Permit: T07CM04528

Parcel: 11615088L


Addresses:

395 N SILVERBELL RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM04528

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
PARTIAL
L1-22 OK, L2-03 OK, L2-12 OK, S.L5, CORNER OK, 3RD FLR CHASE OK
07/29/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
07/22/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) 3RD FLOOR NORTH CHASE FSD EAST SIDE FAILED
2) S.E. CORNER OF CORRIDOR FSD HAS NO ACCESS DOOR 3RD FLOOR
07/21/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DUCT SMOKE DETECTOR L2-12 NOT WORKING L2-03 DSD FAILED
07/20/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) L1-01 DUCT SMOKE DETECTOR TEST FAILED
2) L1-22 DUCT SMOKE DETECTOR TEST FAILED
3) SOUTH CHASE 2ND FLOOR NORTH DUCT NOT CLOSING 100 PERCENT SUPPLY AIR TO 1ST FLOOR
4) ALL OTHER DUCT SMOKE DETECTORS AND FIRE SMOKE DAMPERS OK
07/17/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE INSTALLATION INSTRUCTIONS ON FIRE/SMOKE DAMPERS
07/16/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) MAKE ALL CORRECTIONS AT FIRE CHASES AND DAMPER FIRE WALLS