Permit: T03CM05695

Parcel: 117120340


Addresses:

17 W CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM05695

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2006 ELECTRIC - INTERMEDIATE Approved
12/28/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) EMERGENCY SYSTEM NOT COMPLETE AS OF 2:30 P.M.
12/27/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*EQUIPMENT GROUND'S UNDER SIZED " DPB" TO DINNER RACK
MAKE SURE TO CONNECT EQUIPMENT GROUND WHEN HANGING LIGHT FIXTURES
REPAIR BONDING BUSHING IN TRANSFORMER " T2"
GENERATOR NOT STARTING @ THIS POINT
NOTE: SERVICE GFI TEST AND TORQUE REPORTS HANDED IN TODAY.
12/15/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*NO INSPECTION REQUESTED TODAY, TOUCHED BASE WITH ROB, WALKED AROUND, LOOKED AT ROOF TOP CHILLER AND GENERATOR, SWITCHGEAR ALL NOT WIRED YET, TOOK A LOOK DOWN IN THE DRESSING ROOM AREA'S. I HAVE SOME CONCERNS ABOUT RACEWAY SUPPORT, ACCESS TO J-BOX'S AND J-BOX SIZE'S FOR CONDUCTOR FILL AND BENDING RADIUS.
12/08/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*TALKED TO JEFF-ELECTRICAL CONTRACTOR NO IN TODAY, TRANSFORMERS NOT FINISHED
12/06/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*WALKED THROUGH WITH ROB ( ELECTRICAL FOREMAN) HE WILL START CALLING IN ALL ELECTRICAL LEADING UP TO FINAL SERVICE HOT
11/30/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* OK TO CLEAR TEMP POWER SUBJECT TO BOND FOR TESTING POWER OBTAINED THRU PERMIT OFFICE
OK TO ENERGIZE PANEL ??? AFTER BONDING JUMPER INSTALLED A TRANSFORMER OK TO ENERGIZE PANEL " Y"
NOTE: BOND BUILDING STEEL AND CONDUCT TEST FOR SERVICE GFCI PER EQUIPMENT INSTRUCTIONS
11/08/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*COULD NOT LOCATE CONTR. RECALL INSP
10/28/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/18/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK ROUGH WALLS AT STAGE BASEMENT AREA.
08/04/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CALL BACK WHEN ACCESSIBLE
06/21/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* ORCHESTRA PIT-PVC CONDUITS FOR COMM, SOUND & POWER.
06/16/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/19/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ROUGH IN OF TECH ROOM AND WIRING OF 2 PANELS IN BASEMENT STORAGE
04/15/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*RMS. 102, 103, 105
04/08/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* BASEMENT LEVEL ROOMS 004, 002, 005, STORAGE & BATHROOM
03/18/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* 1) ROUGH WALLS OK TO COVER BASEMENT LOUNGE RM 001.
01/30/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*