Permit Number: T04CM04415
Parcel: 14011007A

Address:
2627 E BENSON HY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04415
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2008 SEPTIC APPROVAL WWM REVIEW Approved
12/13/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/14/2007 DAVE MANN FIRE REVIEW Approved
12/17/2007 ROBERT SHERRY WATER REVIEW Approved
12/17/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/17/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/20/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE HANDICAP ACCESS FROM STREET TO FACILITY ENTRANCE PER IBC SECTION 1104.1.
2. 1:1 CURB SLOPE INDICATED ON SHEET C-2 AT HANDICAP ACCESS RAMP DETAIL DOES NOT MEET ANSI SECTION 405.2 REQUIREMENT.
3. TOILET INDICATED ON SHEET 3:
A) MUST HAVE HIGH/LOW DRINKING FOUNTAIN PER
ANSI SECTION 602.4.
B) LAVATORY MUST MEET CLEARANCES PER ANSI SECTION 606 AND YOUR SHEET 4.
C) SHOWER MUST MEET CLEARANCES PER ANSI
SECTION 608 AND YOUR SHEET 4.
4. PLAN SCALES ON SHEET 3 SHOULD BE REFERENCED AS 3/16" RATHER THAN 1/4".
5. SHEET 3 FLOOR PLAN: 1 HOUR FIRE WALL BETWEEN STORAGE AND OFFICE IS A CODE REQUIREMENT, NOT AN ISSUE TO BE VERIFIED.
6. ADDRESS COMMENT 4 OF REVIEW COMMENTS MADE 4/12/05 CONCERNING THRESHOLDS.
7. ADDRESS COMMENT 16 OF REVIEW COMMENTS MADE 4/12/05 CONCERNING MINIMUM 1/8" LETTERING.
8. NEED CALCULATIONS AND APPROPRIATE DETAILS CONCERNING THE TRANSFER OF LATERAL LOADS AT THE ROOF DECK INTO THE EXTERIOR WALL WHEN ROOF TRUSSES ARE PARALLEL TO THE EXTERIOR WALL.
9. ADDRESS COMMENT 23 OF REVIEW COMMENTS MADE 4/12/05 CONCERNING ADEQUACY OF THE EXISTING WALL. NEED CALCULATIONS AND APPROPRIATE DETAILS INDICATING:
A) STRUCTURAL ADEQUACY OF EXISTING WALL FOOTING WITH NEW VERTICAL AND LATERAL
LOADS (FOOTING SIZE VARIES ON SHEET 2,
SECTIONS 2 AND 3.
B) STRUCTURAL ADEQUACY OF NEW WALL
CONNECTION TO EXISTING WALL.
C) VERIFICATION OF EXISTING WALL CONSTRUCTION.
12/21/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/27/2007 HEATHER THRALL ZONING REVIEW Denied See building code comments and site and grading plan denial comments for ADA issues unresolved.
12/28/2007 JASON GREEN ENGINEERING REVIEW Denied A re-review of the site and grading plan is needed to assure ANSI compliance. A sidewalk must connect the street to the building. Resubmit the site plan and grading plan for over the counter approval once the sidewalk has been label and dimensioned.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/10/2008 VFLORES1 OUT TO CUSTOMER Completed
01/10/2008 SHANAE POWELL REJECT SHELF Completed