Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM05695
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
12/28/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) EMERGENCY SYSTEM NOT COMPLETE AS OF 2:30 P.M. |
|
12/27/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*EQUIPMENT GROUND'S UNDER SIZED " DPB" TO DINNER RACK MAKE SURE TO CONNECT EQUIPMENT GROUND WHEN HANGING LIGHT FIXTURES REPAIR BONDING BUSHING IN TRANSFORMER " T2" GENERATOR NOT STARTING @ THIS POINT NOTE: SERVICE GFI TEST AND TORQUE REPORTS HANDED IN TODAY. |
|
12/15/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*NO INSPECTION REQUESTED TODAY, TOUCHED BASE WITH ROB, WALKED AROUND, LOOKED AT ROOF TOP CHILLER AND GENERATOR, SWITCHGEAR ALL NOT WIRED YET, TOOK A LOOK DOWN IN THE DRESSING ROOM AREA'S. I HAVE SOME CONCERNS ABOUT RACEWAY SUPPORT, ACCESS TO J-BOX'S AND J-BOX SIZE'S FOR CONDUCTOR FILL AND BENDING RADIUS. | |
12/08/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*TALKED TO JEFF-ELECTRICAL CONTRACTOR NO IN TODAY, TRANSFORMERS NOT FINISHED | |
12/06/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*WALKED THROUGH WITH ROB ( ELECTRICAL FOREMAN) HE WILL START CALLING IN ALL ELECTRICAL LEADING UP TO FINAL SERVICE HOT | |
11/30/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO CLEAR TEMP POWER SUBJECT TO BOND FOR TESTING POWER OBTAINED THRU PERMIT OFFICE OK TO ENERGIZE PANEL ??? AFTER BONDING JUMPER INSTALLED A TRANSFORMER OK TO ENERGIZE PANEL " Y" NOTE: BOND BUILDING STEEL AND CONDUCT TEST FOR SERVICE GFCI PER EQUIPMENT INSTRUCTIONS |
|
11/08/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*COULD NOT LOCATE CONTR. RECALL INSP |
|
10/28/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/18/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK ROUGH WALLS AT STAGE BASEMENT AREA. | |
08/04/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CALL BACK WHEN ACCESSIBLE |
|
06/21/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ORCHESTRA PIT-PVC CONDUITS FOR COMM, SOUND & POWER. | |
06/16/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/19/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ROUGH IN OF TECH ROOM AND WIRING OF 2 PANELS IN BASEMENT STORAGE |
|
04/15/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*RMS. 102, 103, 105 | |
04/08/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BASEMENT LEVEL ROOMS 004, 002, 005, STORAGE & BATHROOM | |
03/18/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ROUGH WALLS OK TO COVER BASEMENT LOUNGE RM 001. | |
01/30/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |