Permit: T07CM04528

Parcel: 11615088L


Addresses:

395 N SILVERBELL RD

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/18/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/16/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. L2-01, 03, 05, 06, 31-10 UNIT DISCONNECTS IN
VIOLATION 110.26 WORKING CLEARANCE - 2ND FLOOR
2. OK 3RD FLOOR LOBBY AND MAIN CORRIDOR
06/10/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
3RD FLOOR
1. IDENTIFY FIRE ALARM BOXES
2. MAINTAIN WORKING CLEARANCES A/C DISCONNECTS
3. TIGHTEN LOOSE FITTINGS
4. VDV CABLING TO BE PLENUM RATED

2ND FLOOR
1. MAINTAIN WORKING CLEARANCES A/C DISCONNECTS
2. TIGHTEN LOOSE FITTINGS
3. FILL UNUSED OPENINGS
4. ONLY ONE CONDUCTOR TO LUG TERMINATION
5. SUPPORT M/C CABLE AS PER CODES
6. SUPPORT FLEX CONDUIT OVER 4' AS PER CODES
05/29/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEC 300.11
SEISMICS FOR KEY SW BOXES
NEED SEISMIC WIRES FOR EXITS

AH DISCONNECT IN VIOLATION OF NEC 110.26 (WORKING CLEARANCE) L3-26, 3.27, 3.25, 3.21, 3.22, 3.17, 3.22, 3.17, 3.18, 3.15, 3.13, 3.14, 3.11, 3.8, 3.9, 3.6
03/11/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 1ST AND 2ND FLOOR BATHROOMS, JANITOR ROOMS, WALLS AND HARD LIDS

OK 3RD FLOOR HARD LIDS BATHROOMS

1. OPEN WALLS COVERED WITHOUT INSPECTION AS DISCUSSED
02/23/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*