Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/09/2007 | MECHANICAL - FINAL | Partial Approval | - HAVE ENGINEER REVIEW AIR BALANCE REPORT & ADDRESS ANY PROBLEMS. - SMOKE DETECTOR TUBES HOLES MUST BE AGAINST AIR FLOW - ALL DUCT SMOKE DETECTORS MUST BE ACCESSIBLE - RELOCATE RESET SWITCHES AS NEEDED - ALTA 3 FAN NOT SHUTTING DOWN - PRE-TEST ALL DUCT SMOKE DETECTORS & DAMPERS - PRIOR TO NEXT INSPECTION OK TO FILE FOR TEMP C OF O |