Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) RECEIVED LETTER FROM KC MECHANICAL FOR 110 DEGREE SET POINT OF TEMPERING FOR HOT WATER SYSTEM FOR PUBLIC USE LAVS |
|
| 08/04/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE DRAIN AND BACKFLOW CERTIFICATION FOR 009MZ #A16146 2) OBTAIN BOILER INSPECTION PERMIT AND HAVE BOILER INSPECTED 3) PROVIDE PIPING LABELING IN MECHANICAL ROOM 4) INSTALL CW TO TEMPERING VALVE PER PLAN PAGE 2.1 DETAIL 1 FOR MECHANICAL ROOM 110 5) DESIGN TEMPERED WATER IS 120 DEGREE, PROVIDE TEMPERING OF PUBLIC USE LAVS TO MAXIMUM 110 DEGREE 6) BACTERIA STERILIZATION REPORT ON SITE TO BE VIEWED BY R. MYERS 7) JANITOR SINKS AND ROOF TOP-OK |