY 4A & 4B
12/28/2010 BUILDING ABOVE CEILING JBURGE Approved IVRS - Inspection :*
1) AREAS "C" & "D" COMPLETE OK TO SET CEILING TILES
12/28/2010 STEM WALL/RETAINING WALL JBURGE Approved IVRS - Inspection :*
1) SEAT WALL FOOTING IN "C" AREA COURTYARD OK TO POUR FOOTINGS
12/28/2010 PLUMBING - ABOVE CEILING RLEDONNE Approved IVRS - Inspection :*
12/28/2010 ELECTRIC - ABOVE CEILING RJIROUDE Approved IVRS - Inspection :*
06/14/2011 SIGN - FINAL JYBARRA Approved C/O ONLY
06/14/2011 RIGHT OF WAY - FINAL P.Whiddon Approved
06/15/2011 NPPO - FINAL MRUSSO Approved
06/15/2011 LANDSCAPE - FINAL MRUSSO Approved
06/15/2011 ENGINEERING - FINAL MRUSSO Approved
06/16/2011 PLUMBING - MEDICAL GAS/FINAL BBENEDON Approved IVRS - Inspection :*
06/21/2011 ZONING - FINAL pgehlen Approved Documents recorded as required.
06/23/2011 FIRE - FINAL WMOTTO Approved
06/23/2011 CERTIFICATE OF OCCUPANCY JBURGE Approved IVRS - Inspection :*
06/23/2011 OUTDOOR LIGHTING FINAL RMORENO Approved IVRS - Inspection :*
06/24/2011 ELECTRIC - UFER RMORENO Approved PER EL FINAL

Documents

File Name Document Type  
TEMP C OF O_01-28-2011.TIF CERT OF OCC VIEW
None DOCUMENTS VIEW