Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/09/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BONDING JUMPER/CONDUCTORS ARE UNDERSIZED IN SECONDARY PULL BOX -- NEC 250.102 C 2. NEED PROPER WORKING CLEARANCE IN FRONT OF METER AND DISCONNECT (3' FRONT, 30" WIDE) NEC 110.26 3. TRANFORMER TO CLOSE TO BACK WALL - NEC 110.3B 4. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - NEC 250.6 5. SECURE TRANSFORMER TO SLAB, NEC 110.13 AND INSTALL SECONDARY CONDUCTORS 6. BONDING FOR SECONDARY RACEWAYS UNDERSIZED NEC 250.102 C 7. FINISH PERFORMANCE TEST NEC 230.95 C LETTER OF TORQUE RECEIVED TODAY |
|
| 03/08/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |