Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/24/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE 4" VENT ON WATER HEATER WATER HEATER OK IN EQUIPMENT ROOM FINISH WORK IN BASEMENT |
|
| 05/22/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RATED CHASE, 1ST FLOOR SUPPLY DUCT AT FIRE/SMOKE DAMPER. RETAINING ANGLE CUT, LOWER LEFT CORNER W/2 3/4 EMT CIRCUITS 1. 4TH/3RD/2ND FLOORS OK 2. 1ST FLOOR WEST SIDE, OK CK. PENT HOUSE - WATER HTR. VENTING 1. DUCT INSUL. 2. RETURN AIR SENSOR ON AIR HANDLER/GAS FIRED WATER IN SPACE. |
|
| 05/08/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | BASEMENT - COMPLETE FRAMING W/NECESSARY ACCESS THRU 1 HR. WALL TO ACCESS DUCT FIRE DAMPER. SUGGEST 18" SQ. |
|
| 05/07/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/30/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. 2ND FLOOR RETURN SOFFIT, OK TO FRAME & SEAL LEAVE PROPER ACCESS PANELS AND RETURN DUCT IN NEW FRAMING. 2. IN LINE BLWR. ACCESS FOR MOTOR/SERVICE NEEDS CLEAR ACCESS AS NECESSARY. 3. BASEMENT EQUIP. ROOM PROVIDE ACCESS TO REACH FIRE DAM. ASSY. |
|
| 04/20/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED DUCT INSIDE SHAFT. OK TO CLOSE SHAFT. WATER PIPING PROGRESSING. RM 112 OK TO SHEETROCK RM 115 OK TO SHEETROCK |
|
| 04/12/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SHAFT DUCTS INSULATION NOT ADEQUATELY SECURED. OK TO PROCEED WITH SHAFT DUCTS. |
|
| 03/28/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | DISCUSSED PRESSURE TEST PROCEDURES. PROVIDE COMPLETE ACCESS TO ALL FIRE DAMPER INTERNAL COMPONENTS. |
|
| 03/22/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE A DISCONNECTING MEANS AT EACH FAN COIL OK TO SHEETROCK 2ND FLOOR LOBBY |
|
| 02/22/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO SHEETROCK WALLS ON SECOND FLOOR LOBBY. STILL NEED TO SEE RETURN FIRE DAMPER ANGLES ABOVE LID |
|
| 02/13/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 4TH FLOOR RETURN DUCT FIRE DAMPER HAS HUGE GAP ABOVE. OK TO SHEETROCK CORRIDOR WALLS 3RD & 4TH FLOORS. CHECKED INSIDE SHAFT OK TO USE PARTIAL RETAINING ANGLES IN SHAFT WITH FULL ANGLES ON OPPOSITE SIDE. USE FIRE CAULK IN GAPS. |
|
| 01/23/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUPPLY & EXHAUST IN RESTROOMS 2ND, 3RD, 4TH FLOORS OK TO SHEET ROCK. |
|
| 01/22/2007 | MECHANICAL - INTERMEDIATE | Denied | COULD NOT LOCATE MECH-CONTRACTOR OR SUPERINTENDENT. CHECKED ALL FLOORS. | |
| 01/05/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WORK PROGRESSING LYLE 977-8206 |
|
| 12/07/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HOT WATER PIPING 100 PSI TEST 2ND, 3RD, 4TH FLOOR OK TO INSULATE |
|
| 11/20/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PENTHOUSE HOT WATER SUPPLY/RETURN DOWN VERTICAL CHASE TO LOWER FLOOR -- PRESS. TEST 32 100 PSI |
|
| 11/17/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PIPING TEST #1 HYRONIC/CHILLED WATER PIPING 1. PROVIDE REDLINE PLAN CONNECTING NEW HYDRONIC PIPING TO EXISTING SOURCE OF CENTRAL PLANT. 2. PRESS. TEST WEST SIDE OF BLDG. UP & OVER 2ND FLRS. ROOF -- 100 PSI. MECH. CHASE VERTICAL CW PIPING, 100 PSI |
|
| 11/13/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* VERTICAL 42 2 SQ SUPPLY AIR DUCT IN CHASE 2ND FLR. UP TO 4TH FLR. |