Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T04CM04415
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/14/2005 | ROBERT SHERRY | WATER | REVIEW | Denied | City of Tucson Ordinance 1802 requires a reduced pressure backflow preventer to be located immediately after the water meter. Please show the RPBP on the drawings and include the pressure drop on the water calculations. Reference Section 103.2.3, UPC 1994. |
| 03/14/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Remove all references to the IRC, in Electrical Notes and all other places which apply. Applicable Code in NEC 2002. 2. Feeder load calculation methodology is not Code-compliant for this occupancy. NEC 220.30 allows this Optional Calculation for Dwelling Units only. Rework per NEC Article 220. 3. Minimum font size is 1/8". Enlarge as necessary. 4. Will review panel schedule after this has been enlarged. See Comment #3 above. 5. Will review Riser Diagram after this has been enlarged. See Comment #3 above. 6. Lighting Power Budget shall comply with 2000 IECC. Submit calculations. 7. Provide lighting fixture cut sheets. 8. Provide lighting fixture schedule, one which includes lighting fixture power requirements. 9. Demonstrate that exterior lighting fixtures are in compliance with 2000 IECC. 10. Demonstrate that exterior lighting fixtures are in compliance with the Outdoor Lighting Ordinance. 11. Demonstrate that exterior lighting fixtures are listed for wet location. 12. Provide TEP Available Fault Current, or specifically require the Contractor to do so. 13. Provide a disconnect for the Water Heater, per NEC Article 422 Part III. 14. HP #1 on Ckt 1,3 on Electrical Panel Schedule. Show location on Electrical Plans. 15. HP #1 is not located on Mechanical Plans, but is located and circuited on Electrical Plans. Coordinate with Mechanical and clarify. 16. Heat Strip #1 on Ckt 5,7 on Electrical Panel Schedule. Show location on Electrical Plans. 17. Show disconnect for HP #2 per NRC 440, Part III, or justify otherwise. 18. HP #2 is on electrical, but not on Mechanical Equipment schedule. Coordinate with Mechanical and clarify. 19. Heat Strip #2 on Ckt 6,8 on Electrical Panel Schedule. Show location on Electrical Plans. 20. Specify voltage and amperage rating of panel. 21. Provide power requirements for Exhaust Fans on Mechanical Equipment schedule. 22. Provide power for EF-1. Is listed on Mechanical Equipment schedule. No EF-1 specifically powered on electrical. 23. Provide power for EF-2. Is listed on Mechanical Equipment schedule. No EF-2 powered on electrical. 24. Provide maintenance receptacle for all HVAC equipment. Reference NEC 210.63. 25. Office and Conference Room shall have bi-level switching per IECC 805.2.1.1. |
| 03/14/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Remove all references to the International Residential Code, it is not the relevant code for this project. 2. Demonstrate energy code compliance using calculations based on the current code for commercial buildings. Reference Section 101.3, International Energy Conservation Code 2000. 3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference Section 803.2.1, IECC 2000. 4. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2000. 5. Provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that the work complies with the applicable codes. Reference Section 302.3, Uniform Administrative Code, 1997. 6. Revise the font size used on the drawings to a minimum of 10 points. Reference Section 302.3, Uniform Administrative Code, 1997. 7. Revise the Mechanical Notes, General Notes, and the Mechanical Equipment descriptions to accurately reflect this project. Reference Section 302.3, Uniform Administrative Code, 1997. 8. Provide the installed weight of the rooftop equipment. Provide the manufacturer and the listed model of the mechanical equipment (i.e. the heat pump and evaporative cooler) used as the basis for design. Reference Section 106.3.1, IMC 2000. 9. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit. Reference Section 302.1, IMC 2000. 10. Show the design for the return air ductwork. Reference Section 106.3.1, IMC 2000. 11. Specify the listed air filters to be provided with this project and show on the drawing where they are to be located. Reference Section 605, IMC 2000. 12. Show the size, routing, and termination of the condensate drain for the heat pump. Reference Section 307.2, IMC 2000 and Section 807.2, UPC 1994. 13. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000. 14. Ventilation for restrooms in public spaces requires a minimum of 75 CFM of mechanical exhaust per water closet or urinal or the amount of air supplied to the restroom, whichever is greater. Reference Section 403.2.1 and Table 403.3, IMC 2000. 15. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2000. |
| 03/15/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plumbing plans to a known scale. Reference Section 103.2.3, UPC 1994. 2. Revise the Plumbing Notes to accurately reflect this project. Reference Section 302.3, Uniform Administrative Code, 1997. 3. Provide fixture descriptions for all plumbing fixtures. Reference Section 103.2.3, UPC 1994. 4. Provide water, waste and vent isometrics. Reference Section 103.2.3, UPC 1994. 5. Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 1994. 6. Provide equipment data for the water heater. Reference Section 103.2.3, UPC 1994. 7. Provide water pressure and water pipe sizing calculations. Reference Section 610.4, UPC 1994. 8. Provide vent piping of sufficient size to comply with Section 904.1, UPC 1994. 9. Provide a shut off valve for the water supply at the entrance to the building. Reference Section 605.3, UPC 1994. |
| 03/28/2005 | DOUG WILLIAMS | ENGINEERING | REVIEW | Denied | Building plans may not be approved prior to site plan approval. Include a copy of the stamped approved site plan with each set of building plans submitted. |
| 04/01/2005 | SEPTIC APPROVAL | WWM | REVIEW | Denied | customer called by PC DEQ |
| 04/05/2005 | DAN CASTRO | ZONING | REVIEW | Denied | Zoning 4/5/05 Reviewer: Dan Castro 1. Building plans may not be approved by Zoning Review prior to obtaining site plan approval. 2. Site plan notes a maximum propsoed building height of 14. Elevation drawing on sheet 4 indicates a greater height. Revise plans to be consistent with one another. In addition, provide the building height measured fromd design grade. |
| 04/08/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 4/12/05 ACTIVITY NUMBER: T04CM04415 PROJECT NAME: New Office / Storage PROJECT ADDRESS: 2627 E. Benson Highyway ARCHITECT / ENGINEER: Talavera Design & Construction PROJECT REVIEWER: Christy Foreman TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) Provide restroom facilities per ANSI A117.1 2003 per Chapt. 11 Accessibility requirements. 2) Per City of Tucson Amendments section 1805.2 depth of footings equals minimum of 18 inches for values of table 1804.2 Justify detail 2 & 3 sht. 2. 3) Landing @ back door 1008.1.5. 4) Clarify thresholds per section 1008.1.6. 5) Roof covering classification - drainage and slope. 6) No soil report see code section 1615.1.1 site class D shall be used. Clarify / Justify calculations therefore table 1616.3(1) .50g less than or equal S DS 7) Clarify formula 16-18 section 1605.3.2 used per 2003 IBC (equation 16-18) .9D + E/1.4 8) Clarify calculations used per IBC sec 1617.4 see section 9.5.5 of ASCE 7 shall be used clarify use of this equation from this reference. 9) Clarify code section for equation for checking masonry wall wind w/e = ? Answer not readable / ledgable. 10) Provide complete section cut for each type of lintel to be used. Justify with calculations W10 x 22 or 2 - #4 rebar. Clarify welding of rebar. 11) Bearing length-missing detail 5, sht. 2 specifies length per schedule. 12) On building section callout for ledger connection detail is inaccurate. 13) Provide calculation justifying 5 x 3 x ½ angle reinforcing. 14) Clarify furr-out framing bottom & top plate connections also frequency of framing members. 15) All notes sht. 3 refer to IRC 2000 the City of Tucson has adopted the IBC 2003 for commercial buildings. 16) All text on documents shall be a minimum of 10 pt. Approximately 1/8" in height. 17) Clarify justification of sizing of footing. 18) Clarify justify numbers used for shear panel design. 19) Clarify / justify parapet per code section 704.11.1. 20) Cross Screen bending and provide calculations for 2x ledger at roof diaphragm. 21) Specify interior finishes for restroom. 22) Clarify / justify design per 1604.8.2 concrete & masonry walls. 23) Clarify / justify existing wall is adequate to be used as a building wall. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/15/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 04/15/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |