Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2009 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* 1) RECEIVED LETTER OF GFI MAIN TESTS, 2 BREAKERS 1000A AND 3000A 2) CONTR. TO INSURE ONLY AUTHORIZED PERSONS TO HAVE ACCESS TO ELECTRIC EQUIPMENT LOCK OUT AND TAG OUT EQUIPMENT |
|
| 04/15/2009 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1. OK UFER, BLDG. STEEL, WATER, GAS, BONDING 2. GFI MAIN BRKR TESTING REQUIRED PER 230.95 NEC 3. RECEIVED LETTER OF TORQUE |