Permit Number: T07CM04528
Parcel: 11615088L

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM04528
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2008 ROBERT SHERRY WATER REVIEW Approved
03/26/2008 DAVE MANN FIRE REVIEW Approved
03/28/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; West District; 70,357 Square Feet Medical Office; $340,879.67
03/28/2008 GERRY KOZIOL WWM REVIEW Denied NEEDS TO BUILD PUBLIC SEWER
03/31/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: St. Mary's Hospital - New Medical Building
T07CM04528
Building Plan (1st Review)

TRANSMITTAL DATE: March 31, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t07cm04528.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
04/23/2008 ELIZABETH EBERBACH ENGINEERING REVIEW Approved TO: Bob Tenor, RLS, EEC Engineering
SUBJECT: St Mary's Hospital New MOB Building structure Engineering Review
ADDRESS: 1601 W Saint Mary's Rd
PROPERTY OWNER: Carondelet St. Mary's Hospital and Health Center
LOCATION: T14S R13E Section 10
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: T07CM04528

SUMMARY: The package including the site, grading, and landscape plan sheets, and location map were received and reviewed by Engineering Division. Engineering recommends approval of the site plan. Submit a grading plan package for a grading permit prior to construction activity; see comments below. Site plan is approved however a Grading Permit will be required prior to site disturbance or building construction. The following are preliminary comments offered for subsequent grading permit application submittal.

GRADING PLAN PRELIMINARY COMMENTS:
1) DS Sec.2-05.2.4.D.1: Clarify extent of existing curbing along Anklam Road labeling type on grading plan.
2) DS Sec.3-01.10.Figure 6: From a driveway to local street a minimum of 18-ft curve radii is required. Dimension proposed radii on both the existing and proposed south entrances.
3) Clarify locations of ADA required truncated domes on grading plan sheet.
4) Tucson Code 26: Provide a SWPP for this project. The following are considerations when preparing the SWPPP:
a) Assure that the new NOI form is is used as well as signed and completed, for your project per recent ADEQ update to the CGP. The updated NOI, NOT, and Waiver Certification forms can be found at the ADEQ websites at: http://www.azdeq.gov/function/forms/appswater.html#cgp http://www.azdeq.gov/environ/water/permits/download/constnoi.pdf
b) Signatures for the operators on Certification Statements must be on the site copy of the Stormwater Pollution Prevention Plan (SWPPP) at, or before, commencement of construction. At minimum, one operator, either the engineer of record or the project manager shall sign the certification and submit with the SWPPP for the grading plan package.
c) State receiving waters in SWPP report. Also, show and label receiving waters on grading plan and/or a SWPPP exhibit.
d) Emergency notification information should be provided for the SWPPP report and exhibit. For safety, efficiency, and convenience of operators, at minimum add note to the SWPP plan: The operator shall report to ADEQ any noncompliance (including spills) which may endanger human health or the environment. The operator shall orally notify the office listed below within 24 hours: Arizona Department of Environmental Quality, 1110 W. Washington, 5th floor (5515B-1), Phoenix, AZ 85007, Office: 602-771-4466; Fax 602-771-4505
e) Assure specific sediment and erosion controls are provided on the SWPPP exhibit.
f) For inspection purposes, please fill out the enclosed "AZPDES - Posting Requirements" green sheet, and post at construction entrance of the site at beginning of construction activities and maintain this posted document throughout project construction.
5) Address the following dimension and elevation comments:
a) Clarify the low point near scupper in water harvest area.
b) Provide invert elevations on both ends of the scupper.
c) Provide dimensions for the water harvest area on the grading plan. See geotechnical setback comment 5d, below.
d) Clarify ADA access ramps on grading plan. Or state in response letter whether ADA access is located at the west side of building only.
e) Clarify roof drainage and locations of any type 1 scuppers to accommodate flows beneath proposed sidewalks.
6) Provide the following items with a grading permit application:
a) A copy of the approved Site Plan.
b) 3 copies of the revised grading plan.
c) 3 copies of the SWPPP.
d) A copy of a geotechnical letter stating acceptance of water harvesting area at the location adjacent to the building, or revise the configuration for the water harvesting area to a least a minimum distance of 20-ft from the building and dimension on the grading plan
e) Response letter.

If you have any questions, please call me at 837-4934.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2008 GERARDO BONILLA OUT TO CUSTOMER Completed