Permit: T09CM02836

Parcel: 11012094A


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T09CM02836

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
08/24/2010 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
08/23/2010 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/20/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) SOIL PIPING AREA C, MATCH LINE TO COL. 4 OK
2) INSTALL TEST FITTINGS ?
3) RW MAN HOLE INSIDE BLDG
4) VAC TEST WITNESSED BY MATT WITH RBV
08/17/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
801.2.3 INDIRECT PIPING MAY NOT COMBINE
08/16/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
08/11/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
08/10/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
08/09/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
08/05/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
07/30/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*

1) STAFF TR AND SINKS, CONFERENCE ROOM AND CHILD ? BABY OK
07/29/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
07/23/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) AREA 'A' SOIL PIPE WITH TST THRU ABOVE SLAB TEST FITTINGS OK, ALL EXCEPT 15052
07/09/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) EAST OF COL. PC, SOIL PIPEW WITH TEST THRU CLEANOUT FITTINGS OK TO COVER
07/08/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
06/28/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
06/23/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) PUBLIC TRS 15059 & 60 ALSO MS 58 OK
2) NOTE: WILL NEED TO SEAL SHOWER DRAINS PER UPC INSTALLATION STANDARD #4 WHICH REQUIRES UTILIZATION OF DRAIN CLAMPING RING AND WEEP HOLES
06/21/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) SOIL PIPE CORRECTION FOR TR10129A OK TO COVER
2) INSTALL WRAPS FOR PRE-SLAB INSPECTION
06/18/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) TR 130A AND 129A OK
2) 129 EXISTING PIPING REQUIRES CORRECTION (LEAKING)
06/16/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
TRS 10132 & 10133A OK
06/15/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
05/19/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 8" SCHEDULE 80 PVC SEWER REPLACEMENT AND CONNECTIONS TO EXISTING AS SPECIFIED OK
05/18/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
SCH 80 MAIN REPLACEMENT W/ WATER TEST OK
05/17/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
PROVIDE WATER TEST, AND REDLINE CHANGES.
LETTER ON SITE FOR CHANGES FROM THOMAS SPARS PE
05/10/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) PROVIDE ENGINEER APPROVAL FOR ANY CHANGES