Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T09CM02836
Parcel: 11012094A

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02836
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
11/24/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/03/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
12/07/2009 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 5301 E GRANT
T09CM02836
Building Plan (1st Review)

TRANSMITTAL DATE: December 7, 2009

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved Development Package. Once all Planning and Development Services agencies have approved the Development Package zoning can approve the building plan.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved Development Package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm02836.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
12/11/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The calculations for the roof drains are acceptable but the sizes for the individual scuppers are not clearly stated. The minimum scupper width is the circumference of the required roof drain per Section 1101.11.2.1, UPC 2006. Detail J4/A311 shows a 10.25" wide scupper which will meet the minimum width requirements for roof areas less than or equal to 2,147 square feet. Clearly indicate the scupper widths for each occurrence. Reference: Section 103.2.3, UPC 2006.
12/11/2009 ELIZABETH LEIBOLD ENGINEERING REVIEW Denied TMC base plan not yet approved so building plans can not be approved.
12/14/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The submitted energy code compliance calculations for the building envelope refer to a roof construction as "other"; provide the supporting documentation as described in footnote b of the calculations. Reference: Section 101.4, International Energy Conservation Code 2006.
2. The submitted ventilation calculations illegible and also appear to be based on a different edition of the ASHRAE standard. Reference: Section 401.2, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/21/2009 CPIERCE1 OUT TO CUSTOMER Completed
12/21/2009 SUE REEVES REJECT SHELF Completed