Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - PROGRESS
Permit Number - T07CM04528
Inspection Description - MECHANICAL - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/14/2009 | MECHANICAL - PROGRESS | Approved | IVRS - Inspection :* | |
06/02/2009 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* 1. ITEMS DATED 1/30/09 NOT COMPLETE 2. HYDRO TEST OK |
|
03/11/2009 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* | |
01/30/2009 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* 1. PROVIDE FSD ACCESS DOORS 2. INSTALL FSD FLANGE RINGS PER INSTALL INSTRUCTIONS 3. FSD MOTOR & CONTROLS ARE TOO CLOSE TO WALL 4. SEAL ALL TAPS 5. OK TO INSULATE |
|
01/16/2009 | MECHANICAL - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
01/15/2009 | MECHANICAL - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
01/14/2009 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* 1. PROVIDE DUCT HANGERS AT APPROVED SPACING 2. PROVIDE PROPER RATED SLEEVE/PASS THROUGH AT ALL FIRE-SMOKE DAMPERS. MAINTAIN DAMPER BLADE WITHIN PLANE OF WALL 3. OK TO INSULATE DUCT ON SECOND FLOOR IN BAY AREAS ONLY |