Permit Details

Status:
Complete
Type:
Commercial Building
Address:
2627 E BENSON HY
Address NEW:
2627 E BENSON HY
Apply Date:
04/28/2006
Applicant:
Description:
OFFICE:STORAGE:NEW

Permit Reviews

Permit Number - T04CM04415
Permit Status: Complete
Permit Description: OFFICE:STORAGE:NEW
Start Date Submittal Complete Date Status  
01/22/2008 RESUBMITTAL - SITE 02/14/2008 COMPLETED Review Details
01/22/2008 RESUBMITTAL 02/14/2008 COMPLETED Review Details
03/07/2006 RESUBMITTAL 04/28/2006 COMPLETED Review Details
03/07/2006 RESUBMITTAL - SITE ALL 04/28/2006 COMPLETED Review Details
03/11/2005 SITE 04/15/2005 COMPLETED Review Details
03/11/2005 COMMERCIAL NEW 04/15/2005 COMPLETED Review Details
03/27/2007 RESUBMITTAL 05/07/2007 COMPLETED Review Details
03/27/2007 RESUBMITTAL - SITE 05/07/2007 COMPLETED Review Details
07/21/2014 REVISION - - 1ST 03/10/2016 COMPLETED Review Details
07/26/2007 RESUBMITTAL - SITE ALL 09/04/2007 COMPLETED Review Details
07/27/2007 RESUBMITTAL 09/04/2007 COMPLETED Review Details
10/04/2004 PLANS OK TO SUBMIT - COMM 03/11/2005 COMPLETED Review Details
10/04/2004 PLANS OK TO SUBMIT - SITE 12/03/2004 COMPLETED Review Details
10/13/2006 RESUBMITTAL 12/29/2006 COMPLETED Review Details
10/13/2006 RESUBMITTAL - SITE ALL 12/29/2006 COMPLETED Review Details
11/01/2006 OTHER 11/01/2006 COMPLETED Review Details
12/13/2007 RESUBMITTAL 01/10/2008 COMPLETED Review Details
12/14/2007 RESUBMITTAL - SITE 01/10/2008 COMPLETED Review Details
12/06/2022 BUILDING DEFERRED SUBMITTAL REVIEW v.1 01/03/2023 APPROVED Review Details

Conditions

Permit Number - T04CM04415
Permit Status: Complete
Permit Description: OFFICE:STORAGE:NEW
Date Description Comments
10/04/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.
04/13/2005 SHOP DRAWINGS REQUIRED FOR TJI 's With review and approval stamp by project engineer.
01/22/2008 SPECIAL INSPECTION IS REQUIRED FOR EXISTING MASONRY WALL AND FOOTING PER IBC 2006.

Outstanding Inspections

Permit Status: Complete
Permit Number: T04CM04415
Permite Description: OFFICE:STORAGE:NEW
Total Outstanding Inspections - 11
Last Inspection Date Description Inspector Results Comments
09/14/2022 PDSD Engineering Division Pre-Construction SITE N/A Complete (Recurring) {Activity date: 09/14/2022; Status: Continued; Inspector: MHERNANDEZ; Comment: Entered by VVERA1 - CN/ CONTRACTOR WILL RESCHEDULE.}
10/26/2022 COT - LCBU - Building Above Ceiling N/A Not Ready
10/27/2022 PDSD Site/Engineering Division - Landscaping N/A Not Ready
10/26/2022 COT - LCEL - Electrical Underground N/A Not Ready
10/26/2022 COT - LCPL - Plumbing Progress N/A Not Ready
10/26/2022 COT - LCME - Mechanical Final N/A Not Ready
10/27/2022 COT - LCPL - Plumbing Intermediate N/A Not Ready
10/26/2022 COT - LCEL - Temporary Service N/A Not Ready
10/26/2022 COT - LCPL - Rough Soil N/A Not Ready
10/26/2022 COT - LCEL - Electrical Above Ceiling N/A Not Ready
10/26/2022 COT - LCBU - Building Progress N/A Not Ready

Completed Inspections

Permit Status: Complete
Permit Number: T04CM04415
Permit Description: OFFICE:STORAGE:NEW
Total Completed Inspections - 27
Date Description Inspector Results Comments
03/13/2008 COT - LCEL - Grounding/Bonding Passed {Activity date: 03/13/2008; Status: Approved; Inspector: RJIROUDE; Comment: Entered by RJIROUDE - IVRS - Inspection :*}
03/28/2008 COT - LCBU - Stem Wall/Retaining Wall Passed {Activity date: 03/28/2008; Status: Approved; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*} ; {Activity date: 03/27/2008; Status: Denied; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :
See detailed listing on site.| 999*
BOND BEAM VERTICALS NEED TO BE 2" FROM TOP OF BOND BEAM AND AT LEAST 1" SEPARATION BETWEEN THEM}
05/02/2008 BULD - Electrical Clearance Passed {Activity date: 05/02/2008; Status: Approved; Inspector: JWEATHER; Comment: Entered by JWEATHE1 - TEC CLEARED PER D. SANTACRUZ}
08/20/2008 COT - LCBU - Excavation/Rebar/Zoning Passed {Activity date: 08/20/2008; Status: Approved; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*
RECEIVED SPECIAL INSPECTION FOR EXISTING WALL} ; {Activity date: 03/13/2008; Status: Partial Approval; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*
N,S,E FOOTINGS TO PLAN OK TO POUR FOOTING
NEEDS DOOR JAMB AND CORNER VERT REBAR NEEDS SPECIAL INSPECTION FOR EXISTING CMU WALL FOOTING W.SIDE AND BOND BEAMS}
08/20/2008 COT - LCBU - Masonry Pregrout Passed {Activity date: 08/20/2008; Status: Approved; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*
OK TO TOP OUT} ; {Activity date: 08/14/2008; Status: Partial Approval; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*
OK TO GROUT W & NORTH WALLS TO 12'4"
LOWER BOND BEAM IN PLACE} ; {Activity date: 08/01/2008; Status: Partial Approval; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*
EAST WALL OK TO TOPOUT} ; {Activity date: 07/31/2008; Status: Not ready for Inspection; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*} ; {Activity date: 07/21/2008; Status: Partial Approval; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*
S.WALL TO 19.5 OK TO TOP OUT
BOND BEAM IN PLACE

NEED RFI TO REPLACE LEDGER S-2 WITH JOIST
STILL NEED SPECIAL INSPECTION FOR PRE-EXISTING FOOTING} ; {Activity date: 07/17/2008; Status: Partial Approval; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*
E.WALL TO 13'6" DOUBLE BOND BEAM IN PLACE
SW TO 12' BOND BEAM IN PLACE} ; {Activity date: 07/09/2008; Status: Partial Approval; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*
2ND LIFT, ADD MISSING CORNER BAR} ; {Activity date: 05/21/2008; Status: Partial Approval; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*
1. PARTIAL OK TO GROUT 1ST LIFT REPAIR NORTH WALL
2. NEED SPECIFIC SPECIAL INSPECTION FOR PRE-EXISTING WALL AND FOOTING}
09/05/2008 COT - LCBU - Roof Nailing Passed {Activity date: 09/05/2008; Status: Approved; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :*} ; {Activity date: 09/04/2008; Status: Denied; Inspector: MHENSON; Comment: Entered by MHENSON - IVRS - Inspection :
See detailed listing on site.| 999*
1. PER PLAN SHEATHING TO BE NAILED (STAPLES USED)
2. NEEDS ANCHOR BOLTS ON SOUTH JOIST
3. LADDER NEEDS TO BE TIED OFF!}
02/22/2012 COT - LCBU - Preslab Passed {Activity date: 02/22/2012; Status: Approved; Inspector: AQUIROZ; Comment: Entered by AQUIROZ - IVRS - Inspection :*} ; {Activity date: 08/23/2011; Status: Denied; Inspector: GDABBS; Comment: Entered by GDABBS - IVRS - Inspection :
See detailed listing on site.| 999*
NO ACCESS GATE LOCKED} ; {Activity date: 08/26/2010; Status: Partial Approval; Inspector: GDABBS; Comment: Entered by GDABBS - IVRS - Inspection :*
1) WEST HALF OF BLDG ONLY-OK
2) NOTE: MUST HAVE #03015 PLUMBING PRE-SLAB APPROVAL BEFORE POUR

}
08/12/2013 COT - LCBU - Framing Passed {Activity date: 08/12/2013; Status: Approved; Inspector: MRAMBER; Comment: Entered by MRAMBER - IVRS - Inspection :*} ; {Activity date: 02/14/2013; Status: Denied; Inspector: MRAMBER; Comment: Entered by MRAMBER - IVRS - Inspection :
See detailed listing on site.| 999*NO ONE ON SITE, GATES LOCKED} ; {Activity date: 08/17/2012; Status: Partial Approval; Inspector: JBURGE; Comment: Entered by JBURGE - INFORMATION ONLY, KEEP PERMIT ACTIVE}
02/13/2014 COT - LCME - Mechanical Intermediate Passed {Activity date: 02/13/2014; Status: Approved; Inspector: MRAMBER; Comment: Entered by MRAMBER - IVRS - Inspection :*} ; {Activity date: 02/10/2014; Status: Not ready for Inspection; Inspector: MRAMBER; Comment: Entered by CSHARRA1 - 1. NO ADDRESS POSTED. PROVIDE PROPER ADDRESSING PRIOR TO NEXT INSPECTION OR A RE-FEE WILL BE ATTACHED
2. WORK NOT COMPLETE} ; {Activity date: 02/10/2014; Status: Not ready for Inspection; Inspector: MRAMBER; Comment: Entered by MRAMBER - IVRS - Inspection :*}
07/28/2014 COT - LCEL - Electrical Intermediate Passed {Activity date: 07/28/2014; Status: Approved; Inspector: DSANTACR; Comment: Entered by DSANTACR - IVRS - Inspection :*} ; {Activity date: 06/05/2014; Status: Denied; Inspector: DSANTACR; Comment: Entered by CSHARRA1 - ELECTRICAL FEEDER CONDUIT/SUBPANEL NOT PER PLAN} ; {Activity date: 06/05/2014; Status: Denied; Inspector: DSANTACR; Comment: Entered by DSANTACR - IVRS - Inspection :
See detailed listing on site.| 999*} ; {Activity date: 05/30/2014; Status: Not ready for Inspection; Inspector: RCANCINO; Comment: Entered by RCANCIN1 - NO ACCESS TO PROPERTY CALLED 631-7695 NO ANSWER ON SITE AT 0825}
09/19/2014 COT - HCBU - Interior Shear Bracing Passed {Activity date: 09/19/2014; Status: Approved; Inspector: DSANTACR; Comment: Entered by DSANTACR - IVRS - Inspection :*}
09/14/2022 COT - LCBU - Building Final Passed {Activity date: 09/14/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by VVERA1 - Approved} ; {Activity date: 03/29/2022; Status: Partial Approval; Inspector: TGAUSP; Comment: Entered by NGARCIA3 - - Partial, building inspection approved, pending final reports and special inspections, Fire and civil}
09/14/2022 COT - LCEL - Electrical Final Passed {Activity date: 09/14/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by VVERA1 - Approved} ; {Activity date: 03/10/2022; Status: Partial Approval; Inspector: TLUNDBERG; Comment: Entered by VVERA1 - PA} ; {Activity date: 03/09/2022; Status: Correction Required; Inspector: TLUNDBERG; Comment: Entered by VVERA1 - CO
1. Electrican required on site during inspection to open panels
2. Level area in front of main panel
3. Label all breakers in main panel and sub panel
4. No history of electric above-ceiling inspection and hard lid installed

