Permit Number: T09CM02836
Parcel: 11012094A

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T09CM02836
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEETS S-200/S-201; PLANS: PROVIDE EXPLANATION AND/OR STRUCTURAL CALCULATIONS FOR REVISED FOOTING SIZES.
2. SHEET A-316: EXPLAIN NOTE IN THE DRAWING CHANGES AS TO WHY THIS SHEET HAS CORRECTIONS BUT IS NOT ISSUED OR INCLUDED FOR REVIEW.
03/01/2010 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
03/05/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/05/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2010 DELMA ROBEY OUT TO CUSTOMER Completed
03/16/2010 FFIGUER1 REJECT SHELF Completed