Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM04528
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/16/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. L2-01, 03, 05, 06, 31-10 UNIT DISCONNECTS IN VIOLATION 110.26 WORKING CLEARANCE - 2ND FLOOR 2. OK 3RD FLOOR LOBBY AND MAIN CORRIDOR |
|
06/10/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 3RD FLOOR 1. IDENTIFY FIRE ALARM BOXES 2. MAINTAIN WORKING CLEARANCES A/C DISCONNECTS 3. TIGHTEN LOOSE FITTINGS 4. VDV CABLING TO BE PLENUM RATED 2ND FLOOR 1. MAINTAIN WORKING CLEARANCES A/C DISCONNECTS 2. TIGHTEN LOOSE FITTINGS 3. FILL UNUSED OPENINGS 4. ONLY ONE CONDUCTOR TO LUG TERMINATION 5. SUPPORT M/C CABLE AS PER CODES 6. SUPPORT FLEX CONDUIT OVER 4' AS PER CODES |
|
05/29/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEC 300.11 SEISMICS FOR KEY SW BOXES NEED SEISMIC WIRES FOR EXITS AH DISCONNECT IN VIOLATION OF NEC 110.26 (WORKING CLEARANCE) L3-26, 3.27, 3.25, 3.21, 3.22, 3.17, 3.22, 3.17, 3.18, 3.15, 3.13, 3.14, 3.11, 3.8, 3.9, 3.6 |
|
03/11/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 1ST AND 2ND FLOOR BATHROOMS, JANITOR ROOMS, WALLS AND HARD LIDS OK 3RD FLOOR HARD LIDS BATHROOMS 1. OPEN WALLS COVERED WITHOUT INSPECTION AS DISCUSSED |
|
02/23/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |