Permit: T05CM05519

Parcel: 117110610


Addresses:

149 N STONE AV

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
06/07/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
05/24/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE 4" VENT ON WATER HEATER
WATER HEATER OK IN EQUIPMENT ROOM
FINISH WORK IN BASEMENT
05/22/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
RATED CHASE, 1ST FLOOR SUPPLY DUCT AT FIRE/SMOKE DAMPER. RETAINING ANGLE CUT, LOWER LEFT CORNER W/2
3/4 EMT CIRCUITS

1. 4TH/3RD/2ND FLOORS OK
2. 1ST FLOOR WEST SIDE, OK

CK. PENT HOUSE - WATER HTR. VENTING
1. DUCT INSUL.
2. RETURN AIR SENSOR ON AIR HANDLER/GAS FIRED WATER IN SPACE.
05/08/2007 MECHANICAL - INTERMEDIATE Partial Approval BASEMENT - COMPLETE FRAMING W/NECESSARY ACCESS THRU 1 HR. WALL TO ACCESS DUCT
FIRE DAMPER. SUGGEST 18" SQ.
05/07/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/30/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. 2ND FLOOR RETURN SOFFIT, OK TO FRAME & SEAL
LEAVE PROPER ACCESS PANELS AND RETURN DUCT IN NEW FRAMING.
2. IN LINE BLWR. ACCESS FOR MOTOR/SERVICE NEEDS CLEAR ACCESS AS NECESSARY.
3. BASEMENT EQUIP. ROOM PROVIDE ACCESS TO REACH FIRE DAM. ASSY.
04/20/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED DUCT INSIDE SHAFT. OK TO CLOSE SHAFT.
WATER PIPING PROGRESSING. RM 112 OK TO SHEETROCK
RM 115 OK TO SHEETROCK
04/12/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
SHAFT DUCTS INSULATION NOT ADEQUATELY SECURED.
OK TO PROCEED WITH SHAFT DUCTS.
03/28/2007 MECHANICAL - INTERMEDIATE Partial Approval DISCUSSED PRESSURE TEST PROCEDURES.
PROVIDE COMPLETE ACCESS TO ALL FIRE DAMPER INTERNAL COMPONENTS.
03/22/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE A DISCONNECTING MEANS AT EACH FAN COIL
OK TO SHEETROCK 2ND FLOOR LOBBY
02/22/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO SHEETROCK WALLS ON SECOND FLOOR LOBBY.
STILL NEED TO SEE RETURN FIRE DAMPER ANGLES ABOVE LID
02/13/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
4TH FLOOR RETURN DUCT FIRE DAMPER HAS HUGE GAP ABOVE. OK TO SHEETROCK CORRIDOR WALLS 3RD & 4TH FLOORS. CHECKED INSIDE SHAFT OK TO USE PARTIAL RETAINING ANGLES IN SHAFT WITH FULL ANGLES ON OPPOSITE SIDE. USE FIRE CAULK IN GAPS.
01/23/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
SUPPLY & EXHAUST IN RESTROOMS 2ND, 3RD, 4TH FLOORS OK TO SHEET ROCK.
01/22/2007 MECHANICAL - INTERMEDIATE Denied COULD NOT LOCATE MECH-CONTRACTOR OR SUPERINTENDENT. CHECKED ALL FLOORS.
01/05/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
WORK PROGRESSING
LYLE 977-8206
12/07/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
HOT WATER PIPING 100 PSI TEST
2ND, 3RD, 4TH FLOOR OK TO INSULATE
11/20/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
PENTHOUSE HOT WATER SUPPLY/RETURN DOWN VERTICAL CHASE TO LOWER FLOOR -- PRESS. TEST 32 100 PSI
11/17/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
PIPING TEST #1
HYRONIC/CHILLED WATER PIPING

1. PROVIDE REDLINE PLAN CONNECTING NEW HYDRONIC PIPING TO EXISTING SOURCE OF CENTRAL PLANT.
2. PRESS. TEST WEST SIDE OF BLDG. UP & OVER 2ND FLRS. ROOF -- 100 PSI.

MECH. CHASE VERTICAL CW PIPING, 100 PSI
11/13/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
VERTICAL 42 2 SQ SUPPLY AIR DUCT IN CHASE
2ND FLR. UP TO 4TH FLR.