Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM04415
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Third request. Include the size of the building water supply pipe on the site plan. Reference Section 103.2.3, UPC 2003. 2. Show the size of the reduced pressure backflow preventer. 3. Tucson Water does not have a ¾" water meter; a 5/8" and a 1" water meter can be obtained from Tucson Water. 4. Specify the size of the reduced pressure backflow assembly being installed. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf 5. Show how the support frame for the water heater is to be anchored to the wall in an "approved manner" Reference Section 103.2.3, UPC 2003. |
| 08/03/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/03/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The restroom exhaust fan is controlled by a wall switch and when it is switched off, recirculation of the air from the restroom will occur because the heat pump will still be supplying air into the restroom. Revise the design to prevent this occurrence. Reference Section 403.2.1, IMC 2000 |
| 08/07/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Registrant shall seal, sign, and date Sheet E2. All other Electrical issues resolved. |
| 08/13/2007 | HEATHER THRALL | ZONING | REVIEW | Denied | The building footprints and heights do not match the site plan that is under review. Revise the site plan or the building plan to the accurate proposed dimensions. Contact me for an appointment time to come in to meet at the counter rather than resubmit. 837-4951 or Heather.Thrall@tucsonaz.gov |
| 08/29/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | An approved site plan is required prior to building plan approval. |
| 08/29/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | DATE: August 30, 2007 SUBJECT: 2627 E Benson Hwy Site Plan and Grading Plan- 5th Engineering Review TO: Francisco H. Maldonado LOCATION: T15S R14E Sec05, Ward 5 REVIEWERS: Jason Green, CFM ACTIVITY: T04CM04415 (site plan) and T06BU00512 (grading plan) SUMMARY: Engineering Division of Development Services Department has received and reviewed the resubmitted site plan (T04CM04415), grading plan (T06BU00512), drainage report (JE Fuller Hydrology and Geomorphology, Inc., June 9, 2006, with addendum dated 14MAY07), and Stormwater Prevention Pollution Plan (SWPPP), for the above referenced property. Engineering Division recommends approval of the site plan and grading plan at this time. § If any changes occur to the site plan or grading plan due to other Development Services Departments comments Engineering Division will be required to re-review the submittal and re-stamp the plans approved. If you have any questions, or to schedule an appointment, I can be reached at 837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division Development Services |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/04/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 09/04/2007 | GERARDO BONILLA | REJECT SHELF | Completed |