Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM04528
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/14/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/12/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 3RD FLOOR BATHROOMS JANITOR AND STORAGE 1. 20' COIL TO BE IN CONTACT WITH DIRT |
|
03/11/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/04/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 1ST FLOOR ELEC. RM. WALLS |
|
01/21/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK EXTERIOR COLUMNS BOXES AND MC |
|
01/15/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO POUR FOR UFER OK 3RD FLOOR CORRIDOR OK 2ND FLOOR STAIRWELL AND ELECTRIC ROOM 1. BOND COPPER TO REBAR 250.6 2. REMOVE EXCESS LOOPS IN M/C CABLE 3. USE APPROVED STRAPS ON VERTICAL RUNS |
|
11/20/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 2ND FLOOR CORRIDOR |