Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/09/2008 | PLANS OK TO SUBMIT - 3RD PARTY | 01/16/2008 | COMPLETED |
01/16/2008 | 3RD PARTY REVIEW-COMMERCIAL | 03/25/2008 | COMPLETED |
01/30/2008 | SITE | 03/24/2008 | COMPLETED |
03/25/2008 | POST 3RD PARTY REVIEW | 05/05/2008 | COMPLETED |
03/26/2008 | RESUBMITTAL - SITE | 05/05/2008 | COMPLETED |
05/05/2008 | RESUBMITTAL | 06/05/2008 | COMPLETED |
05/05/2008 | RESUBMITTAL - SITE | 06/05/2008 | COMPLETED |
06/12/2008 | RESUBMITTAL - SITE | 06/26/2008 | COMPLETED |
06/12/2008 | RESUBMITTAL | 06/30/2008 | COMPLETED |
06/30/2008 | RESUBMITTAL | 07/09/2008 | COMPLETED |
10/21/2008 | RESUBMITTAL | 11/03/2008 | COMPLETED |
12/04/2007 | PLANS OK TO SUBMIT - SITE | 01/29/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07CM04528
Permit Status: C of o
Permit Description: NEW MEDICAL OFFICE BLDG
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
12/04/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T07CM04528
Permit Description: NEW MEDICAL OFFICE BLDG
Total Completed Inspections - 40
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2008 | ELECTRIC - CONSTRUCTION POWER | RHOLLAND | Approved | |
12/03/2008 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* CORRIDOR 208 EXTERIOR SIDE TOP 4' |
12/03/2008 | PLUMBING - PRE SLAB | RMYERS | Approved | OK FOR CONCRETE AT LOBBY AREA S.T.O.I |
12/04/2008 | ELECTRIC - PROGRESS | RHOLLAND | Approved | IVRS - Inspection :* 1. NO FURTHER INSPECTION FOR UNDERGROUND UNTIL 02010 ADDED TO PERMIT 2. OK PVC STUBS AT DS2 & DS3 3. OK OUTSIDE CONDUIT TO MAIN SES 4. 17 - 4" PVC; 4 - 2" PVC |
12/17/2008 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* |
12/18/2008 | BUILDING PRE-SLAB | AQUIROZ | Approved | IVRS - Inspection :* 1ST FLOOR |
12/22/2008 | PLUMBING - ROOF DRAINS | BBENEDON | Approved | IVRS - Inspection :* MAIN BUILDING RWLS TESTED TO ROOF OK |
12/23/2008 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* OK TO POUR FOR UFER OK 3RD FLOOR CORRIDOR OK 2ND FLOOR STAIRWELL AND ELECTRIC ROOM 1. BOND COPPER TO REBAR 250.6 2. REMOVE EXCESS LOOPS IN M/C CABLE 3. USE APPROVED STRAPS ON VERTICAL RUNS |
12/23/2008 | ELECTRIC - UFER | RHOLLAND | Approved | IVRS - Inspection :* |
12/30/2008 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* 1) INTERIOR COLUMNS ON 2ND & 3RD FLOOR VTR OK TO COVER 2) THIRD FLOOR RESTROOM SOUTHSIDE DWV OK |
04/21/2009 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | |
04/21/2009 | PLUMBING - GAS PRESS TEST FNL | RMYERS | Approved | IVRS - Inspection :* |
04/28/2009 | ELECTRIC - TEMP POWER FOR TEST | DSANTACR | Approved | IVRS - Inspection :* 1) RECEIVED LETTER OF GFI MAIN TESTS, 2 BREAKERS 1000A AND 3000A 2) CONTR. TO INSURE ONLY AUTHORIZED PERSONS TO HAVE ACCESS TO ELECTRIC EQUIPMENT LOCK OUT AND TAG OUT EQUIPMENT |
04/29/2009 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED FOR "HOUSE PANEL" PER D. SANTACRUZ |
06/18/2009 | ELECTRIC - ABOVE CEILING | DSANTACR | Approved | IVRS - Inspection :* |
07/13/2009 | NPPO - FINAL | PMCLAUGH | Approved | |
07/13/2009 | LANDSCAPE - FINAL | PMCLAUGH | Approved | |
07/13/2009 | ENGINEERING - FINAL | DROBERTS | Approved | |
07/13/2009 | RIGHT OF WAY - FINAL | LLOPEZ | Approved | PER EMAIL |
07/13/2009 | SIGN - FINAL | JYBARRA | Approved | |
07/14/2009 | MECHANICAL - PROGRESS | JMILITEL | Approved | IVRS - Inspection :* |
07/14/2009 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |
07/14/2009 | BUILDING - PROGRESS | AQUIROZ | Approved | IVRS - Inspection :* |
07/14/2009 | U VALUE FOR WINDOW | AQUIROZ | Approved | IVRS - Inspection :* |
07/14/2009 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* |
07/14/2009 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* |
07/14/2009 | ROOF NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
07/14/2009 | REINFORCED MASONRY PRE-GROUT | AQUIROZ | Approved | IVRS - Inspection :* |
07/14/2009 | SITE - SEWER | RMYERS | Approved | IVRS - Inspection :* |
07/14/2009 | PLUMBING - YARD WTR LINE/TEST | RMYERS | Approved | IVRS - Inspection :* |
07/14/2009 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* |
07/14/2009 | FIRE - ALARM FINAL | LTHOMAS | Approved | |
07/14/2009 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
07/14/2009 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
07/28/2009 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* |
07/29/2009 | FIRE - FINAL | LTHOMAS | Approved | |
07/30/2009 | MECHANICAL - FINAL | MRAMBER | Approved | IVRS - Inspection :* PARTIAL L1-22 OK, L2-03 OK, L2-12 OK, S.L5, CORNER OK, 3RD FLR CHASE OK |
08/06/2009 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* 1) RECEIVED LETTER FROM KC MECHANICAL FOR 110 DEGREE SET POINT OF TEMPERING FOR HOT WATER SYSTEM FOR PUBLIC USE LAVS |
08/07/2009 | STUCCO MESH | AQUIROZ | Approved | |
08/07/2009 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* |