Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM05695
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
| 12/28/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) EMERGENCY SYSTEM NOT COMPLETE AS OF 2:30 P.M. |
|
| 12/27/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*EQUIPMENT GROUND'S UNDER SIZED " DPB" TO DINNER RACK MAKE SURE TO CONNECT EQUIPMENT GROUND WHEN HANGING LIGHT FIXTURES REPAIR BONDING BUSHING IN TRANSFORMER " T2" GENERATOR NOT STARTING @ THIS POINT NOTE: SERVICE GFI TEST AND TORQUE REPORTS HANDED IN TODAY. |
|
| 12/15/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*NO INSPECTION REQUESTED TODAY, TOUCHED BASE WITH ROB, WALKED AROUND, LOOKED AT ROOF TOP CHILLER AND GENERATOR, SWITCHGEAR ALL NOT WIRED YET, TOOK A LOOK DOWN IN THE DRESSING ROOM AREA'S. I HAVE SOME CONCERNS ABOUT RACEWAY SUPPORT, ACCESS TO J-BOX'S AND J-BOX SIZE'S FOR CONDUCTOR FILL AND BENDING RADIUS. | |
| 12/08/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*TALKED TO JEFF-ELECTRICAL CONTRACTOR NO IN TODAY, TRANSFORMERS NOT FINISHED | |
| 12/06/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*WALKED THROUGH WITH ROB ( ELECTRICAL FOREMAN) HE WILL START CALLING IN ALL ELECTRICAL LEADING UP TO FINAL SERVICE HOT | |
| 11/30/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO CLEAR TEMP POWER SUBJECT TO BOND FOR TESTING POWER OBTAINED THRU PERMIT OFFICE OK TO ENERGIZE PANEL ??? AFTER BONDING JUMPER INSTALLED A TRANSFORMER OK TO ENERGIZE PANEL " Y" NOTE: BOND BUILDING STEEL AND CONDUCT TEST FOR SERVICE GFCI PER EQUIPMENT INSTRUCTIONS |
|
| 11/08/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*COULD NOT LOCATE CONTR. RECALL INSP |
|
| 10/28/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/18/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK ROUGH WALLS AT STAGE BASEMENT AREA. | |
| 08/04/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CALL BACK WHEN ACCESSIBLE |
|
| 06/21/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ORCHESTRA PIT-PVC CONDUITS FOR COMM, SOUND & POWER. | |
| 06/16/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/19/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ROUGH IN OF TECH ROOM AND WIRING OF 2 PANELS IN BASEMENT STORAGE |
|
| 04/15/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*RMS. 102, 103, 105 | |
| 04/08/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BASEMENT LEVEL ROOMS 004, 002, 005, STORAGE & BATHROOM | |
| 03/18/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ROUGH WALLS OK TO COVER BASEMENT LOUNGE RM 001. | |
| 01/30/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |