Permit: T05CM05519

Parcel: 117110610


Addresses:

149 N STONE AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/22/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/04/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PARTIAL OK
PNL LIA OK --- OK TO ENERGIZE
TRAN C2 OK -- OK TO ENERGIZE
TRAN T1 OK -- OK TO ENERGIZE
PNL PIA, PIB OK -- OK TO ENERGIZE
PNL CPIA OK -- OK TO ENERGIZE
04/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PENTHOUSE OK
1. PH GUTTER OK
2. PH TRANS OK
3. 60A DISC VFD OK -- NEED TO SEPARATE 4-6 CONDUCTORS
4. 30A DISC VFD OK -- NEED TO SEPARATE 4-6 CONDUCTORS
5. 30A CW PUMP DISC OK WP-OK
6. 30A HW PUMP DISC OK HW OK
7. PH PNL OK

ELEVATOR ROOM - OK
1. 60A DISC OK -- MUST LABEL & INSTALL GRD BUSHING PRIMARY.
2. TRANS (STRAP CW BOND IN PH) OK - LABEL
MOVE GRD ON BUSHING IN TRANS 2" FLEX TO BOTTOM SCREW
04/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PARTIAL INTERMEDIATE - 1ST FLOOR ENTRY, SPECIAL SERVICES, RM 102
2. PNL L2A AT SWGEAR (MAIN) CB ON TERM OK GRD OK
3. 2ND FLOOR PNL L2A, PNL OK TER OK GRD OK
4. T-2 TRANS OK -- GRD TO SW GEAR GRD OK
5. PNL 2PA OK -- TRANS C-1 (CLEAR POWER) OK
6. PNL CP2A OK
7. 3/0 CU GRD FROM 2ND FL TRANS TO SW GEAR

OK TO ENERGIZE 2ND FLOOR
04/06/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) REVIEW FAN MOTORS BELOW FLOOR IF 1/8 HP IT ?
2) REVIEW ELEVATOR ROOM FOR LOCATION OF 45 KWA TRANS.
04/05/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/03/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
MEETING WAS SET UP TO DISCUSS ELEVATOR RM
CLEARANCES FOR ELECTRICAL EQUIPMENT, CONTRACTOR COULD NOT MAKE MEETING.
03/28/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
BASEMENT WALLS OK
03/22/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD & 4TH FLOOR CONDUITS UNDER RAISED FLOOR
OK ELECTRICAL CONDUITS ONLY
01/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSPECTION FOR SERVICE SECONDARY CONDUCTORS
OK TO COVER RACEWAYS IN STAIR AREA. BUILDING LINE TO TRANSFORMER WILL NEED CONCRETE ENCASEMENT PER
NEC 300.5 NOTE 5 IF 18" OF COVER CAN'T BE OBTAINED, CALL FOR INSPECTION OF RACEWAYS. IN THIS AREA AFTER CONCRETE ENCASEMENT. ALONG THE ENTIRE LENGTH OF SERVICE TRENCH, A WARNING RIBBON IS TO BE INSTALLED PER NEC 300.5 D3
01/22/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WALLS FOR FLOORS
#1 THROUGH #4
ALSO, OK HARD LID COVER IN BATHROOMS FOR THESE AREAS
12/29/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MAKE SURE BOXES ARE PROPERLY MOUNTED-NEC 314.23 B1
2) MAKE SURE EMT PROPERLY SECURED/SUPPORTED-NEC 358.30 AND MAXIMUM 360 DEGREE IN BENDS NEC 358.26
3) PULL BOX SIZE INFORMATION-NEC 314.28
4) GUTTER CONDUCTOR DERATION INFORMATION-NEC 366.6/366.7
5) OK RESTROOM COVER 2ND THRU 4TH FLOORS
10/30/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER INTERIOR UNDERGROUND PORTION OF PHONE BOOTH/L.V RUN, STUB TO EXTERIOR OF BUILDING.