Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM04528
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* PARTIAL L1-22 OK, L2-03 OK, L2-12 OK, S.L5, CORNER OK, 3RD FLR CHASE OK |
|
07/29/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
07/22/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) 3RD FLOOR NORTH CHASE FSD EAST SIDE FAILED 2) S.E. CORNER OF CORRIDOR FSD HAS NO ACCESS DOOR 3RD FLOOR |
|
07/21/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) DUCT SMOKE DETECTOR L2-12 NOT WORKING L2-03 DSD FAILED |
|
07/20/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) L1-01 DUCT SMOKE DETECTOR TEST FAILED 2) L1-22 DUCT SMOKE DETECTOR TEST FAILED 3) SOUTH CHASE 2ND FLOOR NORTH DUCT NOT CLOSING 100 PERCENT SUPPLY AIR TO 1ST FLOOR 4) ALL OTHER DUCT SMOKE DETECTORS AND FIRE SMOKE DAMPERS OK |
|
07/17/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE INSTALLATION INSTRUCTIONS ON FIRE/SMOKE DAMPERS |
|
07/16/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MAKE ALL CORRECTIONS AT FIRE CHASES AND DAMPER FIRE WALLS |