Permit: T07CM04528

Parcel: 11615088L


Addresses:

395 N SILVERBELL RD

Inspection Status: Approved

Inspection History: MECHANICAL - PROGRESS

Date Description Inspector Results Comments
07/14/2009 MECHANICAL - PROGRESS Approved IVRS - Inspection :*
06/02/2009 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
1. ITEMS DATED 1/30/09 NOT COMPLETE
2. HYDRO TEST OK
03/11/2009 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
01/30/2009 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
1. PROVIDE FSD ACCESS DOORS
2. INSTALL FSD FLANGE RINGS PER INSTALL INSTRUCTIONS
3. FSD MOTOR & CONTROLS ARE TOO CLOSE TO WALL
4. SEAL ALL TAPS
5. OK TO INSULATE
01/16/2009 MECHANICAL - PROGRESS Not ready for Inspection IVRS - Inspection :*
01/15/2009 MECHANICAL - PROGRESS Not ready for Inspection IVRS - Inspection :*
01/14/2009 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
1. PROVIDE DUCT HANGERS AT APPROVED SPACING
2. PROVIDE PROPER RATED SLEEVE/PASS THROUGH AT ALL FIRE-SMOKE DAMPERS. MAINTAIN DAMPER BLADE WITHIN PLANE OF WALL
3. OK TO INSULATE DUCT ON SECOND FLOOR IN BAY AREAS ONLY