Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
17 W CONGRESS ST
Apply Date:
12/09/2003
Applicant:
JOHN HILL
Description:
REHABILITATION : HISTORIC FOX THEATRE
Contractors:
  • CONCORD COMPANIES INC

Permit Reviews

Permit Number - T03CM05695
Permit Status: C of o
Permit Description: REHABILITATION : HISTORIC FOX THEATRE
Start Date Submittal Complete Date Status  
01/06/2006 RESUBMITTAL 01/10/2006 COMPLETED Review Details
01/13/2005 REVISION 02/02/2005 COMPLETED Review Details
01/23/2004 RESUBMITTAL 03/29/2004 COMPLETED Review Details
02/23/2006 REVISION - - 1ST 03/13/2006 COMPLETED Review Details
02/24/2006 REVISION - - 2ND 03/02/2006 COMPLETED Review Details
03/10/2005 REVISION 04/12/2005 COMPLETED Review Details
03/10/2006 REVISION - - 3RD 04/14/2006 COMPLETED Review Details
03/16/2004 RESUBMITTAL 04/15/2004 COMPLETED Review Details
03/23/2006 REVISION - - 4TH 04/14/2006 COMPLETED Review Details
04/19/2005 REVISION 05/10/2005 COMPLETED Review Details
04/21/2006 REVISION - - 4TH 05/19/2006 COMPLETED Review Details
05/03/2004 RESUBMITTAL 06/18/2004 COMPLETED Review Details
05/10/2005 REVISION 05/18/2005 COMPLETED Review Details
07/19/2005 REVISION 07/21/2005 COMPLETED Review Details
07/20/2006 REVISION - - 5TH 07/25/2006 COMPLETED Review Details
09/09/2004 REVISION 09/09/2004 COMPLETED Review Details
09/09/2004 REVISION 10/20/2004 COMPLETED Review Details
10/18/2005 REVISION 11/28/2005 COMPLETED Review Details
10/25/2005 REVISION - 2ND 11/28/2005 COMPLETED Review Details
10/28/2004 RESUBMITTAL 11/04/2004 COMPLETED Review Details
11/04/2004 REVISION 11/17/2004 COMPLETED Review Details
11/28/2005 REVISION 12/12/2005 COMPLETED Review Details
12/06/2005 REVISION - 2ND 12/12/2005 COMPLETED Review Details
12/09/2003 PLANS OK TO SUBMIT - COMM 12/09/2003 COMPLETED Review Details
12/09/2003 COMMERCIAL TI 01/09/2004 COMPLETED Review Details
12/12/2005 REVISION 12/14/2005 COMPLETED Review Details
12/21/2005 REVISION - WALK THRU 12/21/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03CM05695
Permit Status: C of o
Permit Description: REHABILITATION : HISTORIC FOX THEATRE
Total Outstanding Activity Conditions - 1
Date Name
12/09/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T03CM05695
Permit Description: REHABILITATION : HISTORIC FOX THEATRE
Total Completed Inspections - 36
Date Description Inspector Results Comments
02/21/2003 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved 01075 - FIRESTOP
- SUBMITTALS ACCEPTED FOR HILTI FIRESTOP SYSTEMS
- PROGRESSION FS OK, BUT NO AREA COMPLETE
02/21/2003 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
12/28/2004 STEM WALL/RETAINING WALL AMATHIES Approved IVRS - Inspection :*53.0 DEX.131 CONC. SHEAR BAL. LEVEL.
10/05/2005 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*UNDERGROUND COMPLETE EXCEPT SUMP
WATER SERVICER TO INSIDE BLDG, AND STUBBED UP OUTSIDE OK
10/06/2005 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection :*
10/09/2005 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection :*
10/28/2005 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*OK TO COVER WALLS IN BASEMENT UNDER STAGE
12/01/2005 ELECTRIC - TEMPORARY SERVICE DSANTACR Approved
12/01/2005 TEP CLEARANCE - PM JKOZUCH Approved ECO PER E MAIL FROM J MORALES
12/19/2005 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
12/21/2005 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
12/21/2005 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*
12/21/2005 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
12/22/2005 ROOF NAILING LHANLY Approved IVRS - Inspection :*I NEED WELD REPORTS FOR ELECTRICAL ROOM
I NEED SPECIAL INSP REPORTS FOR CATWALK SUPPORT
12/22/2005 BUILDING PRE-SLAB LHANLY Approved IVRS - Inspection :*USE THIS TO CALL IN POST TENSION INSPECTION PER CIVILS
I NEED WELD INSPECTION REPORTS FOR CHILLER DECK
12/22/2005 SHEET ROCK NAILING LHANLY Approved IVRS - Inspection :*
12/22/2005 STUCCO MESH LHANLY Approved IVRS - Inspection :*
12/22/2005 FRAMING LHANLY Approved IVRS - Inspection :*
12/22/2005 EXT METAL CLIPS/EXT SHEATHING LHANLY Approved IVRS - Inspection :*
12/22/2005 REINFORCED MASONRY PRE-GROUT LHANLY Approved IVRS - Inspection :*
12/22/2005 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection :*
12/22/2005 FRAMING LHANLY Approved IVRS - Inspection :*
12/27/2005 MECHANICAL - PROGRESS CWILLIAM Approved IVRS - Inspection :*
12/28/2005 ELECTRIC - INTERMEDIATE CCLEMENS Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) EMERGENCY SYSTEM NOT COMPLETE AS OF 2:30 P.M.
12/28/2005 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*LITTLE PROGRESS HAS BEEN MADE SINCE LAST WEEK SAME ISSUES:
CENTERLINE TO SIDE WALL OR OBSTRUCTION 15" ADA = 18"
FINISH FLUSHOMETER
FINISH CONCESSION AREAS
GRATES AND STRAINERS MUST BE IN PLACE.
PROVIDE LISTING FOR ICE MAKER OR INSTALL BACKFLOW PROTECTIO.
12/29/2005 BUILDING - PROGRESS LHANLY Approved IVRS - Inspection :*
1. FIRE STOP PROGRESS OK - BUT PLEASE KEEP IN MIND THAT THERE ARE MANY OTHER AREAS AND ISSUES CONCERNING FIRE SEPARATION AND PROTECTION.
2. ONE BIG ISSUE IS THAT 3 HR FLOOR CEILING ASSEMBLY BETWEEN STAGE RIGHT EXIT PASSAGE AND BASEMENT INCIDENTAL USE AREA IS INCOMPLETE. STRUCTURE IS PARTIALLY WOOD FRAME.
12/29/2005 ELECTRIC - PROGRESS CCLEMENS Approved IVRS - Inspection :*CLOSE OFF ALL J-BOX'S AND OPEN WIRING IN ANY AREA THAT ARE ACCESSIBLE TO THE PUBLIC
INSTALL ALL DOORS ON AREAS THAT ARE NOT TO BE ACCESSED TO PUBLIC
EMERGENCY LIGHTS NORTHEAST ALLEY EXIT AND EXTERIOR ELECTRICAL ROOM NEED TO BE WORKING
12/30/2005 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245$ OK TO OCCUPY BUILDING FOR THE PURPOSE OF DEC 31 ST CELEBRATION ONLY
PLEASE CALL IN FINAL INSPECTIONS AS WORK BECOMES COMPLETED. MAKE SURE THERE IN NO OPEN WIRING IN AREAS ACCESSIBLE TO THE PUBLIC
12/30/2005 BUILDING - FINAL LHANLY Approved IVRS - Inspection :*
FOR SATURDAY NIGHT PARTY - TCO YOU NEED:
1. FINISH SEATING ASSEMBLY
2. REMOVE ALL SCAFFOLD, LADDERS, GENERATORS, BOXES, ETC. FROM AISLES, CORRIDORS AND SEATING AREAS.
3. REMOVE STRAP FROM STONE EXIT.
12/31/05 -- OK TCO FOR NEW YEARS PARTY
12/30/2005 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*
12/30/2005 FIRE - FINAL LTHOMAS Approved
12/30/2005 FIRE SPKLR - FINAL LTHOMAS Approved
08/22/2006 ELECTRIC - ABOVE CEILING CCLEMENS Approved
08/22/2006 ELECTRIC - UFER CCLEMENS Approved
08/31/2006 PLUMBING - ABOVE CEILING SLONG Approved
09/01/2006 SIGN - FINAL JYBARRA Approved Spoke to Julie Ybarra this morning (9/1/06, 8:00 AM) and she said that the Fox could be approved and closed

Documents

File Name Document Type  
C OF O_09-01-2006.TIF CERT OF OCC VIEW
None DOCUMENTS VIEW