Permit: T07CM04528

Parcel: 11615088L


Addresses:

395 N SILVERBELL RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM04528

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/14/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
06/04/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/07/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO INSULATE HOT PIPING IN MECH. RM.
04/24/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
2 - 2" MAKE UP WATER UNDERGROUND TO COOLING TOWERS OK TO COVER
03/17/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LOBBY RESTROOMS FLOORS 1-3 OK TO COVER
NEED TO SEE FIRST FLOOR CLOSET FLANGE
03/12/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/24/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST FLOOR OVERHEAD COPPER OK
TEST OK
01/27/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO INSULATE HOT PIPING AT FIRST FLOOR LOBBY
2. OK TO COVER WALLS AT THIS AREA AFTER PIPE INSULATION
3. WILL NEED TO SEE CLOSET FLANGES
01/09/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. N/H UNDERGROUND AT MECHANICAL ROOM #110
OK TO COVER
2. GAS PIPING FROM ELECTRICAL ROOM UP TO TWO ROOF TOP UNITS OK - PRESSURE TEST OK
3. FIRST FLOOR LOBBY RESTROOMS OK
N/H WATER TEST OK
4. 3" ROOF DRAIN AT LOBBY WATER TEST OK
OVERFLOW IS A SCUPPER
01/06/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3" K CW STUB INTO BUILDING W/BRAZED JOINT AND TEST OK
LEVEL 3 WATER MAINS OK TO INSULATE
TESTED TO 85 PSI
ISOLATE FROM METAL STUDS
12/30/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INTERIOR COLUMNS ON 2ND & 3RD FLOOR VTR OK TO COVER
2) THIRD FLOOR RESTROOM SOUTHSIDE DWV OK
12/22/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND LEVEL PUBLIC TRS; DWV W/TEST TO ABV 3RD LEVEL OK
CW WATER PIPING NOT SIZED PER PLAN
PROVIDE CLEARANCE FOR HW PIPE INSULATION
2ND LEVEL MAIN UNDER TEST, OK TO INSULATE
SOME CLAMPS MISSING