Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/TEST
Permit Number - T09CM02836
Inspection Description - PLUMBING - MEDICAL GAS/TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2011 | PLUMBING - MEDICAL GAS/TEST | Approved | IVRS - Inspection :* | |
| 12/10/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) 150 PSI TEST ON 02 AND AIR MAINS |
|
| 12/07/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) MED GAS TIE INS TO AREA B ZONE AND EXISTING ROOM 10600 (45037) OK 2) CACTUS MEDICAL ON SITE FOR FIELD TESTING |
|
| 12/06/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) INSTALLING SOVS FOR 02 AND MED AIR TIE INS |
|
| 12/03/2010 | PLUMBING - MEDICAL GAS/TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 12/02/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 12/01/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 11/30/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 11/29/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) O2 AND MED AIR LINES IN SKY WALK 2) 2 INSTALLERS ? D OUTLETS |
|
| 11/24/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) 2 INSTALLER IN SKY WALK 2) LOG BOOK CHECKED |
|
| 11/23/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 11/22/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 11/19/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | 1) OUTLET CONNECTIONS WITH 75 PSI TEST 10119 | |
| 11/18/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 11/17/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 11/16/2010 | PLUMBING - MEDICAL GAS/TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 11/15/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 11/12/2010 | PLUMBING - MEDICAL GAS/TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 11/10/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 11/09/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 11/05/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 11/04/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) 3 INSTALLERS AT A/B 2) AREA A STILL UNDER TEST |
|
| 11/03/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 11/02/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) AREA A 75 PSI TEST ON ALL MED GAS, OUTLETS INSTALLED |
|
| 11/01/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/29/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) 4 INSTALLATIONS CONNECTING OUTLETS AREA A |
|
| 10/28/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/26/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) PRESSURE TEST AREA A MED GAS ALL SYSTEMS, 150 PSI |
|
| 10/22/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/21/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/20/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/19/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) 4 INSTALLERS ON MED GAS |
|
| 10/18/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/15/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* LOW PSI TEST, AREA C LABELS INSTALLED |
|
| 10/14/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/12/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/08/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/07/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/06/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/05/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 10/04/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) 40A, 39A, 38A AND 37A OK TO COVER WALL 2) CONTRACTOR CALL IN MED GAS INSPECTION |
|
| 10/01/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) LOG BOOK OK (ROOM READY FOR TEST) #127-128, 129, 130, 132 AND STUB IN TO #133-MED GAS |
|
| 09/30/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 09/29/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) GANG BOX 2) STORAGE 3) BOTTLES 4) 3 INSTALLERS WITH CERTS |
|
| 09/28/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 09/27/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) WALK THRU WITH PLUMBING CONTRACTOR FOR MED GAS HANGER UP PIPING IN HANGERS 2) CLEAN BOX FOR FIITING OK |
|
| 09/24/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 09/23/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) 2 INSTALLERS, LOG BOOK KEPT IN RELEE TRAILER OK 2) INSTALLER CERTS VERIFIED 3) CONTRACT 3RD PARTY VERFIER |
|
| 08/05/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 06/02/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 05/27/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 05/12/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) 150 PSI TEST ON VAC COFR 10949 THRU SERVICE VALVE 2) LOG BOOK OK |
|
| 05/10/2010 | PLUMBING - MEDICAL GAS/TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 04/22/2010 | PLUMBING - MEDICAL GAS/TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 04/12/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 04/09/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 03/30/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) ISOLATE CU FROM METAL GRID WIRES |