Permit: T05CM05519
Permit Details
Apply Date:
10/31/2005
Applicant:
MICKELBERG, PAUL DAVID
Description:
TI:DOT OFFICE 1ST & 2ND FLOOR ONLY
Architects:
- MICKELBERG, PAUL DAVID
Contractors:
- TRIUMPH BUILDERS SOUTHWEST LLC *C*
Permit Reviews
Permit Number - T05CM05519
Permit Status: C of o
Permit Description: TI:DOT OFFICE 1ST & 2ND FLOOR ONLY
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/25/2006 | POST 3RD PARTY REVIEW | 03/17/2006 | COMPLETED |
| 01/29/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 01/29/2007 | COMPLETED |
| 02/12/2008 | REVISION - - 1ST | 03/21/2008 | COMPLETED |
| 03/17/2006 | POST 3RD PARTY REVIEW | 08/17/2006 | COMPLETED |
| 03/21/2008 | OTHER | 10/21/2008 | COMPLETED |
| 10/01/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 11/06/2007 | COMPLETED |
| 10/31/2005 | PLANS OK TO SUBMIT - 3RD PARTY | 10/31/2005 | COMPLETED |
| 10/31/2005 | 3RD PARTY REVIEW-COMMERCIAL TI | 01/25/2006 | COMPLETED |
| 11/28/2007 | POST 3RD PARTY REVIEW | 12/19/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM05519
Permit Status: C of o
Permit Description: TI:DOT OFFICE 1ST & 2ND FLOOR ONLY
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/31/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T05CM05519
Permit Description: TI:DOT OFFICE 1ST & 2ND FLOOR ONLY
Total Completed Inspections - 40
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2006 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* RESTROOMS #116 & #119 OK FOR CONCRETE |
| 10/30/2006 | BUILDING PRE-SLAB | AALEGRIA | Approved | IVRS - Inspection :* IN COMPLIANCE WITH APPROVED PLANS AND SPEC. DETAIL ON S3.1 DETAIL 103 |
| 11/30/2006 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL |
| 12/07/2006 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* HOT WATER PIPING 100 PSI TEST 2ND, 3RD, 4TH FLOOR OK TO INSULATE |
| 12/07/2006 | FRAMING | LHANLY | Approved | IVRS - Inspection :* 1. OK TO 1 SIDE ALL CFS FRAMING. 2. PROVIDE SLIP JOINT AT HEAD OF WALLS PER DISCUSSION/PLAN REQUIREMENTS. 3. MID-SPAN BRIDGING REQUIRED. |
| 12/10/2006 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* 1. CALL 03050 FOR GAS INSPECTION 2. ROOF DRAINS TERMINATING AT LOBBY 100 OK 3. 4" ROOF DRAINS CONNECTING TO EXISTING AND RUN OUT THE FRONT OK 4. SINGLE 3" ROOF DRAIN OK 5. RESTROOMS #116 & #119 OK TO COVER WALLS ONLY 6. PIPING DEMO'D IN BASEMENT OK TO COVER 7. OK TO COVER JANITOR ROOM 206 |
| 12/11/2006 | PLUMBING - YARD WTR LINE/TEST | RMYERS | Approved | IVRS - Inspection :* 1. REQUIRE ENGINEERS APPROVAL OF YARDWATER REDLINES 2. GAS PENETRATION THRU ROOF REQUIRES FLASHING 3. CHECK ROOFTOP SIZING |
| 12/11/2006 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
| 12/29/2006 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* ONE SIDE ONLY |
| 12/29/2006 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection :* 1) MAKE SURE BOXES ARE PROPERLY MOUNTED-NEC 314.23 B1 2) MAKE SURE EMT PROPERLY SECURED/SUPPORTED-NEC 358.30 AND MAXIMUM 360 DEGREE IN BENDS NEC 358.26 3) PULL BOX SIZE INFORMATION-NEC 314.28 4) GUTTER CONDUCTOR DERATION INFORMATION-NEC 366.6/366.7 5) OK RESTROOM COVER 2ND THRU 4TH FLOORS |
| 03/12/2007 | TEP CLEARANCE - AM | BFLORES | Approved | TMPP PER R.MAJUTA |
| 05/10/2007 | U VALUE FOR WINDOW | LHANLY | Approved | IVRS - Inspection :* |
| 05/10/2007 | STUCCO MESH | LHANLY | Approved | IVRS - Inspection :* |
| 05/10/2007 | BUILDING ABOVE CEILING | LHANLY | Approved | IVRS - Inspection :* |
| 05/10/2007 | EXT METAL CLIPS/EXT SHEATHING | LHANLY | Approved | IVRS - Inspection :* |
| 05/22/2007 | PLUMBING - SEWER HCS CONNECT | RMYERS | Approved | IVRS - Inspection :* |
| 05/22/2007 | PLUMBING - GAS PRESS TEST FNL | RMYERS | Approved | IVRS - Inspection :* |
| 05/22/2007 | PLUMBING - ABOVE CEILING | RMYERS | Approved | IVRS - Inspection :* |
| 05/22/2007 | ELECTRIC - SERVICE UPGRADE | RMAJUTA | Approved | IVRS - Inspection :* |
| 05/22/2007 | ELECTRIC - TEMP POWER FOR TEST | RMAJUTA | Approved | IVRS - Inspection :* |
| 05/22/2007 | ELECTRIC - CONSTRUCTION POWER | RMAJUTA | Approved | IVRS - Inspection :* |
| 05/22/2007 | ELECTRIC - TEMPORARY SERVICE | RMAJUTA | Approved | IVRS - Inspection :* |
| 05/22/2007 | ELECTRIC - CABLE DROP | RMAJUTA | Approved | IVRS - Inspection :* |
| 06/05/2007 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
| 06/05/2007 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 06/05/2007 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 06/05/2007 | FIRE - FINAL | LTHOMAS | Approved | |
| 06/05/2007 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
| 06/06/2007 | ELECTRIC - ABOVE CEILING | RMAJUTA | Approved | IVRS - Inspection :* INTERIOR OK 1. OK OUTSIDE LIGHTING STONE SIDE 2. LIGHTING IN FRONT OF POCA COSA NOT IN 3. LIGHTING IN FRONT ALAMEDA SIDE NOT IN |
| 06/07/2007 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
| 06/29/2007 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection :* 1. CONNECT SUMP PUMP DIRECTLY INTO DISCONNECT REMOVE WIRING TO OLD BELL 2. REMOVE OLD WIRING TO CONDUITS ABOVE OLD SW GEAR AREA. |
| 06/29/2007 | OUTDOOR LIGHTING FINAL | RMAJUTA | Approved | IVRS - Inspection :* |
| 07/02/2007 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | |
| 07/03/2007 | NPPO - FINAL | ACONNOR | Approved | N/A |
| 07/09/2007 | SIGN - FINAL | JYBARRA | Approved | PERMIT OBTAINED |
| 07/11/2007 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |
| 12/27/2007 | BUILDING - FINAL | LHANLY | Approved | IVRS - Inspection :* |
| 12/28/2007 | ENGINEERING - FINAL | MRUSSO | Approved | |
| 12/31/2007 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* WHERE ARE YOUR ORIGINAL RED LINE DRAWINGS AS DRAWN BY GARY THOMPSON. THESE ORIGINAL RED LINES ARE ESSENTIAL TO DETERMINING THE EXTENT OF CHANGED WORK CONTRACTOR TO PAY REINSPECTION FEE |
| 03/21/2008 | PERMIT FINALED | LJACKSON | Approved |