} ; {Activity date: 03/09/2022; Status: Cancelled; Inspector: IVR USER; Comment: Entered by IVR USER - IVRS - RI canceled} ; {Activity date: 09/15/2015; Status: Denied; Inspector: MRAMBER; Comment: Entered by MRAMBER - IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio} ; {Activity date: 03/18/2015; Status: Denied; Inspector: MRAMBER; Comment: Entered by MRAMBER - IVRS - Inspection :
See detailed listing on site.| 999*}
09/14/2022 COT - LCPL - Yard Water Line Passed {Activity date: 09/14/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by VVERA1 - Approved} ; {Activity date: 05/02/2008; Status: Partial Approval; Inspector: RLEDONNE; Comment: Entered by RLEDONNE - IVRS - Inspection :*
1. TRACER WIRE OK
2. COMPLETE AND CALL BACK FOR FINAL} ; {Activity date: 05/01/2008; Status: Not ready for Inspection; Inspector: RLEDONNE; Comment: Entered by RLEDONNE - IVRS - Inspection :*
1. PROVIDE TRACER WIRE ON ALL UNDERGROUND YARD WATER PIPING OUTSIDE OF BUILDING, BLUE #18 THAT IS PVC
2. PSI TEST FROM METER TO 5' FROM BUILDING OK
3. PROVIDE BACKFLOW
4. CALL BACK FOR INSPECTION WHEN TRACER WIRE IS INSTALLED}
09/14/2022 COT - LCPL - Sewer Passed {Activity date: 09/14/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by VVERA1 - Approved}
09/14/2022 COT - LCPL - Plumbing Final Passed {Activity date: 09/14/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by VVERA1 - Approved}
10/26/2022 COT - FCON - Fire - Final Passed
11/10/2022 COT - LCBU - Building Above Ceiling Passed
11/10/2022 PDSD Site/Engineering Division - Landscaping Passed
11/10/2022 COT - LCEL - Electrical Underground Passed
11/10/2022 COT - LCPL - Plumbing Progress Passed
11/10/2022 COT - LCME - Mechanical Final Passed
11/10/2022 COT - LCPL - Plumbing Intermediate Passed
11/10/2022 COT - LCEL - Temporary Service Passed
11/10/2022 COT - LCPL - Rough Soil Passed
11/10/2022 COT - LCEL - Electrical Above Ceiling Passed
11/10/2022 COT - LCBU - Building Progress Passed

Documents

File Name Document Type  
T04CM04415 2025 MASS-UPLOAD.PDF DOCUMENTS VIEW
COFO_FINALCOFO_COMMERCIAL.PDF DOCUMENTS VIEW
SPECIAL INSPECTION CERTIFICATE-2022-11-29_V1.PDF DOCUMENTS VIEW
TRUSS CALCULATION AND LAYOUT_V1.PDF DOCUMENTS VIEW
T04CM04415_001.TIF CONSTRPLANS VIEW
T04CM04415_002.TIF CONSTRPLANS VIEW
T04CM04415_003.TIF CONSTRPLANS VIEW
T04CM04415_004.TIF CONSTRPLANS VIEW
T04CM04415_005.TIF CONSTRPLANS VIEW
T04CM04415_006.TIF CONSTRPLANS VIEW
T04CM04415_007.TIF CONSTRPLANS VIEW
T04CM04415_008.TIF CONSTRPLANS VIEW
T04CM04415_009.TIF CONSTRPLANS VIEW
T04CM04415_010.TIF CONSTRPLANS VIEW
T04CM04415_011.TIF CONSTRPLANS VIEW
T04CM04415_012.TIF CONSTRPLANS VIEW
T04CM04415_013.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW