Permit: T05CM05519

Parcel: 117110610


Addresses:

149 N STONE AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/22/2008 PLUMBING - FINAL Approved
01/09/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. HAVE REVISED APPROVED PLAN ON SITE
2. I CANNOT TELL WHAT CHANGES HAVE BEEN INCORPORATED INTO THE REVISED PLAN WITHOUT COMPARING IT TO THE ORIGINAL REDLINED PLAN
3. WHERE ARE YOUR ORIGINAL RED LINE DRAWINGS AS DRAWN BY GARY THOMPSON. THESE ORIGINAL RED LINES ARE ESSENTIAL TO DETERMINING THE EXTENT OF CHANGED WORK
CONTRACTOR TO PAY REINSPECTION FEE
12/31/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
WHERE ARE YOUR ORIGINAL RED LINE DRAWINGS AS DRAWN BY GARY THOMPSON. THESE ORIGINAL RED LINES ARE ESSENTIAL TO DETERMINING THE EXTENT OF CHANGED WORK
CONTRACTOR TO PAY REINSPECTION FEE
12/28/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
I CANNOT TELL WHAT CHANGES HAVE BEEN INCORPORATED INTO THE REVISED PLAN WITHOUT COMPARING IT TO THE ORIGINAL REDLINED PLAN
12/27/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
07/09/2007 PLUMBING - FINAL Partial Approval PENDING AS-BUILT PLAN APPROVAL
STILL REQUIRE REVISED APPROVED PLAN
PLUMBING FINAL OK SUBJECT TO APPROVED PLAN
STILL LOOKING FOR TEMP C OF O

1. PLEASE COMPLETE ALL ITEMS BEFORE CALLING FINAL HAVE REVISED APPROVED PLAN ON SITE
CONTINUED "NOT READYS" WILL RESULT IN A
REINSPECTION FEE
07/05/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. CONDENSATE DRAINS MAY BE TIED TOGETHER WHEN SIZED PROPERLY
2. INDIRECT WASTES MAY NOT BE TIED TOGETHER
I.E DRAIN FOR RPPBP, TANK DRAINS, ETC
3. INSTALL COUNTER SUNK TAPPED CLEANOUT PLUGS AT ALL CLEANOUT AND LEAVE COVERS OFF
4. SUMP PUMP INCOMPLETE
5. TEMPERING VALVES AT PUBLIC USE LAVATORIES
6. GRATES AND STRAINERS

INSPECTION STOPPED - CONTRACTOR REQUESTS TEMP C OF O
07/03/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*