Permit: T09CM02836

Parcel: 11012094A


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Permit Number - T09CM02836

Inspection Description - PLUMBING - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
06/23/2011 PLUMBING - PROGRESS Approved IVRS - Inspection :*
06/21/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
1) AREA D SINK CORRECTIONS COMPLETE
06/16/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
06/13/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
05/26/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
1) 4 INSTALLERS MAKING TIE IN TO ROOM OUTLETS WEST, AREA B
05/17/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
1) DOMESTIC PIPING K.T. 10597 AND WORK ROOM 10598 OK
2) MED GAS OUTLETS WITH TEST, WEST SIDE OF AREA B
04/27/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
04/25/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
04/20/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
04/18/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
04/13/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
1) MED GAS PROGRESS AND SHOWER DIVERTERS OK, CALL FOR DAILY PROGRESS INSPECTIONS
03/22/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
1) IRRIGATION SYSTEM IS DIRECTLY CONNECTED TO A HOSE BIBB WITHOUT APPROVED BACKFLOW PREVENTION (AT OLD JOB TRAILER LOCATION). PLEASE CORRECT THIS UNLAWFUL CROSS CONNECTION
2) MOTHER/BABY 5-SHOWER VALVE REPLACEMENT OK
02/25/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
1) PROVIDE APPROVED DRAINAGE TUBING WITHOUT RESTRICTIONS ON FILTER BLEED DOWN. CLAMP DRAIN HOSE CONNECTIONS STRAINER
02/02/2011 PLUMBING - PROGRESS Not ready for Inspection we will use plumbing progress for the remainder of this project
01/31/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
01/26/2011 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
01/11/2011 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
1) MET WITH VALERIE ROBINSON, SHIRLEY AND FRED REGARDING A SOLUTION FOR THE EXTERNAL OVERFLOW TUBING ON SINKS AND LAVS
2) WILL REMOVE UNLISTED FITTINGS
12/07/2010 PLUMBING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE OVER FLOW DRAIN ASSEMBLY CONNECTED TO THE UNLISTED SINKS AND LAVS, INSTALLED IN PATIENT ROOMS DO NOT APPEAR TO MEET THE REQUIREMENTS PRESCRIBED IN UPC SECTIONS 401.1 AND 301.1.3 THEY APPEAR TO PRESENT A POTENTIAL BACTERIA CONTAMINATION HAZARD
2) PROVIDE THE LISTING AS REQUIRED BY UPC 301.1.1 OR REMOVE THIS ASSEMBLY
3) BRIAN T WITH TMC, JASON WITH LLOYD AND FRED FROM R E ?
11/23/2010 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
11/09/2010 PLUMBING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) KEEP OPEN DRAIN PIPES PLUGGED DURING CONSTRUCTION
11/03/2010 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
11/02/2010 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
09/22/2010 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
1) CALL FOR DAILY MED GAS INSPECTION
08/16/2010 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
07/30/2010 PLUMBING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONTRACTORS NEED TO CORDINATE DEMO TO KEEP ALL OPEN DRAINS CAPPED! SECOND WARNING, SEE NOTES FROM 2/24 DO NOT LET THIS BECOME A PROBLEM
07/15/2010 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
07/08/2010 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
05/19/2010 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
1) CAP ALL OPENINGS TO PREVENT THE ESCAPE OF SEWER GASES
05/06/2010 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*