Permit: T05CM05519

Parcel: 117110610


Addresses:

149 N STONE AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/22/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/09/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BONDING JUMPER/CONDUCTORS ARE UNDERSIZED IN SECONDARY PULL BOX -- NEC 250.102 C
2. NEED PROPER WORKING CLEARANCE IN FRONT OF METER AND DISCONNECT (3' FRONT, 30" WIDE) NEC 110.26
3. TRANFORMER TO CLOSE TO BACK WALL - NEC 110.3B
4. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - NEC 250.6
5. SECURE TRANSFORMER TO SLAB, NEC 110.13 AND INSTALL SECONDARY CONDUCTORS
6. BONDING FOR SECONDARY RACEWAYS UNDERSIZED
NEC 250.102 C
7. FINISH PERFORMANCE TEST NEC 230.95 C

LETTER OF TORQUE RECEIVED TODAY
03/08/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*