Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* INTERIOR OK 1. OK OUTSIDE LIGHTING STONE SIDE 2. LIGHTING IN FRONT OF POCA COSA NOT IN 3. LIGHTING IN FRONT ALAMEDA SIDE NOT IN |
|
| 05/17/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. BASEMENT CEILING OK TO COVER, J-BOX ON EAST END TO BE EXTENDED TO CEILING TO BE MADE ACCESSIBLE. 2. PENTHOUSE FLOOR ELEVATOR RM - CONNECT WIRING TO DAMPER REMOVE ALL OLD WIRING NOT USED OUTSIDE LABEL ALL AC DISCONNECTS, FINISH WIRING INSIDE MECH RM. 3. LABEL ALL PANELS PERMANENTLY & DISCONNECTS 4. EM LIGHTS ON 4TH & 3RD FLOOR SOME NOT WORKING 5. HALL FIXTURES ON 4TH & 3RD FLOOR - LABEL INDICATES THEY ARE HUNG UPSIDE DOWN -- CORRECT PER LABEL 6. TRIMS ON FIXTURES IN 4TH & 3RD FLOOR CORRIDORS NOT IN. 7. EXITS -- FLOW METERS ON SPRINKLERS NOT CONNECTED. 8. AC UNIT EQUIPMENT ROOM 4TH & 3RD FLOORS NOT CONNECTED. 9. 1ST FLOOR CEILING NOT READY |