Permit: T09CM02836

Parcel: 11012094A


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09CM02836

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/23/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
05/16/2011 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) MOTHER BABY 5 FINAL PLUMBING OK
05/13/2011 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) ROOMS 10103 THRU 10118 INCLUDING 10988 ONLY COMOPLETE WATER TIGHT SEAL OFF OF FIXTURES AT FLOOR AND WALLS
01/26/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
AREAS A AND C:
1) HB VACUUM BREAKERS REQUIRED (COURTYARD)
2) PVC BETWEEN COPPER AND GALV UPSTREAM OF RP REQUIRES PRIMER
3) NEED BACKFLOW CERTS FOR ALL RPS
4) CAULK DFS
5) SEAL CLEANOUT PLUGS AT EXTERIOR
6) ICE AND COFFEE NOT YET INSTALLED
7) SINK CORRECTIONS IN PROGRESS OK
12/10/2010 PLUMBING - FINAL Not ready for Inspection 1) AREAS A AND C APPROVED
09/17/2010 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) PHASE 3 MOTHER BABY OK, WILL NEED TO SEE ICE MAKER
08/30/2010 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
08/17/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/11/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ICE MAKER IN ROOM 10941 IS UNSAFE AND NOT INSTALLED PER PLAN-SEE P-204 NOTE #5
2) CONNECT TO BACKFLOW ASSEMBLY, HARD PIPE DRAIN AND PROVIDE MIN AG.
3) ALSO COFFEE REQUIRES BACKFLOW PROTECTION PER UPC 602.1 AND 603.1 & PROVIDE APPROVED ASSEMBLY
07/15/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/21/2010 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) PHASE I OK, MOTHER-BABY
04/12/2010 PLUMBING - FINAL Partial Approval IVRS - Inspection :*